INSTALLATION: SETUP TOOLS
MVS Series
23
710-03261-00D
Setup Tools
7
MVS soft starters offer programming and simulation features specifically designed
to make commissioning safe and easy.
7.1 Simulation
Tools
Software simulation functions allow the MVS to be tested without a motor
connected, to confirm that the soft starter's control circuits are operating correctly.
There are three simulation modes available:
•
Run simulation: simulates a motor starting, running and stopping to confirm
that the soft starter has been installed correctly.
•
Protection simulation: simulates activation of each protection mechanism to
confirm that the soft starter is responding correctly in each situation.
•
Signalling simulation: simulates output signalling to confirm that outputs are
operating correctly.
For details of the simulation functions, refer to
Commissioning Menu: Simulation
Tools
on page 30.
7.2
Low Voltage Test Mode
The MVS can be connected to a low voltage motor (
≤
500 VAC) for testing. This
allows the user to thoroughly test the soft starter and its associated power and
control circuits. The low voltage test mode provides a means of testing the soft
starter's configuration without requiring a full medium voltage test facility. To
perform the low voltage test, one non-conduction resistor assembly must be
connected to each phase arm (three resistor assemblies are supplied with the soft
starter).
During the low voltage test, the soft starter's input, output and protection settings
can be tested. Low voltage mode is not suitable for testing soft starting or soft
stopping performance.
To operate the MVS in low voltage test mode:
1. Isolate the soft starter from the motor and the mains supply.
2. Connect one non-conduction resistor assembly to each phase arm.
For V02, V03 and V04 units:
Clip one end of the resistor assembly to the plated hole on the non-conduction
PCB. The non-conduction PCB is located at the top of the phase arm, behind
the long round grading resistor (on the left hand side when viewed from the
front). Clip the other end of the resistor assembly to any point on the steel
bracket behind the other grading resistor.
Non-conduction
PCB
Non-conduction
resistor assembly
Steel
bracket
Chapter 7
Содержание MVS0080
Страница 1: ...G U I D E MVS SERIES SOFT STARTERS PRODUCT ...
Страница 22: ...INSTALLATION CONTROL CIRCUITS MVS Series 21 710 03261 00D 6 2 Internal Wiring Diagram 4 Internal Wiring ...
Страница 42: ...OPERATION OPERATION MVS Series 41 710 03261 00D Diagram 5 Slip Ring Motor Connection ...
Страница 52: ...NOTES MVS Series 51 710 03261 00D ...
Страница 53: ...NOTES 710 03261 00D 52 MVS Series ...