background image

installer

 

HRC

70 

35kW HIGH TEMPERATURE HEAT PUMP

 

manual

 - 

8

9

3.2.3 - Pressure-relief valves

The Heat Pump and the Pilot are both equipped with  pressure-

relief valves.

The pressure-relief valve on the Heat Pump sets the maximum 

acceptable pressure in the installation (2.5 bars when hot). The 

maximum service pressure on the Heat Pump must, consequently 

be lower than 2.5 bars. 

Example : If the Heat Pump is positioned 5m below the Pilot, the 

pressure reading on the Pilot would be 0.5 bars less than 

the real pressure of the water in the Heat Pump. In this case, 

the maximum service pressure for the Pilot would be 2 bars. 

 

Therefore it would be advisable to fill the heating circuit at 

an intermediary pressure (between 1 and 1.5 bars).

In case of operating with a back-up boiler, these pressure-relief 

valves 

MUST

 be installed in addition to the ones which the boiler 

is already equipped with (set at 3 bars).

The connections and  the evacuation conduits for the pressure-

relief valves must be made from materials which are resistant to 

high temperatures and corrosion.

3.2.4.1 - Backflow prevention device

French law (articles 16.7 and 16.8 of the ‘‘Règlement Sanitaire 

Départemental’’) stipulates that a type CB backflow prevention 

device must be installed. This device must be at different, non-

regulated pressure zones, in accordance with the NF P 43-011 

standard. This is also an obligatory requirement in other countries,  

which makes it important to verify the current laws and standards 

in effect in the country of installation and ensure that your 

installation is in compliance with them. The backflow prevention 

device is designed to prevent incoming heating water from 

entering the drinking water circuit. It must be connected to the 

mains drainage system. 

3.2.4 - Heat Pump water inlet filter (supplied)

A 1’’ valve with a built-in 500µm filter must be installed on the water 

inlet piping on the Heat Pump:

 

• Respect the direction of flow on the filter (arrow on the 

valve)

 

• Install the 1’’ valve with a filter on the inside of the 

building and ensure it is thermally insulated.

Before making any hydraulic connections to 

the Heat Pump, it is necessary to desludge 

and rinse the installation. 

Clean the filter several times as soon as the Heat 

Pump circulator pump has been activated (make 

sure to switch off the Heat Pump circulator 

pump before cleaning).

 

• Clean the filter at least once per year. 

3.2.4.2 - Purging the heating circuit(s)

All necessary measures must be taken to ensure that the 

installation can be continuously degassed. Automatic air purging 

valves should be placed at each high point of the installation, and 

manual air purging valves should be installed on each radiator. 

3.2.4.3 - Insulating the piping

Insulants must conform to the DTU 67.1 standard, or the current 

regulations in effect in the country of installation.

All visible piping and accessories (circulator pump, expansion 

vessel, valves, etc...) must be either insulated or placed in 

insulated sleeves. 

Remember to insulate the distribution manifolds and the inlet 

and outlet flow pipes to the underfloor heating circuit. 

Remember to insulate the piping which connects the Heat Pump 

to the Pilot. 

3.2.4.4 - Expansion vessel

An expansion vessel needs to be installed onto the heating circuit. 

See Appendix A4 for information on proper sizing of the 

expansion vessel.

3.2.4.5 - Frost protection and water treatment

See the recommendation in Annexes A3 and A5.

Heat Pump model

35kW

Minimum nominal flow rate

3500 L/h

Maximum pressure

2.5 bars

Minimum Ø of piping

if distance* between HP and pilot < 15m

36 mm / 38 mm

If distance* between HP and pilot < 25m

42 mm / 44 mm

If distance* between HP and pilot < 50m

46 mm / 48 mm

* distance consists of both inlet and outlet

Содержание 950280

Страница 1: ...r manual HRC70 35kW High temperature modulating Heat Pump HRC70 35 2 t Ref 950280 The information contained in this document is non contractual Auer reserves the right to modify the technical specifications or characterisitcs of any of their appliances without prior notice ...

Страница 2: ... Pump to the power supply 10 3 4 3 HRC70 Heat Pump 400V three phase connection 11 3 4 4 Electrical protection of the compressors 12 4 MAINTENANCE AND TROUBLESHOOTING 12 4 1 General information 12 4 2 Maintenance on the hydraulic circuit 12 4 3 Maintenance on the Heat Pump 13 4 4 Maintenance of the electrical components 13 4 5 Decommissioning and disposal 13 4 6 Compressor start up faults 13 5 LIST...

Страница 3: ...Pump absorbs the calories present in exterior air and transforms them into useful energy which is then transferred to the heating water for your home AUER cannot be held responsible for any other usage of the appliance The safety advice and instructions present in this document must be strictly respected Before making any connections to the installation make sure the appliances are compatible with...

Страница 4: ...Pump to be installed outdoors exclusively and of an interior unit Pilot to be installed indoors exclusively connected together through a hydraulic connection and a communication bus The air to water Heat Pump draws calories from the exterior air and transfers them to the heating water circuit with high energy efficiency The Pilot ensures the regulation and hydraulic distribution of the installatio...

Страница 5: ...e installed OUTSIDE exclusively AnyinstallationinanENCLOSEDand UNVENTILATEDspaceisPROHIBITED unless thereisventilationwhichensureatleast80 of thenominalflowrateoftheHeatPump DO NOT RESTRICTairintakeorventilation exhaust NO OBJECTshouldimpedetheflowof airovertheheatexchanger ortherenewalofair TheHeatPumpshouldbeplacedOUT OFTHE WAY OF PREVAILINGWINDS DO NOT INSTALLtheHeatPumpNEAR SOURCES OF EXCESSIV...

Страница 6: ...ir flow for intake and exhaust In regards to the fan the free space from any obstacles must be at least 2m Minimum distances to respect for proper installation of the Heat Pump mm TO AVOID TO AVOID 3 1 3 Noise levels The Heat Pump is equipped with a large diameter fan so as to allow for an appropriate air flow rate This flow rate can rise up to 12 000 m3 h The fan speed is adjustable to limit the ...

Страница 7: ...e base case a Front of the HRC70 heat pump Back of the HRC70 heat pump 3 1 4 Condensates drainage 3 2 1 Hydraulic connections on the installation 3 2 Hydraulic installation In order to ensure that fluids can circulate properly it is advisable to check that the sizing of piping in the circuit is appropriate between the Heat Pump and the Pilot The HRC70 35 Heat Pump is intended for with a large vari...

Страница 8: ...system 3 2 4 Heat Pump water inlet filter supplied A 1 valve with a built in 500µm filter must be installed on the water inlet piping on the Heat Pump Respect the direction of flow on the filter arrow on the valve Install the 1 valve with a filter on the inside of the building and ensure it is thermally insulated Beforemakinganyhydraulicconnectionsto theHeatPump itisnecessarytodesludge andrinsethe...

Страница 9: ...s cable with a 20m cable which is available to order Ref 751005 On the Pilot cut the bus link to the right length LOOPS ARE FORBIDDEN On the Pilot cleanly remove 10cm of the shielding to prevent any short circuits Connect the two wires stripped to 10mm to the Pilot IMPORTANT DO NOT connect the bus link shielding to the ground of the Pilot DiagramofconnectiontotheHeatPump withoutthe2 coresheathedca...

Страница 10: ...lap just above or below the identification number 2 Insert the wire into the CAGE CLAMP when the flap is open 3 Remove the screwdriver Note The wires must be stripped to the following lengths for the 2 5mm control terminals between 10 and 12mm for the mains power terminal between 18 and 20mm 3 4 1 Recommendations for connecting the system to the power supply Check The power consumption Number and ...

Страница 11: ...erminal When the Pilot is switched on a BUS Err error message will be displayed Reverse the two phases on the three phase power cable of the Heat Pump Switch the power back on and check the voltage on each phase In the case of INCORRECT WIRING Caution neverworkwithlivevoltage CORRECT WIRING orange and green LEDs on INCORRECT WIRING only green LED on Thermal magnetic circuit breaker or fuse Neutral...

Страница 12: ...NANCE AND TROUBLESHOOTING Inordertoensurethebestperformance resultsfromyourHRC70 HeatPumpit shouldbesubjecttoregularmaintenance Anannualmaintenancecheckisrecommended tobecarriedoutbyaqualifiedprofessionalon thehydraulicheatingcircuit Allworkcarriedoutontherefrigerantcircuit mustbedonebyaqualifiedprofessionalwitha category1certificateofaptitude Alwaysswitchtheapplianceoffbeforeopeningit 4 1 General...

Страница 13: ...nceontheHeatPump 4 4 Maintenanceoftheelectricalcomponents Check on both the HRC70 Heat Pump and the HRC70 Pilot that the electrical supply cables are properly connected to the terminals Check the electrical connections for oxidization or overheated sections Check the tightness of the cables on the compressor starters Clean any dust from the electrical box and check the connections Check that the g...

