5.2.
Connection via bayonet connector
Figure 8: Arrangement of connections
[XK1] Power terminals (mains cables)
[XK2] Control contacts/fieldbus cables
↑
from previous device
[XK3] Control contacts/fieldbus cables
↓
to next device
Cross sections:
●
Power terminals: max. 1.5 mm² flexible
●
Control contacts: max. 1.5 mm² flexible
Hazardous voltage at open connector (capacitor discharge)!
Risk of electric shock.
→
After disconnecting the power supply (removing connector for power terminals),
wait at least 5 seconds before touching the pins/sockets.
5.2.1.
Mains and fieldbus cables: connect
Observe prior to connec-
tion
●
Observe permissible cross sections of connectors used.
●
Use suitable crimping tools to connect wires:
-
For bayonet connectors:
e.g. Cannon four indent crimping tool
●
Observe operation instructions of the connector manufacturer.
●
Upon request, AUMA provide suitable connection sets.
●
For further information refer to separate "Technical data Connector".
●
Observe characteristics of network topology used.
15
SVM 05.1 – SVM 07.5 / SVMR 05.1 – SVMR 07.5
Modbus RTU
Electrical connection