5.2 I/O Cabinet
Configuration setting for the networked I/O Cabinets.
5.2.1 Network
Set the IP address of the I/O Cabinet in the network. The default IP address for an I/O
cabinet is 192.168.0.11.
The Marine Watch system currently supports connection with up to four I/O Cabinets. In
each I/O Cabinet, locate the bus coupler and set the rotary switches S1 and S2 as follows:
Page 31 (49)
I/O Cabinet
S1
S2
IP address
I/O Cabinet 1 (default)
1
1
192.168.0.11
I/O Cabinet 2
1
2
192.168.0.12
I/O Cabinet 3
1
3
192.168.0.13
I/O Cabinet 4
1
4
192.168.0.14
Make sure to reboot the I/O Cabinet after any changes to the S1 or S2 rotary
switches.