auer 950280 Скачать руководство пользователя страница 11

installer

 

HRC

70 

35kW HIGH TEMPERATURE HEAT PUMP

 

manual

 - 

installer

 

HRC

70 

35kW HIGH TEMPERATURE HEAT PUMP

 

manual

 - 

10

11

Make sure to strip the cable before placing it into the 

terminals, and make sure that the copper is in good 

condition. 

A method of disconnection must always be installed in 

compliance with the installation rules. 
If the power supply cable is damaged, it must be replaced by a 

qualified professional to avoid any risk of danger. 
To access the terminals: remove the panel on the bottom left-

hand side (2 screws) and open the electrical box (8 screws). 
The electrical power supply cable should first be inserted 

through an exterior compression gland and then through a cable 

grommet on the electrical box.

Power supply cable

Cable grommet

Cable gland

3.4.3. - HRC

70

 Heat Pump: 

400V three-phase connection

• Three-phase monitor relay for 35kW HRC

70 

Heat 

Pump.

A phase monitor relay is installed to prevent phase failure, which 

could damage the compressors. If the phases are reversed, it will 

stop the power supply to the Heat Pump. 

If the phase order is reversed, or there is a phase missing, the 

relay cuts the power supply to the circuit board. A «BUS Err» error 

message will appear. This is indicated on the phase monitor relay 

by the orange light at the top being off and the green light at the 

bottom being on. To correct the error, reverse the two phases on 

the mains power terminal. 

When the Pilot is switched on, a «BUS Err» error message will be 

displayed. Reverse the two phases on the three-phase power 

cable of the Heat Pump. Switch the power back on and check the 

voltage on each phase. 

In the case of INCORRECT WIRING :

Caution: never work with live voltage!

CORRECT WIRING

orange and 

green LEDs on

INCORRECT WIRING

only green 

LED on

Thermal-magnetic

circuit breaker or fuse

Neutral

Ground

Neutr

al

Gr

ound

3-wire section to be defined

See § Recommendations for connecting 

the systemto the power supply.

HRC

70

 Heat Pump model

HRC70 35

 three-phase

Power supply voltage

400 V three-phase

Maximum power consumption

13 kVA

Maximum current requirements

32 A

Maximum current at start-up

60 A

Presence of a progressive starter for th compressor

YES

Phi tangent at Heat Pump start up

1,66

Heat Pump (Zmax) impedance (ohm)

-

Phase impedance (Zmax) (ohm)

0,269

Neutral impedance (Zmax) (ohm)

0,176

Heat Pump regulation mode

Fixed speed

Number of power stages

2

Circuit breaker dimensions

32 A three-phase

Power supply by phase (2)

10 mm²

Number of conductors (2)

4 x 10mm² + T(*)

(1) D-curve tetra-polar general circuit breaker. 

(2) The figures given here are for informational purposes only. They must be checked an 

modified if necessary, according to conditions of installation and the current rules and 

regulations in effect.  

If the length of the cable exceeds 15m, or if the network is susceptible to a drop in voltage  

of more than 10V, use a thicker cable.    

(*) The width of the ground cable must be equal to the thickest power supply cable. 

Содержание 950280

Страница 1: ...r manual HRC70 35kW High temperature modulating Heat Pump HRC70 35 2 t Ref 950280 The information contained in this document is non contractual Auer reserves the right to modify the technical specifications or characterisitcs of any of their appliances without prior notice ...

Страница 2: ... Pump to the power supply 10 3 4 3 HRC70 Heat Pump 400V three phase connection 11 3 4 4 Electrical protection of the compressors 12 4 MAINTENANCE AND TROUBLESHOOTING 12 4 1 General information 12 4 2 Maintenance on the hydraulic circuit 12 4 3 Maintenance on the Heat Pump 13 4 4 Maintenance of the electrical components 13 4 5 Decommissioning and disposal 13 4 6 Compressor start up faults 13 5 LIST...

Страница 3: ...Pump absorbs the calories present in exterior air and transforms them into useful energy which is then transferred to the heating water for your home AUER cannot be held responsible for any other usage of the appliance The safety advice and instructions present in this document must be strictly respected Before making any connections to the installation make sure the appliances are compatible with...

Страница 4: ...Pump to be installed outdoors exclusively and of an interior unit Pilot to be installed indoors exclusively connected together through a hydraulic connection and a communication bus The air to water Heat Pump draws calories from the exterior air and transfers them to the heating water circuit with high energy efficiency The Pilot ensures the regulation and hydraulic distribution of the installatio...

Страница 5: ...e installed OUTSIDE exclusively AnyinstallationinanENCLOSEDand UNVENTILATEDspaceisPROHIBITED unless thereisventilationwhichensureatleast80 of thenominalflowrateoftheHeatPump DO NOT RESTRICTairintakeorventilation exhaust NO OBJECTshouldimpedetheflowof airovertheheatexchanger ortherenewalofair TheHeatPumpshouldbeplacedOUT OFTHE WAY OF PREVAILINGWINDS DO NOT INSTALLtheHeatPumpNEAR SOURCES OF EXCESSIV...

Страница 6: ...ir flow for intake and exhaust In regards to the fan the free space from any obstacles must be at least 2m Minimum distances to respect for proper installation of the Heat Pump mm TO AVOID TO AVOID 3 1 3 Noise levels The Heat Pump is equipped with a large diameter fan so as to allow for an appropriate air flow rate This flow rate can rise up to 12 000 m3 h The fan speed is adjustable to limit the ...

Страница 7: ...e base case a Front of the HRC70 heat pump Back of the HRC70 heat pump 3 1 4 Condensates drainage 3 2 1 Hydraulic connections on the installation 3 2 Hydraulic installation In order to ensure that fluids can circulate properly it is advisable to check that the sizing of piping in the circuit is appropriate between the Heat Pump and the Pilot The HRC70 35 Heat Pump is intended for with a large vari...

Страница 8: ...system 3 2 4 Heat Pump water inlet filter supplied A 1 valve with a built in 500µm filter must be installed on the water inlet piping on the Heat Pump Respect the direction of flow on the filter arrow on the valve Install the 1 valve with a filter on the inside of the building and ensure it is thermally insulated Beforemakinganyhydraulicconnectionsto theHeatPump itisnecessarytodesludge andrinsethe...

Страница 9: ...s cable with a 20m cable which is available to order Ref 751005 On the Pilot cut the bus link to the right length LOOPS ARE FORBIDDEN On the Pilot cleanly remove 10cm of the shielding to prevent any short circuits Connect the two wires stripped to 10mm to the Pilot IMPORTANT DO NOT connect the bus link shielding to the ground of the Pilot DiagramofconnectiontotheHeatPump withoutthe2 coresheathedca...

Страница 10: ...lap just above or below the identification number 2 Insert the wire into the CAGE CLAMP when the flap is open 3 Remove the screwdriver Note The wires must be stripped to the following lengths for the 2 5mm control terminals between 10 and 12mm for the mains power terminal between 18 and 20mm 3 4 1 Recommendations for connecting the system to the power supply Check The power consumption Number and ...

Страница 11: ...erminal When the Pilot is switched on a BUS Err error message will be displayed Reverse the two phases on the three phase power cable of the Heat Pump Switch the power back on and check the voltage on each phase In the case of INCORRECT WIRING Caution neverworkwithlivevoltage CORRECT WIRING orange and green LEDs on INCORRECT WIRING only green LED on Thermal magnetic circuit breaker or fuse Neutral...

Страница 12: ...NANCE AND TROUBLESHOOTING Inordertoensurethebestperformance resultsfromyourHRC70 HeatPumpit shouldbesubjecttoregularmaintenance Anannualmaintenancecheckisrecommended tobecarriedoutbyaqualifiedprofessionalon thehydraulicheatingcircuit Allworkcarriedoutontherefrigerantcircuit mustbedonebyaqualifiedprofessionalwitha category1certificateofaptitude Alwaysswitchtheapplianceoffbeforeopeningit 4 1 General...

Страница 13: ...nceontheHeatPump 4 4 Maintenanceoftheelectricalcomponents Check on both the HRC70 Heat Pump and the HRC70 Pilot that the electrical supply cables are properly connected to the terminals Check the electrical connections for oxidization or overheated sections Check the tightness of the cables on the compressor starters Clean any dust from the electrical box and check the connections Check that the g...

