Aumuller EMB 7300 Series Скачать руководство пользователя страница 11

11

Installation instruction
SHEV - Control Unit EMB 7300

Electrical data and connected loads

Operating voltage, primary: 

Frequency: 

Nominal current (secundär) / 
Current consumption (primär): 

Current output 

(short-time duty)

Constant current consumption:

Output voltage, drives: 
Residual ripple: 

Number of detectors 
(manual / automatic): 
Line output: 
Battery voltage: 
Battery nominal capactiy: 

195…..253 V AC

50….60 Hz

Version 
Version    
Version
Version

Nominal current 30% max. duty ratio
30 % max. of nominal current 
(depending on version)

24V DC nominal (20….28 V DC)
max. 2,0 Vpp (Version 2,5 A)
max. 0,5 Vpp (Version 5 A, 10 A, 20 A)

10 units per detector line

18….26 V (detector voltage)
2 x 12 V
2,3 or 7,0 Ah (depending on version)

2,5 A / 0,4 A

     5A / 0,8 A

10 A / 1,3 A

20 A / 2,6A

Environmental Conditions (operation)

Ambient temperature 
range:
Maximum relative air 
humidity: 

-5…+40 °C 
(according to EN 12101 Class 1)
75 % (mean value over lifetime)
90 % (for max. 96 hours)

Mechanical Data

Surface mounted housing: 
Protection class: 

Housing dimensions 
(W x H x D): all dimen-
sions given without lock

steel plate painted in RAL 7035
IP 30 (Version 2,5A and 5A)
IP 54 (Version 10A and 20A), with wall 
mounting brackets and seal (not tested).
225 x 285 x 122 mm (Version 2,5A + 5A)
400 x 300 x 150 mm (Version 10A)
400 x 400 x 200 mm (Version 20A)

P

REPARING

 

ASSEMBLY

T

ECHNICAL

 D

ATA

!

W

ARNING

Important instructions for safe assembly:

 

Fully observe all instructions, incorrect assembly 
may lead to serious injuries.

Before starting the installation please check with the delivery note that 
the delivery is complete and correct, any complaints received later cannot 
be considered. It is required to keep a logbook for the EMB 7300 which 
must be accessible to authorized staff at all times.

The available internal emergency power supply (back-up 
batteries), if correctly rated and serviced at regular inter-
vals, ensures that the controller of the Control Unit mo-
ves the connected drives open at least twice and close 
at least once after 72 hours of mains power supply loss.

!

03

 

P

REPARING

 

ASSEMBLY

Scope of delivery: SHEV - Control Unit EMB 7300

without breakglass unit in the cover

•  Installation and Commissioning Instructions 
     (german and english)
•  Test report according to VDE 0113
• Label„Smoke 

Vent“

•  Stickers „ maintenance instructions“
•  Drive line end module
• Resistors
• Key

Scope of delivery: SHEV - Control Unit EMB 7300

with breakglass unit in the cover

•  Installation and Commissioning Instructions 
     (german and english)
•  Test report according to VDE 0113
• Label„Smoke 

Vent“

•  Stickers „ maintenance instructions“
•  Drive line end module
• Resistors
•  Key (2 unit)

Содержание EMB 7300 Series

Страница 1: ...to EN12101 10 and control panel according to prEN12101 9 SHEV CONTROL UNIT EMB 7300 2 5 A 5 A 10 A 20 A tested electrical control device EMB 7300 with recognition number G 514001 Installation and Comm...

Страница 2: ...Maximal detector in drive line INSTALLATION STEP 3 Connection of automatic and manual smoke detectors INSTALLATION STEP 4 Connecting wind and rain sensors INSTALLATION STEP 5 Installing relay plug in...

Страница 3: ...nfiguration using the free software of the Control Unit manufacturer USB connection ABBREVIATIONS USB Scale units C Degree Celsius A Amps Ah Amp hours kg Kilogram m Metres min Minutes mm Millimeters N...

Страница 4: ...of application This control device is intended for power feeding and con trolling electromotive operated windows in facade and roof areas The prime task of this product in combination with the electr...

Страница 5: ...red and active light sensors or pressure mats Contact based anti trap protection 20 ZAA 8 2 Pressure sensitive safety switch strips or Motor current monitoring systems internal and external Hold to r...

Страница 6: ...carelessness 01 The planning and calculation of the wiring system is the responsibility of the builder or his agent or the authori zed constructor and must be performed according to the statutory pro...

Страница 7: ...Post warning signs During the proper assembly of drives with mounting elements at a window and the connection to an external Control Unit the interfaces resulting from mechanical and electrical perfor...

Страница 8: ...ER has no influence on a perfect systems environ ment or object specific systems configuration USB Declaration of Conformity The control device is manufactured and inspected for its intended use in ac...

Страница 9: ...ce free back up batteries 2x 12 V 2 3 Ah Part No 541000 Application Compact Control Unit for smoke and heat exhaust ventilation systems operating with 24V DC voltage suitable for staircases TECHNICAL...

