Figure 15: Local controls
[1]
Push button OPEN
[2]
Push button STOP - operation mode LOCAL/REMOTE
[3]
Push button CLOSE
[4]
Indication light for operation mode LOCAL (blue)
Hot surfaces, e.g. possibly caused by high ambient temperatures or strong
direct sunlight!
Danger of burns
→
Verify surface temperature and wear protective gloves.
Activate operation mode LOCAL:
→
Hold down push button [2] for approx. 3 seconds until the indication light [4] is
blinking in blue.
➥
If the right indication light is blinking in blue, the actuator can be operated via
push buttons [1 – 3]:
-
Run actuator in direction OPEN: Press push button OPEN [1].
-
Stop actuator: Press push button STOP [2].
-
Run actuator in direction CLOSE: Press push button CLOSE [3].
Information
OPEN - CLOSE operation commands can be given either in push-to-run or in self-
retaining operation mode. In self-retaining mode, the actuator runs to the defined
end position after pressing the button, unless another command has been received
beforehand.
Push-to-run operation or self-retaining is set via the controls software. Refer to
<AUMA CDT software (accessories)> chapter. It is possible to temporarily (for one
operation command) activate self-retaining by means of the push buttons:
→
Press and hold down push buttons OPEN [1] or CLOSE [3] for more than 3
seconds.
During this procedure, self-retaining is not saved. The setting programmed within
the software is taken over for the subsequent operation command.
8.2.2.
Actuator operation from remote
Operation mode Remote can be activated via local controls.
Figure 16: Local controls
[2]
Operation mode LOCAL/REMOTE
[4]
Indication light for operation mode LOCAL (blue)
23
SVM 05.1 – SVM 07.5 / SVMR 05.1 – SVMR 07.5
Modbus RTU
Operation