Tripping torques [Nm]
Switch steps
SGM/SGMR
14.1
SGM/SGMR
12.1
SGM/SGMR
10.1
SGM/SGMR
07.1
SGM/SGMR
05.1
SGM/SGMR
04.1
1,950
900
440
220
110
55
7
2,200
1,000
500
250
125
63
8
2,200
1,000
500
250
125
63
9
Setting via software parameters (AUMA CDT)
Condition: Switch [S5] is in position ON (software mode).
Setting parameters
Customer settings
Torque switching
Tripping torque CLOSE (S7)
Tripping torque OPEN (S6)
Default value: depending on the order
Setting ranges: adjustable between 40 – 100 % of the maximum tripping torque
10.5.
Fieldbus address (slave address): set
Setting via switches
Condition: Switch [S5] is in position OFF (hardware mode).
Figure 21: Switch for fieldbus address
[S2]
Third position before decimal point
[S3]
Second position before decimal point
[S4]
First position before decimal point
Table 11:
Software (AUMA CDT)
Connector [S2] [S3] [S4]
Address
126
2
Default value
0 – 126
0 – 126
Setting range
Table 12: Examples
Setting value
[S4]
[S3]
[S2]
Address
1
0
OFF
1
2
0
OFF
2
0
1
OFF
10
2
1
OFF
12
0
0
ON
100
0
1
ON
110
1
1
ON
111
28
SGM 04.1 – SGM 14.1 / SGMR 04.1 – SGMR 14.1
Commissioning (basic settings of controls)
Profibus DP