11.3.2.
End position OPEN: set again
Activate setting mode "end position setting":
1.
Press push button [2] – hold down and press push buttons [1] and [3] at the
same time.
➥
Now, the right indication light is blinking faster (5 Hz).
Set end position OPEN:
2.
Use crank handle/handwheel or push button [1] for running actuator to end
position OPEN. (Actuator runs at reduced output speed in setting mode.)
3.
Press push button [2] – hold it down and press push button [1]. Hold both push
buttons down until the left indication light is blinking in green (default).
➥
Once the left indication light is illuminated in green (default), end position OPEN
setting is complete.
4.
Once both end positions are set, perform a reference operation, i.e. both end
positions must be approached again – either via push buttons [1]/[3] (in operation
mode Local) or from Remote (deactivate operation mode Local).
Deactivate operation mode Local:
5.
Hold down push button [2] for approx. 3 seconds until blue indication light goes
out.
➥
Now, the actuator can be controlled from Remote:
-
via operation commands (OPEN - STOP - CLOSE) in positions OPEN or
CLOSED.
-
via setpoint indication in defined positions between 0 % and 100 % of setting
range.
11.4.
Switch compartment: open
The switch compartment must be opened to perform the following settings (options).
→
Loosen screws [2] and remove cover [1] from the switch compartment.
37
SGM 04.1 – SGM 14.1 / SGMR 04.1 – SGMR 14.1
Profibus DP
Commissioning (basic settings at actuator)