Automated Logic U253 Скачать руководство пользователя страница 8

Revised 8/14/02 • U253

8

© 2002 Automated Logic Corporation

Refer to the section “Writing GFBs for the 
U253” on page 9
 for more information about 
using a LogiStat sensor.

Digital Output Wiring

The U253 has two digital outputs that can be 
connected to a maximum of 24 Volts AC/DC 
(see Figure 9). Each output is a dry contact 
(rated at 1A maximum) that is configured as 
normally open.

Be sure the module’s power is off before 
connecting any inputs or outputs.

To verify each output’s operation, lock the 
output to a known condition using the 
Function Block’s Properties page in WebCTRL 
or the Parameter page in SuperVision, then 
make sure the equipment operates as 
specified.

Analog Output Wiring

The U253 has three analog outputs that 
support voltage devices from 0 to 10VDC (see 
Figure 10). The device being controlled must 
have a minimum of 2000 Ohms resistance 
measured from its input to ground and must 

Be sure the U253’s power is off before wiring 
any inputs or outputs. Connect the output 
wiring to the screw terminals on the module. 

To verify each output’s operation, lock the 
output to a known condition on the Function 
Block’s Properties page in WebCTRL or the 
Parameter page in SuperVision, then make 
sure the equipment operates as specified.

Using Flow Sensors

The U253 controls air flow in the zone using:

• a USF (single) air flow sensor and an 

actuator connected to two digital 
outputs

If you use a flow sensor with the U253, use 
the Airflow microblock in the U253’s GFB.

To connect the sensor, make sure the U253’s 
power is off first. Attach the total or high 
pressure line from the VAV box to the 
module’s HI side, and attach the static 
pressure line to the module’s LO side. 
Connect the USF to the U253 as shown in 
Figure 11 on page 9. 

To ensure an accurate reading from the flow 
sensor, use the Airflow microblock in the 
module’s GFB. You must calibrate this 
microblock using the instructions on the FB’s 
Properties page in WebCTRL or Parameter 
page in SuperVision. Refer to the 

Eikon for 

WebCTRL Microblock Reference Guide

 or the 

Eikon Microblock Reference Guide 

for more 

information.

 

 Figure 8. Flip Lever Wiring

 Figure 9. Digital Output Wiring

2. Press black

tab down to
connect wire

1. Insert wire

into opening

DO

DO

BUSS

DO-1

DO-2

24VAC

Gnd

+

 Figure 10. Analog Output Wiring

0 to 10V

+

-

Gnd

AO-1

Содержание U253

Страница 1: ...d trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions U253 Using the U253 2 Specifications 2 Job Start Up 3 Job Start Up for WebC...

Страница 2: ...n User s Guide for more information NOTE To operate this module based on a schedule the UNI must be networked with a gateway module U253 modules have been designed to meet low end high volume terminal...

Страница 3: ...NI 16 with the U1M module driver UNI 30 with the U3M module driver UNI 32 with the UNM module driver or UNI 59 with the U5M module driver Eikon 3 0a or later U Line Zone GFBs If you have InterOp Tools...

Страница 4: ...bCTRL or on the UNI Status page in SuperVision Power Wiring The Unet follows the same specifications as a legacy CMnet Refer to the Technical Handbook for details on legacy CMnets Also refer to the Te...

Страница 5: ...s you should have a PROT485 within 250 feet of any U line module on the Unet for surge protection However depending on the frequency of electrical surges in your area the 250 foot recommendation may v...

Страница 6: ...PT using the Supplemental Power 5V dc connection see Figure 6 on page 7 and the special power cable to a laptop keyboard jack or an external supply such as a 5V dc transformer 3 Define the connection...

Страница 7: ...0 5mA maximum sense current when the contacts are closed No pulse accumulation inputs are allowed in U253 FBs except for the override button on the LogiStat Using the LogiStat Use Figure 7 and Figure...

Страница 8: ...utput s operation lock the output to a known condition on the Function Block s Properties page in WebCTRL or the Parameter page in SuperVision then make sure the equipment operates as specified Using...

Страница 9: ...he DRV_UNI16 or DRV_UNI32 module driver For SuperVision systems the U1M U3M UNM or U5M module driver When using a LogiStat sensor with the U253 include a LogiStat microblock and a Zone Control microbl...

Страница 10: ...e in SuperVision LEDs The U253 modules have diagnostic LEDs to assist troubleshooting Table 2 Digital Outputs I O Type Signal Type Channel Number DO 1 Digital 11 DO 2 Digital 12 Table 3 Inputs I O Typ...

Страница 11: ...report for the module in WebCTRL or SuperVision Refer to the appropriate user s guide for more information about the module status report A sticker on the back of the module also shows the date the mo...

Отзывы: