![AUTEC C26PRO SERIES Скачать руководство пользователя страница 18](http://html.mh-extra.com/html/autec/c26pro-series/c26pro-series_user-manual_3020248018.webp)
- 14 -
LIPROMA3-00
- 14 Diagnostics -
14
DIAGNOSTICS
If the system “radio remote c machine” does not start, check if the problem
is caused by the radio remote control or the machine. Therefore, before carrying out
any verification connect the alternative control unit: if the machine does not start, the
problem lies with the machine itself.
If, on the other hand, the machine only starts normally when started by the alterna-
tive control unit, the problem lies with the radio remote control. In this case, perform
the following checks.
Diagnostics of
transmitting
unit
Diagnostics of
receiving unit
Is the green
signalling LED
on flashing
slowly?
Is the green
signalling LED
flashing
quickly?
Is the red signalling
LED on with a steady
light?
Carry out
receiving unit
diagnostics.
Insert a battery
that is charged.
Deactivate, if active,
the actuator
and/or the STOP
pushbutton.
If the transmitting unit
does not switch on cor-
rectly,
CALL
TECHNICAL
ASSISTANCE
Is the POWER
light
on?
Is the connection plug
between the receiving
unit and the machine
connected correctly?
Correctly insert
the connection plug
and start the radio
remote control.
Carry out the
frequency change
procedure. Does the
machine start?
Disconnect
the receiving unit
and open it. Is the F1
fuse functional?
Replace the fuse.
Power and restart
the radio
remote control.
Is the
ENABLE
light on?
Disconnect
the receiving unit and
open it. Are the F2-F3
fuses functional?
Power and restart
the radio
remote control.
Replace the fuse.
Check the power
supply connections.
CALL
TECHNICAL
ASSISTANCE
CALL
TECHNICAL
ASSISTANCE