6

Installation instruction 

SHEV - Control Unit EMB 7300

S

AFETY

 

INSTRUCTIONS

Crush and shear points

To avoid injuries, 

crushing and shear points

 between

casement and frame must be secured 

against entrapment 

up to an installation height of 2,5 meters above the 
fl oor 

with appropriate measures. This can be achieved e.g. 

by using contact-based or contactless protective devices 
against entrapment, which stop the motion through contact 
or through interruption by a person. A warning symbol at 
the opening element must indicate this clearly. 

Routing cables and electrical connection 

Routing or installing electrical lines and connections may 
be performed only by approved specialist companies. Never 
operate drives, Control Units, operating elements and sen-
sors at operating voltages and connections contrary to the 
specifi cations of the manufacturer.

!

W

ARNING

Area of application

The control device shall only be used according to its inten-
ded use. For additional applications consult the manufactu-
rer or his authorized dealer.

Installation

These instructions address expert and safety-conscious 
electricians and / or qualifi ed personnel knowledgeable of 
the electrical and mechanical installation of drives and con-
trol systems.

Mounting material

The required mounting material must be modifi ed to fi t the 
occurring load.

S

AFETY

 

INSTRUCTIONS

It is important to follow these instruc-
tions for the safety of persons. These
instructions shall be kept in a safe place 
for the entire service life of the products.

Risk of crushing and entrapment! 
Electromotive operated windows can 
close automatically!
The compressive force is absolutely 
suffi cient to crush fi ngers in case of 
carelessness.

01

The planning and calculation of the
wiring system is the responsibility of 
the builder or his agent or the authori-
zed constructor and must be performed
according to the statutory provisions.

All relevant instructions shall be observed for the in-
stallation, specifi cally:
•  VDE 0100  Setting up high-voltage systems up to 1000 V
•  VDE 0815  Wiring cables
• Specimen Guideline on Conduits German designation

 (MLAR).

N

OTE

We recommend using exclusively sys-
tem components by 

A

UMÜLLER

, because 

their compatibility is carefully checked 
in the factory. 

A

UMÜLLER

 shall not assume

liability for the system-compatible func-
tioning of third party components.
Applications and connections other than 
explicitly described in these instructions 
require the express written consent of 

A

UMÜLLER

. Utilization of applications and 

components not expressly authorized by 

A

UMÜLLER

 are considered as unintended 

use even if their perfect functioning is 
proven at commissioning (e.g. approval 
under building law).

N

OTE

Basic functions of SHEV (smoke and heat exhaust sys-
tem) control devices:

•  Control of electromotive window drives for smoke
  and heat exhaust in case of fi re and for “natural
 ventilation”.
•  Evaluation of trigger signals of manual and automatic 
 

smoke detectors as well as of fi re alarm systems.

•  Emergency power supply provided by batteries for main-
 

taining safety functions if power supply is interrupted in 

 

case of fi re.

•  Monitoring the power supply of all important con-
 

nections for malfunctions. 

•  Diverse automatic and manual control options for con-
  trolling natural ventilation (e.g. via wind and rain
 sensors).
•  Transmission of signals of all essential operating states
  for external evaluation (may require additional com-
 ponents).
•  Comfortable confi guration and parameterization of
 

control via PC software. 

•  Optional integration into external data bus systems via 
 dd-on 

modules.

Содержание EMB 7300 Series

Страница 1: ...to EN12101 10 and control panel according to prEN12101 9 SHEV CONTROL UNIT EMB 7300 2 5 A 5 A 10 A 20 A tested electrical control device EMB 7300 with recognition number G 514001 Installation and Comm...

Страница 2: ...Maximal detector in drive line INSTALLATION STEP 3 Connection of automatic and manual smoke detectors INSTALLATION STEP 4 Connecting wind and rain sensors INSTALLATION STEP 5 Installing relay plug in...

Страница 3: ...nfiguration using the free software of the Control Unit manufacturer USB connection ABBREVIATIONS USB Scale units C Degree Celsius A Amps Ah Amp hours kg Kilogram m Metres min Minutes mm Millimeters N...

Страница 4: ...of application This control device is intended for power feeding and con trolling electromotive operated windows in facade and roof areas The prime task of this product in combination with the electr...

Страница 5: ...red and active light sensors or pressure mats Contact based anti trap protection 20 ZAA 8 2 Pressure sensitive safety switch strips or Motor current monitoring systems internal and external Hold to r...

Страница 6: ...carelessness 01 The planning and calculation of the wiring system is the responsibility of the builder or his agent or the authori zed constructor and must be performed according to the statutory pro...

Страница 7: ...Post warning signs During the proper assembly of drives with mounting elements at a window and the connection to an external Control Unit the interfaces resulting from mechanical and electrical perfor...

Страница 8: ...ER has no influence on a perfect systems environ ment or object specific systems configuration USB Declaration of Conformity The control device is manufactured and inspected for its intended use in ac...

Страница 9: ...ce free back up batteries 2x 12 V 2 3 Ah Part No 541000 Application Compact Control Unit for smoke and heat exhaust ventilation systems operating with 24V DC voltage suitable for staircases TECHNICAL...

