9.
Connect signal cables in push-in technology according to order-related wiring
diagram.
Damage to push-in terminals by jamming of wire end sleeves with the housing!
Replacement of the complete component is required.
→
Use wire end sleeves with smooth surface.
→
Always press the push-in terminals completely down using a screwdriver and
always carefully remove signal cables.
→
It must be possible to pull out the signal cable without resistance when the push-
in terminal held down.
Information: To avoid unevenness at wire end sleeve, AUMA recommends
using the Crimpfox 6 model by Phoenix Contact as suitable crimping pliers.
Figure 15: Connect signal cables
Table 7:
Terminal cross sections
Cross section
Wire type
Designation
max. [mm²]
min. [mm²]
1.5
0.2
solid
I/O signal cable
1.5
0.2
flexible
1.5
0.2
flexible with wire end
sleeve without plastic
sleeve
AWG 16
AWG 24
AWG
10. For shielded cables: Link the cable shield end via the cable gland to the housing
(earthing).
11. If the PE conductor has been removed from the cover, it must be tightened
applying 2.2 Nm tightening torque prior to re-placing the cover.
12. Fasten cable glands with the torque as specified by the manufacturer to ensure
respect of required enclosure protection.
13. Connect power supply.
If the end position setting is carried out with the internal operation buttons
following the connection to the power supply: Do not close cover!
21
PF-M25X – PF-M100X
Parallel
Electrical connection
Содержание PROFOX PF-M100X
Страница 9: ...3 Name plate Figure 4 Name plate arrangement 9 PF M25X PF M100X Parallel Name plate ...
Страница 49: ...15 Spare parts 15 1 Multi turn actuators PF M25 PF M100 49 PF M25X PF M100X Parallel Spare parts ...
Страница 51: ...51 PF M25X PF M100X Parallel ...
Страница 52: ...52 PF M25X PF M100X Parallel ...
Страница 55: ...55 AUMA worldwide ...