background image

Page 9

AC4100-0036 Rev. 19 3/2018

4100ES Network Display Units with SPS Power Supplies for 4120 Network

Table 11: Options for use with either Analog or Digital Amplifiers*

SKU

Description

SKU

Description

A100-1245

Flex-35/50 NAC Expansion Module; (Adds 3 Class B, 1.5

A NACs)

A100-1248

100 W Amplifier NAC Expansion Module; (Adds six Class B, 2 A

NACs)

A100-1246

Flex-35/50 Class A Adapter for 3 NACs

A100-1249

100 W Amplifier Class A Adapter Module for 6 NACs

Note: 

* Refer to document 

 AC4100-0034 

 for additional audio module information.

Table 12: Options for either Analog or Digital Systems

SKU

Description

SKU

Description

Options for either Analog or Digital Systems (refer to data sheet 

 AC4100-0034 

 for additional module details)

A100-1259

Constant Supervision Adapter for 25 VRMS Amplifiers

A100-5116

Expansion Signal Module; three, 1.5 A NACs

A100-1260

Constant Supervision Adapter for 70.7 VRMS Amplifiers

A100-1266

NAC Extender

A100-1240

Auxiliary Audio Input Module; four additional inputs

A100-1267

Class A Adapter

A100-1241

8 Minute Message Expansion Module

A100-1268

Constant Supervision Adapter

Options for use with

Expansion Signal

Module

A100-1242

32 Minute Message Expansion Module

A4081-9018 End-of-line resistor for 70.7 VRMS NACs; 10 kΩ, 1 W

A100-0623

Network Audio Riser Controller Module for control of analog (-0621) or digital (-0622) riser module, see 

 AC4100-0034 

 for details

NDU with VCC, LED/Switch Modules

Note: 

 Refer to 

 AC4100-0032 

 for additional detail.

Table 13: LED/Switch Modules, General Purpose (LED/switch controller and label kit is ordered separately)

Model

LEDs per Switch

LED Color(s)

LED Quantity

Switch Quantity

A100-1276

Red; pluggable

8

A100-1277

LEDs only

Red on top, Yellow on bottom, pluggable

16

LEDs only

A100-1280

One

Red

A100-1281

One

Yellow

8

A100-1282

Two

Red on top, Yellow on bottom

A100-1283

Two

Yellow, top and bottom

16

A100-1284

Two

Red on top, Green on bottom

8

A100-1285

One

Red

A100-1278

One

8 Red on left, 8 Yellow on right

16

16

A100-1287

One

Red

24

24

Table 14: LED/Switch Modules, Special Purpose (LED/switch controller and label kit is ordered separately)

Model

Operation

A100-1286

Eight function HOA (On, Off, Auto) Control Module with labeled switches; ON/OFF/Auto; Green/Red/Green LEDs

Table 15: LED/Switch Controller Modules and Accessories

Model

Description

A100-1288

64 LED/64 Switch Controller Module with mounting plate; controls up to 64 LEDs

and interfaces to up to 64 switches; mounts behind the LED/switch modules and

has provisions for one A100-1289 Controller Module

A100-1289

64 LED/64 Switch Controller Module without mounting plate; mounts on extra

space of A100-1288; controls an additional 64 LEDs and 64 switches

Note:

LED/switch controllers and their connected LED/

switch modules must be in the same bay; refer

to data sheet for additional LED/Switch module

details when Flex-35/50 amplifiers are in the same

bay

4100-1294

LED/Switch Module Slide-in Labels, required when LED/switch modules are present; order one per cabinet

Table 16: LED kits for A100-1276 and A100-1277 modules

Model

Color

Description

4100-9843

Yellow

4100-9844

Green

4100-9845

Red

Kits of 8 LEDs; order as required for A100-1276 and A100-1277 modules

Additional Expansion and Remote Power Supplies and Accessories

SKU

Voltage/Listing

Description

Size

Supv.

Alarm

A100-5101

120 VAC

UL

Expansion Power Supply (XPS)

; 9 A output rated same as SPS, 3

built-in 3 A Class A/B NACs that can provide synchronized strobe or

SmartSync, two-wire operation

2 Blocks 50 mA

50 mA

A100-5102

220-240 VAC

UL

Expansion Power Supply (XPS); 9 A output rated same as SPS, 3

built-in 3 A Class A/B NACs that can provide synchronized strobe or

SmartSync, two-wire operation

2 Blocks 50 mA

50 mA

A100-5115

NAC Expansion Module, 3 NACs, Class A/B, 

mounts on XPS only

N.A.

25 mA

25 mA

Содержание 4100ES

Страница 1: ... port NDU field installed option modules include DACT and City Connection Service modems for remote panel status inquiry RS 232 ports for printers or maintenance terminals Alarm relays and expansion power supplies SafeLINC Internet Interface Battery brackets for seismic area protection For NDU with VCC Optional features are similar to a networked fire alarm control panel and an extensive list of m...

