Operation and display
FOX-EYE (indication LED)
Status indications: OK, end positions, faults and “Bluetooth connection active".
Status indica-
tion
Basic
at the actuator
4 buttons and 1 LED are located below the hood.
Run actuator in directions OPEN and CLOSE. Set end position once mounted to the valve
Set end posi-
tions
Run actuator in directions OPEN and CLOSE. Set end position once mounted to the valve.
Set end posi-
tions
Smart
Via Bluetooth using AUMA Assistant
App or AUMA CDT software in the
latest version
●
Rotation speed
●
Type of seating for end positions,
Torque switching
●
Assignment of signal inputs and outputs
●
Fieldbus parameter (if fieldbus option has been selected).
Basic settings for opera-
tion:
Configura-
tion
For applications, safety and service, including:
●
Positioner
●
EMERGENCY behaviour
●
Torque by-pass
●
Failure behaviour
●
Signal configuration
Additional functions:
Monitoring key figures and measured values for preventive maintenance and consequently
increasing process safety. Limit values can be set. Deviations generate warning signals
which can be transmitted to the DCS via binary outputs or fieldbus.
Diagnostics
Temperature value within actuator
Key figures regarding lifetime of mechanics, grease, electronics,
and motor.
Actuator:
Method for identifying changes in torque requirement: Perform
reference operation and save torque as reference profile. Define
tolerance range. Perform comparative operation if required.
Values outside tolerance initiate a signal which is communicated
as described above.
Actuator and valve:
In basic version, the actuator monitors and records further figures
and conditions. The generated fault and warning signals are
saved within the event log. These signals can be configured as
requested. An overview in the AUMA Assistant App or the CDT
software shows all available fault/warning signals with option to
enter the details.
Further key figures:
With output drive type A for valve shafts with threads (option)
Valve attachment
Trapezoidal thread
Ø
Max.
Stem stroke
Max.
[mm]
F07 (option F10)
TR22
55
M25 with A07.2-F07
F07 (option F10)
TR22
55
M50 with A07.2-F07
F07 (option F10)
TR26
65
M100 with A07.2-F07
F10
TR26
55
M100 with A07.2-F10
The stem stroke can be increased by using spacer elements as special solution; available on request.
Service conditions
Any position
Mounting position
≤
2,000 m above sea level
>
2 000 m above sea level on request
Installation altitude
–30 °C to +60 °C
Standard:
Ambient temperature
–30 °C to +65 °C
Option:
Up to 100 % relative humidity across the entire permissible temperature range
Humidity
47
PF-M25X – PF-M100X
Parallel
Technical data
Содержание PROFOX PF-M100X