Table 15:
Examples of possible settings
SVM/SVMR 07.5
SVM/SVMR 05.1/07.1
Output speed
Output drive
[rpm]
Output speed
Motor
[rpm]
Output speed via parameter:
Speed LOCAL
Speed REMOTE
or via fieldbus:
(
Speed fieldbus
=
External
)
Output speed
Output drive
[rpm]
Output speed
Motor
[rpm]
Output speed via parameter:
Speed LOCAL
Speed REMOTE
or via fieldbus:
(
Speed fieldbus
=
External
)
0.6
133
0.0 %
1.6
133
0.0 %
0.8
186
2.0 %
2.2
176
2.0 %
1.1
255
6.0 %
3.2
256
6.0 %
1.6
371
11.0 %
4
320
9.0 %
2.2
510
18.0 %
5.6
448
15.0 %
3.2
742
29.0 %
8
640
24.0 %
4.0
928
38.0 %
11
880
35.0 %
5.6
1,299
55.0 %
16
1,280
54.0 %
8.0
1,856
81.0 %
22
1,760
77.0 %
9.7
2,250
100.0 %
28.1
2,250
100.0 %
9.8.
Cover to controls: close
1.
Clean sealing faces of housing and cover.
2.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the sealing faces.
3.
Check whether seal is in good condition, replace seal if damaged.
4.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the seal and insert
it correctly.
5.
Place cover [1].
6.
Fasten screws evenly crosswise.
32
SVM 05.1 – SVM 07.5 / SVMR 05.1 – SVMR 07.5
Commissioning (basic settings of controls)
Modbus RTU