Страница 10: ...ng steel sheet RAL 7035 light grey Dimensions WxHxD 400 x 300 x 150 mm Connection terminals 1 5 mm Drives 6 mm rigid wire Motherboard 1 SHEV group 2 Vent groups Application Compact Control Unit for sm...

Страница 11: ...285 x 122 mm Version 2 5A 5A 400 x 300 x 150 mm Version 10A 400 x 400 x 200 mm Version 20A PREPARING ASSEMBLY TECHNICAL DATA WARNING Important instructions for safe assembly Fully observe all instruct...

Страница 12: ...DC for smoke heat exhausting natural ventilation Input for ventilation line 1 max 10 vent buttons Output for drive line 2 only for EMB 7300 5 A 0102 10 A 0102 20 A 0102 Input for ventilation line 2 ma...

Страница 13: ...depend on the type of drive and on the number of drives Line length and cross section can be determined according to the following formula Formula to calculate the required wire cross section of a inf...

Страница 14: ...10 A nominal current EMB 7300 20 A 2X MAX 10 A nominal current SHEV release in case of fire overrides ventilation No ventilation in the event of a mains power supply failure battery operation SHEV rel...

Страница 15: ...s section of line in mm2 L line length in m I current of connected drives in A U line voltage drop 2 V DC A I L 2 U 56 mm2 total x x x length infeed line voltage drop V A m m mm2 Cable installation mu...

Страница 16: ...ECTION OF AUTOMATIC AND MANUAL SMOKE DETECTORS 04 OK 11 10 9 8 7 6 5 4 3 2 1 1 1 1 22 5 71 1 13 14 15 16 17 18 19 A S B 1 72 OK 11 10 9 8 7 6 5 4 3 2 1 10 k IN C O M O UT IN C O M O UT IN C O M OU T B...

Страница 17: ...n sensors is de activated Before mounting and positioning the wind rain sen sors carefully read the safety and assembly instructions provided with the products They are part of the system documentatio...

Страница 18: ...nstallation an connect when disconnected from the mains power supply Switch off power supply and secure against reconnection The motherboard has two slots for using one relay plug in card REL 65 each...

Страница 19: ...230V AC 50 60 Hz On the version with front mounted push button the connector may be removed Routing via external fuse and switching component PE BU BU BU 2 x back up battery 2 3 Ah 12V Ensure correct...

Страница 20: ...V VGG N L USB Do not remove cover F1 F2 F3 Switching power supply 5A RD RD RD RD RD L L Cover SMOKE VENT N N 225 mm 400 mm 285 mm 300 mm 10 A oder 400 mm 20 A Wiring duct 230V AC 50 60 Hz 230V AC 50...

Страница 21: ...free version of the system software version VIEW can be downloaded from the homepage www aumueller gmbh de The software can be installed on a computer notebook or net book Please pay regard to the har...

Страница 22: ...onents SHEV systems require a logbook in which all important master data have to be entered prior to operation enable and all operational events during the period in operation The logbook is part of t...

Страница 23: ...ged Indicator S has steady light open circuit or short circuit in manual fire alarm faulty power monitoring Indicator S blinks slowly open circuit or short circuit in smoke detector line faulty power...

Страница 24: ...B A Z A Z 1 32 33 35 36 37 A Z A Z 1 1 2 2 3 3 1 7 2 USB 1 REL65 2 REL65 BUS Module BUS Wind Rain RM HSE LT 2 F1 A A N N Drive 1 Stecker f r Front Button Drive 2 A Z Reset LT 1 Indicators GN Operatio...

Страница 25: ...the operator shall carry out or order a visual inspection at least once and document it in writing in the log book We recommend a maintenance contract with a specialist company authorized by the manu...

Страница 26: ...lowing Improper use of the product Improper installation commissioning operation maintenance or repair of the product Operating the product by defect and improper installed or not functioning safety a...

Страница 27: ...27 Installation instruction SHEV Control Unit EMB 7300 CERTIFICATES 08...

Страница 28: ...28 Installation instruction SHEV Control Unit EMB 7300 CERTIFICATES 08...

Страница 29: ...EMB 7300 CERTIFICATES THE VdS APPROVAL INCLUDES THE FOLLOWING CONTROL UNITS EMB 7300 without SHEV button EMB 7300 with orange SHEV button EMB 7300 without SHEV button EMB 7300 with orange SHEV button...

Страница 30: ...different Control Unit versions Remark Terminals Drive 1 Drive 2 only version 0102 CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE ZU Operation Fault COM COM OPEN OPEN OPEN OPEN OPEN OPEN Buttons Buttons Buttons...

Страница 31: ...free from mistakes and errors All information and data contained in this document are subject to alterations without prior notice Distribution and reproduction of this document as well as the use and...

Страница 32: ...n Tel 49 8271 8185 0 Fax 49 8271 8185 250 info aumueller gmbh de 9000017000_V0 1_KW05 14 www aumueller gmbh de AUM LLER AUMATIC GMBH Gemeindewald 11 86672 Thierhaupten Tel 49 8271 8185 0 Fax 49 8271 8...

Отзывы: