Installation instruction
SHEV - Control Unit EMB 7300
S
AFETY
INSTRUCTIONS
Crush and shear points
To avoid injuries,
crushing and shear points
between
casement and frame must be secured
against entrapment
up to an installation height of 2,5 meters above the
fl oor
with appropriate measures. This can be achieved e.g.
by using contact-based or contactless protective devices
against entrapment, which stop the motion through contact
or through interruption by a person. A warning symbol at
the opening element must indicate this clearly.
Routing cables and electrical connection
Routing or installing electrical lines and connections may
be performed only by approved specialist companies. Never
operate drives, Control Units, operating elements and sen-
sors at operating voltages and connections contrary to the
specifi cations of the manufacturer.
!
W
ARNING
Area of application
The control device shall only be used according to its inten-
ded use. For additional applications consult the manufactu-
rer or his authorized dealer.
Installation
These instructions address expert and safety-conscious
electricians and / or qualifi ed personnel knowledgeable of
the electrical and mechanical installation of drives and con-
trol systems.
Mounting material
The required mounting material must be modifi ed to fi t the
occurring load.
S
AFETY
INSTRUCTIONS
It is important to follow these instruc-
tions for the safety of persons. These
instructions shall be kept in a safe place
for the entire service life of the products.
Risk of crushing and entrapment!
Electromotive operated windows can
close automatically!
The compressive force is absolutely
suffi cient to crush fi ngers in case of
carelessness.
01
The planning and calculation of the
wiring system is the responsibility of
the builder or his agent or the authori-
zed constructor and must be performed
according to the statutory provisions.
All relevant instructions shall be observed for the in-
stallation, specifi cally:
• VDE 0100 Setting up high-voltage systems up to 1000 V
• VDE 0815 Wiring cables
• Specimen Guideline on Conduits German designation
(MLAR).
N
OTE
We recommend using exclusively sys-
tem components by
A
UMÜLLER
, because
their compatibility is carefully checked
in the factory.
A
UMÜLLER
shall not assume
liability for the system-compatible func-
tioning of third party components.
Applications and connections other than
explicitly described in these instructions
require the express written consent of
A
UMÜLLER
. Utilization of applications and
components not expressly authorized by
A
UMÜLLER
are considered as unintended
use even if their perfect functioning is
proven at commissioning (e.g. approval
under building law).
N
OTE
Basic functions of SHEV (smoke and heat exhaust sys-
tem) control devices:
• Control of electromotive window drives for smoke
and heat exhaust in case of fi re and for “natural
ventilation”.
• Evaluation of trigger signals of manual and automatic
smoke detectors as well as of fi re alarm systems.
• Emergency power supply provided by batteries for main-
taining safety functions if power supply is interrupted in
case of fi re.
• Monitoring the power supply of all important con-
nections for malfunctions.
• Diverse automatic and manual control options for con-
trolling natural ventilation (e.g. via wind and rain
sensors).
• Transmission of signals of all essential operating states
for external evaluation (may require additional com-
ponents).
• Comfortable confi guration and parameterization of
control via PC software.
• Optional integration into external data bus systems via
dd-on
modules.