Appendix 1   

Managing the heat generated by the controller 

 
The heat dissipation of the controller is directly related to the electric current drawing 
power of the heater. If your cooker consumes less than 10 ampere of current or your pot 
is less than 5 gal (19 liters), you do not need to worry about the heat generated by the 
controller. 
 
Sometime, the AC current requirement might not be marked on the cooking appliance. 
To find out how much current it will draw, divide the power (in wattage) by the line voltage, 
for example, an 1800 watts 120V heater will draw 15 A. A 2000 watts 240 V heater will 
draw 8.3 Ampere.   
 

Why the heat becomes an issue? 

The solid state relay (SSR) used in the controller is a critical component for the precision 
temperature control. With SSR, the power can be switched at high speed with no noise 
and no life time limitation. Compared with electromechanical relay, however, SSR has 
one drawback. It generates heat when passing the current. SSR is made of 
semiconductor that has a limited conductance. When passing current, the heat will be 
produced from the resistance. Each ampere of current will produce about 1.3 watts of 
heat. When 12 Amp is passing through the controller, 16 watt of heat is produced in the 
controller. As more heat is produced, the temperature inside the controller will rise. If it 
reaches to higher than 70 C, it can shorten the life or even damage some the 
components in the controller. The temperature inside of the controller depends on the 
amplitude of the current, how long the controller needs to run at full power and the 
ambient temperature. 
 
The heat is only an issue during the start of the heating when the heater is running at full 
power. Once the temperature is close to the set point, the controller will probably need 
less than 50% of the power to maintain the temperature. Since the heat is directly related 
to the current passing the controller, the heat produced at steady state will be 
insignificant and can be ignored. 
 

When the heat becomes an issue? 

 
This controller can run at 10 A continuously without worry of the temperature of the 
controller. At 12A, the temperature of the controller will increase with time. The bottom of 
the controller where the heat sink is located can rise by 63F (35 C) from ambient if 
running at full power continuously for 90 minutes.    For this reason we don’t recommend 
running the controller at full power for more than 90 minutes. For 120 VAC, 15 A for 90 

 
 

16

 

 
 

Содержание WS-1500APH

Страница 1: ...igh wattage appliances and your safety is paramount SAFETY WARNINGS This controller is designed only to be used with devices that have limited power and their own thermal cut off protection such as a...

Страница 2: ...er is specially designed for high power applications Do not replace it with regular computer power cord when heating device is more than 1200 watts This controller is designed to control the devices r...

Страница 3: ...aximum current required In addition an adaptor that can convert the output socket NEMA 5 15 to the socket of local standard is needed Operating Instructions 1 Description of the controller Fig 1 Front...

Страница 4: ...nd the Timer Status Indicator 8 is lit the value displayed in the Parameter Window is time that has been passed since power up If it is flashing but Timer Status Indicator 8 is off the value displayed...

Страница 5: ...ach step contains the temperature C0X and time duration T0X setting They are represented by the symbol C0X and T0X where X is the step number e g Step 4 temperature is represented by C04 and step 4 ti...

Страница 6: ...firmed After programming the necessary steps for cooking you can finish programming by pressing the SET continuously until it passed T06 and display the current temperature You can also leave the cont...

Страница 7: ...e controller is in step 3 of cooking When 8 is on lit and 7 is flashing at the same time LED is in timer mode and shows the actual time passed since the controller was last powered up Please note that...

Страница 8: ...efficiently it transfers heat For example consider the difference between a heat lamp and a hot plate When electricity is applied to a heat lamp it begins to heat instantaneously and when it s turned...

Страница 9: ...ash alternately between A and the current water bath temperature which indicates auto tuning is in progress When the display stops flashing the auto tuning is finished Now the newly calculated PID par...

Страница 10: ...when changing the temperature unit to Fahrenheit I Integral time The unit is in seconds This parameter controls the output of controller based on the difference between the measured and set temperatu...

Страница 11: ...in to confirm the change The display will show the d for a second and its value next Use the same P setting procedure to set the d value When finished press the SET again to confirm the change The nex...

Страница 12: ...mized temperature control system should consume about 25 of the heater power at set temperature steady state for example if you found out that only 50 watts of energy is needed to maintain the tempera...

Страница 13: ...set value Setting the output reduction The parameter window will first show OUt for a second and then its value Use and keys to change OUt value to your desired limit value and press SET Setting Celsi...

Страница 14: ...not cover damage caused by misuse abuse negligent handling or damage due to faulty packaging or mishandling in transit This warranty does not cover damage or defects caused by or resulting from damag...

Страница 15: ...the package as damage in shipping is not covered by your warranty Mark the outside of your package ATTENTION CUSTOMER SERVICE We are constantly striving to improve our products and therefore the speci...

Страница 16: ...e about 1 3 watts of heat When 12 Amp is passing through the controller 16 watt of heat is produced in the controller As more heat is produced the temperature inside the controller will rise If it rea...

Страница 17: ...e current is much lower making heat not an issue 2 Limit maximum output power If you set output reduction parameter to 80 then a 15 A heater will become a 12 A heater It will take 25 longer time to he...

Страница 18: ...connected to the power strip by the 16 AWG power cord supplied blue arrows The generator is connected to the power strip by the power cord from Bradley green arrows The controller output is connected...

Страница 19: ...wer jumper cord provided by the Bradley blue arrows It is the cord that used to connect the generator to smoker The controller output is connected to the smoker by the power cord that came with contro...

Страница 20: ...ble This is especially the problem for the Bradley Original Smoker because of its black color The controller should be placed away from direct sun light also Although the controller uses a high intens...

Страница 21: ...lock the hot air from going up e Operating the controller when ambient temperature is below 32F 0C The controller reading is only accurate for temperature 32 F 0 C In addition if the ambient temperatu...

Отзывы: