OPERATION: KEY FEATURES
MVS Series
25
710-03261-00D
Operation
Key
Features
MVS soft starters offer several special functions to ensure ease of use and to
provide optimal motor control in all environments and applications.
Dual Parameter Set
The MVS can be programmed with two separate sets of operating parameters.
This allows the soft starter to control the motor in two different starting and stopping
configurations.
The secondary motor settings (parameter groups 12 and 13) are ideal for slip-ring
motors, dual speed motors, or conventional (squirrel-cage) motors which may start
in two different conditions (such as loaded and unloaded conveyors).
NOTE
MVS soft starters are not suitable for controlling two separate motors.
The secondary parameter set should only be used for a secondary
configuration of the primary motor.
Customisable Protection
The MVS offers comprehensive protection to ensure safe operation of the motor
and soft starter. The protection characteristics can be customised extensively to
match the exact requirements of the installation.
Advanced Thermal Modelling
Intelligent thermal modelling allows the soft starter to predict whether the motor can
successfully complete a start. The MVS uses information from previous starts to
calculate the motor's available thermal capacity, and will only permit a start which
is predicted to succeed.
Comprehensive Event and Trip Logging
The MVS has a 99-place event log to record information on soft starter operation.
A separate trip log stores detailed information about the last eight trips.
Informative Feedback Screens
A large-format screen allows the MVS to display important information clearly.
Comprehensive metering information, details of starter status and last start
performance allow easy monitoring of the starter's performance at all times.
Section 3
Содержание MVS0080
Страница 1: ...G U I D E MVS SERIES SOFT STARTERS PRODUCT ...
Страница 22: ...INSTALLATION CONTROL CIRCUITS MVS Series 21 710 03261 00D 6 2 Internal Wiring Diagram 4 Internal Wiring ...
Страница 42: ...OPERATION OPERATION MVS Series 41 710 03261 00D Diagram 5 Slip Ring Motor Connection ...
Страница 52: ...NOTES MVS Series 51 710 03261 00D ...
Страница 53: ...NOTES 710 03261 00D 52 MVS Series ...