background image

4100ES Network Display Units with SPS Power Supplies for 4120 Network

Page 3

AC4100-0036 Rev. 19 3/2018

master controller includes analog values for: battery voltage, charger

voltage and current, actual system voltage and current, and individual

NAC currents

• Low battery cutout is selectable for each SPS power supply, Canadian

models are shipped selected, other models are shipped unselected is

selectable for detector reset, door holder, or coded output operation

• Outputs are power-limited, except for the battery charger
• 2 A auxiliary power output selectable for detector reset, door holder,

or coded output operation

Optional SPS modules (select one)

• Optional city connect module (A100-6031, with disc. switches, or

A100-6032, without disc. switches) can be selected for conventional

dual circuit city connections

• Optional alarm relay module (A100-6033) provides three C type relays

for alarm, trouble, and supervisory, rated 2 A resistive @ 32 VDC

Packaging Availability

• Modules are power-limited (unless specifically noted otherwise)
• Enclosure are available for one, two, or three bay sizes or for cabinet

rack mounting

• Additional cabinets can be mounted close-nippled for module

expansion

• NEMA 1/IP30 boxes, doors with tempered glass inserts, and dress

panels are available in platinum or red (ordered separately)

• Cabinet assembly design has been seismic tested and is certified to

IBC and CBC standards as well as to ASCE 7 categories A through F,

requires A100-7912 option for additional legacy card stabilizer brackets

and battery brackets as detailed on data sheet 

 AC2081-0019

• Refer to data sheet 

 AC4100-0037 

 for enclosure details

Software Feature Summary

• Selectable service override allows authorized operators to clear alarm

conditions during System Reset even if status has gone to trouble

before reset occurred

• Duplicate address error detection
• Convenient PC programming using a Microsoft Windows user interface

based program

Содержание 4100ES

Страница 1: ... port NDU field installed option modules include DACT and City Connection Service modems for remote panel status inquiry RS 232 ports for printers or maintenance terminals Alarm relays and expansion power supplies SafeLINC Internet Interface Battery brackets for seismic area protection For NDU with VCC Optional features are similar to a networked fire alarm control panel and an extensive list of m...

Страница 2: ...UI communications output configurable for isolated or un isolated operation supports up to 31 devices per master controller at up to 2500 ft 762 m for single run or 10 000 ft 3048 m total if wiring is Class B and T tapped If more distance is required up to four total RUI channels are supported per master controller up to three A100 1291 RUI expansion modules may be added A100 1291 provides un isol...

Страница 3: ... type relays for alarm trouble and supervisory rated 2 A resistive 32 VDC Packaging Availability Modules are power limited unless specifically noted otherwise Enclosure are available for one two or three bay sizes or for cabinet rack mounting Additional cabinets can be mounted close nippled for module expansion NEMA 1 IP30 boxes doors with tempered glass inserts and dress panels are available in p...

Страница 4: ...k interface card supports Class B or X operation Maximum of 1 left port and 1 right port duplex fiber media card per modular network interface card field connections require left port to right port pairing Order fiber media service kits for retrofit jobs where ST connectors are already installed refer to data sheet AC4100 0056 for full fiber media module specifications and retrofit information N A...

Страница 5: ...he glass window allows viewing of the display status LEDs and available operator switches Features include a two line by 40 character wide viewing angle super twist LCD with status LEDs and switches as shown in Operator Interface Features LED indicators describe the general category of activity being displayed with the LCD providing more detail For the authorized user unlocking the door provides a...

Страница 6: ...s provided using a logical menu driven display Multiple automatic and manual diagnostics for maintenance reduction Alarm and Trouble History Logs up to 1250 entries for each 2500 total events are available for viewing from the LCD or capable of being printed to a connected printer or downloaded to a service computer Convenient PC programmer label editing Password access control ...

Страница 7: ... VAC Input UL 4100ES NDU with Master Controller LCD display and operator interface Network Interface Module select media cards separately Standard Master Controller CPU Module with RUI output communications interface 9 A System Power Supply SPS with battery charger one 2 A Auxiliary Power output and expansion slot for City Circuit or Alarm Supv Tbl Relay option NOTE SPS IDNet channel NACs and Aux ...

Страница 8: ...x 50 50 W Amplifier constant supervision compatible Includes three on board Class B audio NACs power is supplied from an XPS RPS or SPS NAC rating 0 707 A 50 W or 100 speakers Table 8 100 W Analog Amplifiers with Power Supply Constant Supervision Compatible SKU Output Voltage 25 VRMS 70 7 VRMS Power Supply Input Listing Description Details A100 1314 A100 1315 120 VAC 60 Hz UL A100 1318 A100 1319 2...

Страница 9: ...o Red on top Yellow on bottom A100 1283 Two Yellow top and bottom 16 A100 1284 Two Red on top Green on bottom 8 A100 1285 One Red A100 1278 One 8 Red on left 8 Yellow on right 16 16 A100 1287 One Red 24 24 Table 14 LED Switch Modules Special Purpose LED switch controller and label kit is ordered separately Model Operation A100 1286 Eight function HOA On Off Auto Control Module with labeled switche...

Страница 10: ... 5152 12 VDC Power Option 2 A 12 VDC maximum 1 Block 1 5 A maximum A100 0634 120 VAC A100 0635 220 230 240 VAC Power Distribution Module PDM select per system voltage one required per box or cabinet rack VCC Additional Options SKU Description A100 6034 Door Tamper Switch with built in addressable IDNet IAM one per cabinet assembly if required A100 2320 Audio Bay to Bay Interconnection Harness Kit ...

Страница 11: ... max in a row between LED switch modules A100 2300 Expansion Bay Hardware order for each expansion bay unless included with selected option A100 0636 Box Interconnection Harness Kit order one for each close nippled cabinet A100 0632 Terminal Block Module 2 16 position terminal blocks mounted on 4 x 5 single block size for up to 12 AWG wire 3 31 mm2 A100 5128 Battery Distribution Terminal Block mou...

Страница 12: ...ference Note A system ground must be provided for Earth Detection and transient protection devices This connection shall be made to an approved dedi cated Earth connection per NFPA 70 Article 250 and NFPA 780 Additional 4100ES Technical Reference Table 18 Additional technical documents Document Document Number Installation Instructions 574 848AC Operating Instructions 579 197AC ...

Страница 13: ...urs per UL Standard 864 to 70 capacity in 12 hours per ULC Standard S527 Operating Temperature Range 32 to 120 F 0 to 49 C Environmental Operating Humidity Range Up to 93 RH non condensing 90 F 32 C maximum Additional 4100ES and 4120 Network Product Reference Subject Data Sheet Serial DACT SDACT for 4100ES 4010ES 4007ES AC2080 0009 Battery and Battery Cabinet Reference for 4100ES AC2081 0006 110 A...

Страница 14: ...cable contact your local Autocall product supplier for the latest status Listings and approvals under Tyco Fire Security GmbH and the product names listed in this material are marks and or registered marks Unauthorized use is strictly prohibited NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association NFPA 4100ES Network Display Units with SPS Powe...