Страница 10: ...ng steel sheet RAL 7035 light grey Dimensions WxHxD 400 x 300 x 150 mm Connection terminals 1 5 mm Drives 6 mm rigid wire Motherboard 1 SHEV group 2 Vent groups Application Compact Control Unit for sm...

Страница 11: ...285 x 122 mm Version 2 5A 5A 400 x 300 x 150 mm Version 10A 400 x 400 x 200 mm Version 20A PREPARING ASSEMBLY TECHNICAL DATA WARNING Important instructions for safe assembly Fully observe all instruct...

Страница 12: ...DC for smoke heat exhausting natural ventilation Input for ventilation line 1 max 10 vent buttons Output for drive line 2 only for EMB 7300 5 A 0102 10 A 0102 20 A 0102 Input for ventilation line 2 ma...

Страница 13: ...depend on the type of drive and on the number of drives Line length and cross section can be determined according to the following formula Formula to calculate the required wire cross section of a inf...

Страница 14: ...10 A nominal current EMB 7300 20 A 2X MAX 10 A nominal current SHEV release in case of fire overrides ventilation No ventilation in the event of a mains power supply failure battery operation SHEV rel...

Страница 15: ...s section of line in mm2 L line length in m I current of connected drives in A U line voltage drop 2 V DC A I L 2 U 56 mm2 total x x x length infeed line voltage drop V A m m mm2 Cable installation mu...

Страница 16: ...ECTION OF AUTOMATIC AND MANUAL SMOKE DETECTORS 04 OK 11 10 9 8 7 6 5 4 3 2 1 1 1 1 22 5 71 1 13 14 15 16 17 18 19 A S B 1 72 OK 11 10 9 8 7 6 5 4 3 2 1 10 k IN C O M O UT IN C O M O UT IN C O M OU T B...

Страница 17: ...n sensors is de activated Before mounting and positioning the wind rain sen sors carefully read the safety and assembly instructions provided with the products They are part of the system documentatio...

Страница 18: ...nstallation an connect when disconnected from the mains power supply Switch off power supply and secure against reconnection The motherboard has two slots for using one relay plug in card REL 65 each...

Страница 19: ...230V AC 50 60 Hz On the version with front mounted push button the connector may be removed Routing via external fuse and switching component PE BU BU BU 2 x back up battery 2 3 Ah 12V Ensure correct...

Страница 20: ...V VGG N L USB Do not remove cover F1 F2 F3 Switching power supply 5A RD RD RD RD RD L L Cover SMOKE VENT N N 225 mm 400 mm 285 mm 300 mm 10 A oder 400 mm 20 A Wiring duct 230V AC 50 60 Hz 230V AC 50...

Страница 21: ...free version of the system software version VIEW can be downloaded from the homepage www aumueller gmbh de The software can be installed on a computer notebook or net book Please pay regard to the har...

Страница 22: ...onents SHEV systems require a logbook in which all important master data have to be entered prior to operation enable and all operational events during the period in operation The logbook is part of t...

Страница 23: ...ged Indicator S has steady light open circuit or short circuit in manual fire alarm faulty power monitoring Indicator S blinks slowly open circuit or short circuit in smoke detector line faulty power...

Страница 24: ...B A Z A Z 1 32 33 35 36 37 A Z A Z 1 1 2 2 3 3 1 7 2 USB 1 REL65 2 REL65 BUS Module BUS Wind Rain RM HSE LT 2 F1 A A N N Drive 1 Stecker f r Front Button Drive 2 A Z Reset LT 1 Indicators GN Operatio...

Страница 25: ...the operator shall carry out or order a visual inspection at least once and document it in writing in the log book We recommend a maintenance contract with a specialist company authorized by the manu...

Страница 26: ...lowing Improper use of the product Improper installation commissioning operation maintenance or repair of the product Operating the product by defect and improper installed or not functioning safety a...

Страница 27: ...27 Installation instruction SHEV Control Unit EMB 7300 CERTIFICATES 08...

Страница 28: ...28 Installation instruction SHEV Control Unit EMB 7300 CERTIFICATES 08...

Страница 29: ...EMB 7300 CERTIFICATES THE VdS APPROVAL INCLUDES THE FOLLOWING CONTROL UNITS EMB 7300 without SHEV button EMB 7300 with orange SHEV button EMB 7300 without SHEV button EMB 7300 with orange SHEV button...

Страница 30: ...different Control Unit versions Remark Terminals Drive 1 Drive 2 only version 0102 CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE ZU Operation Fault COM COM OPEN OPEN OPEN OPEN OPEN OPEN Buttons Buttons Buttons...

Страница 31: ...free from mistakes and errors All information and data contained in this document are subject to alterations without prior notice Distribution and reproduction of this document as well as the use and...

Страница 32: ...n Tel 49 8271 8185 0 Fax 49 8271 8185 250 info aumueller gmbh de 9000017000_V0 1_KW05 14 www aumueller gmbh de AUM LLER AUMATIC GMBH Gemeindewald 11 86672 Thierhaupten Tel 49 8271 8185 0 Fax 49 8271 8...

Отзывы: