10
11
Make sure to strip the cable before placing it into the
terminals, and make sure that the copper is in good
condition.
A method of disconnection must always be installed in
compliance with the installation rules.
If the power supply cable is damaged, it must be replaced by a
qualified professional to avoid any risk of danger.
To access the terminals: remove the panel on the bottom left-
hand side (2 screws) and open the electrical box (8 screws).
The electrical power supply cable should first be inserted
through an exterior compression gland and then through a cable
grommet on the electrical box.
Power supply cable
Cable grommet
Cable gland
3.4.3. - HRC
70
Heat Pump:
400V three-phase connection
• Three-phase monitor relay for 35kW HRC
70
Heat
Pump.
A phase monitor relay is installed to prevent phase failure, which
could damage the compressors. If the phases are reversed, it will
stop the power supply to the Heat Pump.
If the phase order is reversed, or there is a phase missing, the
relay cuts the power supply to the circuit board. A «BUS Err» error
message will appear. This is indicated on the phase monitor relay
by the orange light at the top being off and the green light at the
bottom being on. To correct the error, reverse the two phases on
the mains power terminal.
When the Pilot is switched on, a «BUS Err» error message will be
displayed. Reverse the two phases on the three-phase power
cable of the Heat Pump. Switch the power back on and check the
voltage on each phase.
In the case of INCORRECT WIRING :
Caution: never work with live voltage!
CORRECT WIRING
orange and
green LEDs on
INCORRECT WIRING
only green
LED on
Thermal-magnetic
circuit breaker or fuse
Neutral
Ground
Neutr
al
Gr
ound
3-wire section to be defined
See § Recommendations for connecting
the systemto the power supply.
HRC
70
Heat Pump model
HRC70 35
three-phase
Power supply voltage
400 V three-phase
Maximum power consumption
13 kVA
Maximum current requirements
32 A
Maximum current at start-up
60 A
Presence of a progressive starter for th compressor
YES
Phi tangent at Heat Pump start up
1,66
Heat Pump (Zmax) impedance (ohm)
-
Phase impedance (Zmax) (ohm)
0,269
Neutral impedance (Zmax) (ohm)
0,176
Heat Pump regulation mode
Fixed speed
Number of power stages
2
Circuit breaker dimensions
32 A three-phase
Power supply by phase (2)
10 mm²
Number of conductors (2)
4 x 10mm² + T(*)
(1) D-curve tetra-polar general circuit breaker.
(2) The figures given here are for informational purposes only. They must be checked an
modified if necessary, according to conditions of installation and the current rules and
regulations in effect.
If the length of the cable exceeds 15m, or if the network is susceptible to a drop in voltage
of more than 10V, use a thicker cable.
(*) The width of the ground cable must be equal to the thickest power supply cable.