Oscillating Prelube
enables the oscillating prelube.
Oscillating On Time
sets the number of seconds the DCU shall lubricate the engine. Typical
setting is 60 seconds.
Oscillating Off Time
sets the number of minutes between each lubrication action. Typical
setting is 60 minutes.
Oscillating Feedback
selects if feedback from the oscillating prelube is required. The
feedback will have to be connected to prelube complete.
Oscillating Feedback Time
sets the time for oscillating feedback failed warning, Prelube
Failure.
Prelube Complete Signal
Prelube Complete Source
selects the channel to be used as a prelube complete indication.
This is typically the “Prelube Complete Switch” input signal, but can be changed if needed.
The prelube complete signal is used for both normal prelube and oscillating
prelube.
Postlube
The DCU can be configured to postlube the engine at stopping. Postlubing takes place in
Stopping and Stopped state.
Postlube Type
enables the postlube. Selectable choices are
No Postlube
or
Fixed Time
.
Postlube Time
specifies the total time to postlude during a stop sequence.
Postlube RPM Threshold
specifies under which RPM level Postlubing should start during the
stop sequence of the engine.
Postlube Activate “Prelube Activation” Output
” selects whether postlube shall also activate
any “Prelube Activation” outputs.
Note, there’s an output function called Postlube Activation. This output function
can be used to signal an lube pump or similar to perform the actual postlubing.
Page 69 (99)