Страница 2: ...UI communications output configurable for isolated or un isolated operation supports up to 31 devices per master controller at up to 2500 ft 762 m for single run or 10 000 ft 3048 m total if wiring is Class B and T tapped If more distance is required up to four total RUI channels are supported per master controller up to three A100 1291 RUI expansion modules may be added A100 1291 provides un isol...

Страница 3: ... type relays for alarm trouble and supervisory rated 2 A resistive 32 VDC Packaging Availability Modules are power limited unless specifically noted otherwise Enclosure are available for one two or three bay sizes or for cabinet rack mounting Additional cabinets can be mounted close nippled for module expansion NEMA 1 IP30 boxes doors with tempered glass inserts and dress panels are available in p...

Страница 4: ...k interface card supports Class B or X operation Maximum of 1 left port and 1 right port duplex fiber media card per modular network interface card field connections require left port to right port pairing Order fiber media service kits for retrofit jobs where ST connectors are already installed refer to data sheet AC4100 0056 for full fiber media module specifications and retrofit information N A...

Страница 5: ...he glass window allows viewing of the display status LEDs and available operator switches Features include a two line by 40 character wide viewing angle super twist LCD with status LEDs and switches as shown in Operator Interface Features LED indicators describe the general category of activity being displayed with the LCD providing more detail For the authorized user unlocking the door provides a...

Страница 6: ...s provided using a logical menu driven display Multiple automatic and manual diagnostics for maintenance reduction Alarm and Trouble History Logs up to 1250 entries for each 2500 total events are available for viewing from the LCD or capable of being printed to a connected printer or downloaded to a service computer Convenient PC programmer label editing Password access control ...

Страница 7: ... VAC Input UL 4100ES NDU with Master Controller LCD display and operator interface Network Interface Module select media cards separately Standard Master Controller CPU Module with RUI output communications interface 9 A System Power Supply SPS with battery charger one 2 A Auxiliary Power output and expansion slot for City Circuit or Alarm Supv Tbl Relay option NOTE SPS IDNet channel NACs and Aux ...

Страница 8: ...x 50 50 W Amplifier constant supervision compatible Includes three on board Class B audio NACs power is supplied from an XPS RPS or SPS NAC rating 0 707 A 50 W or 100 speakers Table 8 100 W Analog Amplifiers with Power Supply Constant Supervision Compatible SKU Output Voltage 25 VRMS 70 7 VRMS Power Supply Input Listing Description Details A100 1314 A100 1315 120 VAC 60 Hz UL A100 1318 A100 1319 2...

Страница 9: ...o Red on top Yellow on bottom A100 1283 Two Yellow top and bottom 16 A100 1284 Two Red on top Green on bottom 8 A100 1285 One Red A100 1278 One 8 Red on left 8 Yellow on right 16 16 A100 1287 One Red 24 24 Table 14 LED Switch Modules Special Purpose LED switch controller and label kit is ordered separately Model Operation A100 1286 Eight function HOA On Off Auto Control Module with labeled switche...

Страница 10: ... 5152 12 VDC Power Option 2 A 12 VDC maximum 1 Block 1 5 A maximum A100 0634 120 VAC A100 0635 220 230 240 VAC Power Distribution Module PDM select per system voltage one required per box or cabinet rack VCC Additional Options SKU Description A100 6034 Door Tamper Switch with built in addressable IDNet IAM one per cabinet assembly if required A100 2320 Audio Bay to Bay Interconnection Harness Kit ...

Страница 11: ... max in a row between LED switch modules A100 2300 Expansion Bay Hardware order for each expansion bay unless included with selected option A100 0636 Box Interconnection Harness Kit order one for each close nippled cabinet A100 0632 Terminal Block Module 2 16 position terminal blocks mounted on 4 x 5 single block size for up to 12 AWG wire 3 31 mm2 A100 5128 Battery Distribution Terminal Block mou...

Страница 12: ...ference Note A system ground must be provided for Earth Detection and transient protection devices This connection shall be made to an approved dedi cated Earth connection per NFPA 70 Article 250 and NFPA 780 Additional 4100ES Technical Reference Table 18 Additional technical documents Document Document Number Installation Instructions 574 848AC Operating Instructions 579 197AC ...

Страница 13: ...urs per UL Standard 864 to 70 capacity in 12 hours per ULC Standard S527 Operating Temperature Range 32 to 120 F 0 to 49 C Environmental Operating Humidity Range Up to 93 RH non condensing 90 F 32 C maximum Additional 4100ES and 4120 Network Product Reference Subject Data Sheet Serial DACT SDACT for 4100ES 4010ES 4007ES AC2080 0009 Battery and Battery Cabinet Reference for 4100ES AC2081 0006 110 A...

Страница 14: ...cable contact your local Autocall product supplier for the latest status Listings and approvals under Tyco Fire Security GmbH and the product names listed in this material are marks and or registered marks Unauthorized use is strictly prohibited NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association NFPA 4100ES Network Display Units with SPS Powe...

Отзывы: