Page 7
AC4100-0036 Rev. 19 3/2018
4100ES Network Display Units with SPS Power Supplies for 4120 Network
NDU Equipment Selection
Table 2: NDU Equipment Selection
Model
Description
Size
Supv.
Alarm
A100-1291
Remote Unit Interface module (RUI); up to three maximum per
control panel
1 Slot
85 mA
85 mA
A100-6031
City Circuit, with
disconnect switches
For SPS only,
maximum 1 per
panel
Maximum 1 per
SPS or RPS
N.A.
20 mA
36 mA
A100-6032
City Circuit, without
disconnect switches
For SPS only,
maximum 1 per
panel
Maximum 1 per
SPS or RPS
N.A.
20 mA
36 mA
A100-6033
Alarm/Supv/Tbl Relay, 3 Form C relays, 2 A
@ 32 VDC
Maximum 1 per
SPS or RPS
N.A
15 mA
37 mA
A100-6038
Dual RS-232 Interface; 3 maximum; can mount in Slot 3 or Slot
2 of Master Controller
1 Slot
60 mA
60 mA
A100-6046
Dual Port RS-232 standard interface (4 x 5 module)
1 Block
60 mA
60 mA
A100-6052
DACT, Point or Event Reporting; includes 2, 14 ft (4.3 m) DACT
cables
1 Slot
30 mA
40 mA
A100-0156
8 VDC Converter, required for multiple Physical Bridge Modules;
3 A @ 8 VDC maximum
1 Block
included with loads
A100-9816
Master Clock Interface Module with one standard RS-232 port
(see AC4100-0033)
1 Slot
132 mA
132 mA
A100-6079
Safelinc internet interface module
2 Slots
145 mA
145 mA
Table 3: Network Display Unit, Non-Voice*
SKU
SKU Type/Listing
Description
Supv.
Alarm
A100-9141 120 VAC Input
UL
4100ES NDU with Master Controller
, LCD display and operator interface;
Network Interface Module (select media cards separately), Standard Master
Controller CPU Module with RUI output communications interface; 9 A System
Power Supply (SPS) with battery charger, one 2 A Auxiliary Power output and
expansion slot for City Circuit or Alarm/Supv/Tbl Relay option (NOTE: SPS IDNet
channel, NACs and Aux Relay are disabled in NDU bay).
419 mA
476 mA
A100-9241 220-240 VAC Input UL
4100ES NDU with Master Controller
, LCD display and operator interface;
Network Interface Module (select media cards separately), Standard Master
Controller CPU Module with RUI output communications interface; 9 A System
Power Supply (SPS) with battery charger, one 2 A Auxiliary Power output and
expansion slot for City Circuit or Alarm/Supv/Tbl Relay option (NOTE: SPS IDNet
channel, NACs and Aux Relay are disabled in NDU bay).
see
NDU, or NDU with
VCC Communication
Modules (with
exceptions as noted)
for selected Network
Media Card current
Table 4: Network Display Unit with Voice Command Center (VCC)*
SKU
SKU Type/Listing
Description
Supv. Alarm
A100-9142
120 VAC Input
UL
4100ES NDU with VCC includes the first bay equipment described for the NDU (above)
and a second bay assembly with separate: Network Interface Module (select media
cards separately); Standard Master Controller CPU with RUI output communications
interface; 9 A System Power Supply (SPS) with battery charger, three 3 A Class A/B
NACs, one 2 A Auxiliary Power output, one Aux Relay and expansion slot for City Circuit
or Alarm/Supv/Tbl Relay option
828 mA 907 mA
A100-9242
220-240 VAC Input
UL
4100ES NDU with VCC includes the first bay equipment described for the NDU (above)
and a second bay assembly with separate: Network Interface Module (select media
cards separately); Standard Master Controller CPU with RUI output communications
interface; 9 A System Power Supply (SPS) with battery charger, three 3 A Class A/B
NACs, one 2 A Auxiliary Power output, one Aux Relay and expansion slot for City Circuit
or Alarm/Supv/Tbl Relay option
see
NDU, or
NDU with VCC
Communication
Modules (with
exceptions
as noted)
for selected
Network Media
Card current
Table 5: System Option for Seismic Compliance
SKU
Description
A100-7912
System option for Seismic compliance, provides additional stabilizer brackets required for legacy style cards
Note:
* For InfoAlarm Command Center expanded content display products, refer to data sheet
AC4100-0045
.