Страница 14: ...VE 12 1239211 HIGH PRESSURE SWITCH PS 80 450 363 13 1239210 LOW PRESSURE SWITCH PS 80 20 5 14 1244578 Temperature sensor lg 2000mm 15 1244578 Temperature sensor lg 2000mm 17 1244522 Exterior air temperature sensor 18 1244578 Temperature sensor lg 2000mm 19 1244578 Temperature sensor lg 2000mm 22 4592251 Fan kit 23 1239128 Pressure relief valve set at 2 5 bars 24 4948083 Condensates drainage pipe 2...

Страница 15: ...roved technical center In the absence of regular maintenance the warranty is rendered null and void Any work on the refrigerant circuit must be undertaken by a qualified professional with a category 1 certificate of aptitude It is forbidden to release gas from the refrigerant circuit into the atmosphere and it is obligatory to recover the refrigerant before undertaking any work on the circuit The ...

Страница 16: ...national standards in effect Not following the electrical connection diagrams provided in the installer manual Electrical supply being significantly over or under the required voltage Not respecting the supply cable sections Absence of or insufficient electrical protection throughout the appliance fuses circuit breaker grounding APPENDICES A1 Dimensions Serial number Air temperature sensor Heating...

Страница 17: ...Air flow rate 6 000 to 12 000 m3 h Adjustable silent blocks standard Sound levels EN 12102 66 dB A HRC70 35 2 three phase Heating output 7 35 C 18 0 Power consumption 4 1 COP 4 4 Heating output 7 65 C 16 0 Puissance absorbée 6 4 COP 2 5 Heating output 2 35 C 14 5 Power consumption 4 2 COP 3 5 Heating output 2 65 C 13 1 Power consumption 6 1 COP 2 2 MAX heating output 7 35 C 25 1 MAX power consumpt...

Страница 18: ...s of installations steel or cast iron radiators PEX underfloor heating We recommend the use of products in the SENTINEL range for preventative and curative treatment of the heating circuit For new installations less than 6 months old Clean the installation with a universal cleaner to eliminate the debris from the installation copper fibres soldering fluxes Example SENTINEL X300 or SENTINEL X800 Th...

Страница 19: ...e inhibitormixturetogether priortoinsertingitintotheinstallation RENDERINGTHEWARRANTY NULL ANDVOID Alldeteriorationoftheappliancedueto aninappropriatequalityofwaterand orthepresenceofcorrosionintheabsenceof treatmentproductsasdescribedabove and oranimproperpurgingofairoftheinstallation willrenderthewarrantytobenullandvoid RegularlycheckthepHleveland of glycolintheinstallation Nevertop uptheglycoli...

Страница 20: ...llow brown grey black black red white black red white white brown grey black grey brown green yellow black brown green yellow grey green yellow blue brown blue green yellow brown orange yellow white red black white red black blue green yellow orange yellow blue blue green yellow g y blue blue brown grey white brown GROUND blue ...

Страница 21: ...CP1 Compressor 1 start up control CP2 Compressor 2 start up control VEM De icing solenoid valve cycle inversion control CH1 Compressor 1 RK1 heater cable CH2 Compressor 2 RK2 heater cable CC External heater cable F Fuse 5x20 4A K1 Compressor 1 thermal protection device K2 Compressor 2 thermal protection device VENT Fan RCP Phase controller KMC1 Compressor 1 contactor KMC2 Compressor 2 contactor RK...

Страница 22: ...ing interval efficiency 5 COPcyc Température maximale eau de chauffage Max temperature for the heating water WTOL 70 Tj 15 C 5 COPd 2 03 Température limite de fonctionnement Operating limit temperature TOL 20 Mode veille Standby mode 6 PSB 0 005 Mode résistance de carter Crankcase heater mode 6 PCK 0 005 Mode arrêt OFF mode 6 POFF 0 023 Mode arrêt thermostat Thermostat off mode 6 PTO 0 008 Régulat...

Страница 23: ...tach a copy of mandate Connections Single phase o Three phase o Circuit breaker Setting ________A Heat Pump HP Type de pump Single phase o Three phase o Make model and reference number ______________________________________________________________ Type of compressor without back up heating Single phase o Three phase o Nominal heating capacity of the Heat Pump without elements for back up heating k...

Страница 24: ...de la République CS 40029 80210 Feuquières en Vimeu Spare parts department Tel 03 22 61 21 21 Fax 03 22 61 33 35 E mail pieces auer fr Technical assistance department E mail sav auer fr Technical assistance service is reserved for professionals ...

Отзывы: