9
Assembly Instruction
KS 4 S12 24V DC
D
ata
Sheet
KS4 S12 24V DC r
a
umüller
chain drives have an integrated cable routing with connection sockets on both housing ends.
This enables the following options:
•
a
umüller
-Click
plug solution
with various cabel lengths
Part.-No.:
501250
- 1 m cable length /
501258
- 2 m cable length /
501251
- 3 m cable length /
501252
- 5 m cable length /
501253
- 10 m cable length
• Series connection of several drives into multi drive systems
• Power supply from both sides
S
L
235
15
5
35
24
R
(Right)
o
ption
TECHNICAL DATA
U
N
Rated voltage
24V DC (19 V ... 28 V)
I
N
Rated current
0,9 A
I
A
Cut-off current
1,2 A
P
N
Rated power
22 W
DC
Duty cycle
5 cycles (ED 30 % - ON: 3 min. / OFF: 7 min.)
Protection rating
IP 32
Ambient temperature range
-5 °C ... +60 °C
F
Z
Pulling force max.
400 N
F
A
Pushing force
max.
s > 600 mm only for pulling application
F
H
Pullout force
1.800 N (fastening depended)
Chain
Stainless steel, without protruding rivet heads.
Simple connection to casement brackets.
Small bending radii allow maximum opening angles
of small windows.
Connecting cable
non-halogen, grey 5 x 0,5 mm², ~ 2 m
v
Speed
s < 400
8,0 mm/s
8,0 mm/s
s > 400 – 600
12,0 mm/s
8,0 mm/s
s > 600
13,5 mm/s
8,0 mm/s
s
Stroke
50 – 1000 mm
L
Length
see order data
Feedback contact
limit position „CLOSE“ (max. 24 V, 500 mA)
Sound pressure level A
≤
70 dB (A)
Application: natural ventilation, RWA, ferralux®-NRWG
Internal intelligent cut-off switch S12
Feedback limit position „CLOSE“ (max. 24V, 500 mA)
Equipment:
Additional
A
umüller
-Click
plug set
for multi-drive operation
Options
Programmable special functions
Programmable feedback limit position „OPEN“ (max. 24V, 500 mA)
M-COM for automatic synchronised run of multi drive systems and automatic sequence
control with locking drives (S3 / S12)
50
100
250
150
200
300
350
400
F
Zug
Pull
Schub
Push
(N)
S
(mm)
0
500
600
700
800
1000
400
300
200
Connection
Connection
D
ata
s
heet
02
Содержание KS4 S12 24V DC R