One channel can source a maximum of 2 A. However, there is a maximum of 2 A in total for
the I/O module including the standard output channels.
The optional two output I/O modules can source a maximum of 2 A in total.
7.6 Alarm Panel Supply
The I/O Cabinet has circuit breaker 4Q35 reserved for 24 V / 2 A power to one external
alarm panel.
Additional alarm panels need a separate power arrangement.
Page 49 (49)
Switch output channel
Connections
1
00 – 10
2
01 – 11
3
02 – 12
etc.
...