20.3 EMERGENCY - OPEN and EMERGENCY - CLOSE signal (option)
(5
th
digit in wiring diagram MSP … C, D, or P)
When an EMERGENCY operation command is given, the actuator operates
the valve to the predetermined end position (effective in all three selector
switch positions: LOCAL, OFF, REMOTE).
.
The input at terminal X
K
1 (refer to wiring diagram) must be connected to
an NC contact (closed circuit principle) at + 24 V DC.
.
If EMERGENCY - OPEN or EMERGENCY - CLOSE signal is generally
not desired:
Take off cover plate and disconnect links B1 (for EMERGENCY - CLOSE)
and B2 (for EMERGENCY - OPEN).
34
Multi-turn actuators SA 07.1 – SA 30.1/SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1/AM 02.1
Operation instructions
Figure 46: Cover plate for EMERGENCY - OPEN or EMERGENCY - CLOSE option
Links:B1 (EMERGENCY-CLOSE)
B2 (EMERGENCY-OPEN)
LED for EMERGENCY
operation command
B2
B1