Connecting the cables
.
Connect cables according to order-related wiring diagram.
Cross sections:
- Power terminals (U1, V1, W1, U2, V2, W2) and
protective earth (symbol:
)
max. 6 mm² flexible, max. 10 mm² rigid
- Control contacts (1 to 50) = max. 2.5 mm²
.
For stranded wires use end-sleeves according to DIN 46228.
.
All PE conductors have to be tightened firmly to the PE connection
(symbol:
) using either ring lugs (flexible cables), or loops (rigid cables)
(figure 17).
Each time the PE connection has been disconnected, it has
to be ensured that the PE conductors are firmly connected.
Screw
Washer
Circlip
Protective earth with ring
luringgs/lugs
PE connection
Socket carrier
Closing the terminal compartment
.
Insert socket carrier into the cover and fasten with screws (2) (figure 15).
.
Clean sealing faces at the cover and the housing.
.
Check whether O-ring is in good condition.
.
Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.
.
Replace cover and fasten bolts (1) evenly crosswise.
.
Fasten cable glands with the specified torque to ensure the required
enclosure protection.
Parking frame, protection cover (accessories)
A special parking frame (figure 16) for protection against touching the bare
contacts and against environmental influences is available.
The open terminal compartment can be closed using a protective cover
(not illustrated).
Multi-turn actuators SA 07.1 – SA 30.1/SAR 07.1 – SAR 30.1
Operation instructions
with actuator controls AUMA MATIC AM 01.1/AM 02.1
17
Figure 16: Parking frame (accessory)
Parking frame
Figure 17: PE connection