Страница 14: ...VE 12 1239211 HIGH PRESSURE SWITCH PS 80 450 363 13 1239210 LOW PRESSURE SWITCH PS 80 20 5 14 1244578 Temperature sensor lg 2000mm 15 1244578 Temperature sensor lg 2000mm 17 1244522 Exterior air temperature sensor 18 1244578 Temperature sensor lg 2000mm 19 1244578 Temperature sensor lg 2000mm 22 4592251 Fan kit 23 1239128 Pressure relief valve set at 2 5 bars 24 4948083 Condensates drainage pipe 2...

Страница 15: ...roved technical center In the absence of regular maintenance the warranty is rendered null and void Any work on the refrigerant circuit must be undertaken by a qualified professional with a category 1 certificate of aptitude It is forbidden to release gas from the refrigerant circuit into the atmosphere and it is obligatory to recover the refrigerant before undertaking any work on the circuit The ...

Страница 16: ...national standards in effect Not following the electrical connection diagrams provided in the installer manual Electrical supply being significantly over or under the required voltage Not respecting the supply cable sections Absence of or insufficient electrical protection throughout the appliance fuses circuit breaker grounding APPENDICES A1 Dimensions Serial number Air temperature sensor Heating...

Страница 17: ...Air flow rate 6 000 to 12 000 m3 h Adjustable silent blocks standard Sound levels EN 12102 66 dB A HRC70 35 2 three phase Heating output 7 35 C 18 0 Power consumption 4 1 COP 4 4 Heating output 7 65 C 16 0 Puissance absorbée 6 4 COP 2 5 Heating output 2 35 C 14 5 Power consumption 4 2 COP 3 5 Heating output 2 65 C 13 1 Power consumption 6 1 COP 2 2 MAX heating output 7 35 C 25 1 MAX power consumpt...

Страница 18: ...s of installations steel or cast iron radiators PEX underfloor heating We recommend the use of products in the SENTINEL range for preventative and curative treatment of the heating circuit For new installations less than 6 months old Clean the installation with a universal cleaner to eliminate the debris from the installation copper fibres soldering fluxes Example SENTINEL X300 or SENTINEL X800 Th...

Страница 19: ...e inhibitormixturetogether priortoinsertingitintotheinstallation RENDERINGTHEWARRANTY NULL ANDVOID Alldeteriorationoftheappliancedueto aninappropriatequalityofwaterand orthepresenceofcorrosionintheabsenceof treatmentproductsasdescribedabove and oranimproperpurgingofairoftheinstallation willrenderthewarrantytobenullandvoid RegularlycheckthepHleveland of glycolintheinstallation Nevertop uptheglycoli...

Страница 20: ...llow brown grey black black red white black red white white brown grey black grey brown green yellow black brown green yellow grey green yellow blue brown blue green yellow brown orange yellow white red black white red black blue green yellow orange yellow blue blue green yellow g y blue blue brown grey white brown GROUND blue ...

Страница 21: ...CP1 Compressor 1 start up control CP2 Compressor 2 start up control VEM De icing solenoid valve cycle inversion control CH1 Compressor 1 RK1 heater cable CH2 Compressor 2 RK2 heater cable CC External heater cable F Fuse 5x20 4A K1 Compressor 1 thermal protection device K2 Compressor 2 thermal protection device VENT Fan RCP Phase controller KMC1 Compressor 1 contactor KMC2 Compressor 2 contactor RK...

Страница 22: ...ing interval efficiency 5 COPcyc Température maximale eau de chauffage Max temperature for the heating water WTOL 70 Tj 15 C 5 COPd 2 03 Température limite de fonctionnement Operating limit temperature TOL 20 Mode veille Standby mode 6 PSB 0 005 Mode résistance de carter Crankcase heater mode 6 PCK 0 005 Mode arrêt OFF mode 6 POFF 0 023 Mode arrêt thermostat Thermostat off mode 6 PTO 0 008 Régulat...

Страница 23: ...tach a copy of mandate Connections Single phase o Three phase o Circuit breaker Setting ________A Heat Pump HP Type de pump Single phase o Three phase o Make model and reference number ______________________________________________________________ Type of compressor without back up heating Single phase o Three phase o Nominal heating capacity of the Heat Pump without elements for back up heating k...

Страница 24: ...de la République CS 40029 80210 Feuquières en Vimeu Spare parts department Tel 03 22 61 21 21 Fax 03 22 61 33 35 E mail pieces auer fr Technical assistance department E mail sav auer fr Technical assistance service is reserved for professionals ...

Отзывы: