13.
Setting the DUO limit switching (option)
Any application can be switched on or off via the two intermediate position
switches.
For setting, the switching point (intermediate position) must
be approached from the same direction as afterwards in
electrical operation.
13.1 Setting direction CLOSE (black section)
.
Move valve to desired intermediate position.
.
Press down
and turn setting spindle G (figure 27) with screw driver
(5 mm) in direction of arrow, while observing pointer H.
While a ratchet is felt and heard, the pointer H moves 90° every time.
When pointer H is 90° from mark C, continue turning slowly. When pointer
H has reached the mark C, stop turning and release setting spindle. If you
override the tripping point inadvertently (ratchet is heard after the pointer
has snapped), continue turning the setting spindle in the same direction
and repeat setting process.
13.2 Setting direction OPEN (white section)
.
Move valve to desired intermediate position.
.
Press down
and turn setting spindle K (figure 27) with screw driver
(5 mm) in direction of arrow, while observing pointer L.
While a ratchet is felt and heard, the pointer L moves 90° every time.
When pointer L is 90° from mark F, continue turning slowly. When pointer
L has reached the mark F, stop turning and release setting spindle. If you
override the tripping point inadvertently (ratchet is heard after the pointer
has snapped), continue turning the setting spindle in the same direction
and repeat setting process.
13.3 Checking the DUO limit switches
The red test buttons T and P (figure 27) are used for manual operation of
the DUO limit switches.
.
Turning T in direction of the arrow TSC (DSR) triggers DUO limit switch CLOSED.
The torque switch CLOSED is actuated at the same time.
.
Turning P in direction of the arrow TSO (DÖL) triggers DUO limit switch OPEN.
The torque switch OPEN is actuated at the same time.
.
After checking the switches, the fault (red indication light) has to be reset using
the OPEN or CLOSE push buttons of the local controls for operation in the oppo-
site direction.
23
Multi-turn actuators SA 07.1 – SA 30.1/SAR 07.1 – SAR 30.1
Operation instructions
with actuator controls AUMA MATIC AM 01.1/AM 02.1
Figure 27: Control unit
G
T
H
C
K
P
L
F