background image

         AUBER INSTRUMENTS

  

 

 

 

 

 

 

 

         

WWW.AUBERINS.COM  

 

 

         2017.01                                                                     

   

                                                       P5/5 

 

different units. For example, if Channel 1 is reading an EGT probe showing 
1000°F, while the Channel 2 is reading a pressure sender showing 50 PSI, 
when you press the DOWN key, the lower window will show 950.     
 

E. Application Examples

 

E.1 Measuring Exhaust Gas Temperature (EGT) and Boost Pressure.  

The SYL-2813 gauge has two input channels and it can read two different 
types of signal simultaneously. The wiring diagram of connecting an EGT 
sensor and a MAP sensor to SYL-2813 is shown in Figure 8. The steps for 
setting up the gauge for this application is also given in this section. 
 

E.1.a) Wire the EGT sensor (K type thermocouple in this example) and the 

MAP sensor (AUBER-303) as shown the Figure 7, where the EGT sensor is 
connected to channel 1 and MAP sensor is connected to channel 2. 

E.1.b) Press SET, change the code to 0089 to enter the Basic Parameter 

Setting mode. Set 

Int1

 to “k” and 

Int2

 to “0-5v”.  

E.1.c) To display the pressure in Bar with 0.01 bar resolution, set the decimal 
point 

dot2 

= 2 (this step needs to be done before set 

PuL2

 and 

PuH2

). Set the 

PuL2

 = -0.38 and 

PuH2

 = 03.38. (Please see the installation guide for AUBER-

303 from the product page on our website).  
E.1.d) To display the pressure in PSI with 0.1 PSI resolution, set the decimal 
point 

dot2 

= 1. Set 

PuL2

 = -05.4 and 

PuH2

 = 048.9.

 

 
 

6

7

8

9

10

14

13

12

11

1

2

3

4

5

SYL-2813

 

EGT sensor 

(K Type Thermocouple)

+

 

MAP  sensor

Signal

12 VDC 

buzzer

(optional)

5V  

power

Ground

DC 12V

 

Figure 8. SYL-2813 wiring example of EGT sensor in Channel 1 and MAP sensor in 
Channel 2. 

 
 

E.2 Measuring Exhaust Gas Temperature (EGT) and Oil Temperature.  

To measure temperatures with one thermocouple sensor and one RTD sensor, 
you can wire the sensors to SYL-2813 gauge as the diagram in Figure 9. In this 
diagram, the thermocouple is connected to the Channel 1, and the RTD sensor 
is connected to the Channel 2. You will need to change the input types and 
other parameters for Channel 1 and 2 accordingly. 
 

E.3 Read Temperature Difference Between Two Probes. 

In this example, a type K thermocouple is wired to channel 1, and a PT100 
probe is wired to channel 2 (see Figure 10 for wiring). To set up the gauge to 
show the temperature difference in the lower window, please use access code 
0036, and then set parameter 

Fun1

 = on. In normal operation mode, the top 

display will show reading from probe #1, and the lower display will show 
reading from probe #2. To check the difference, press the DOWN “V” key 
shortly, and the lower display will show the difference. Press the DOWN key 
again, lower display will be switched back to reading from probe #2.  
 
 

6

7

8

9

10

14

13

12

11

1

2

3

4

5

SYL-2813

 

EGT sensor 

(K Type Thermocouple)

+

 

12 VDC 

buzzer

(optional)

DC 12V

Oil/Water Temperature 

sensor (RTD)

 

Figure 9. SYL-2813 wiring example of an EGT sensor in Channel 1 and an Oil/Water 
Temperature Sensor in Channel 2. 

 

 

Figure 10. Wiring diagram of connecting two temperature probes to SYL-2813A 
gauge and show the temperature difference between two probes.  
 
(End) 
 

Auber Instruments 

5755 North Point Parkway, Suite 99 

Alpharetta, GA 30022, USA 

www.auberins.com

 

E-mail: [email protected] Tel: 770-569-8420 

 

Copyright 2007-2019. Auber Instruments All Rights Reserved. 

No part of this manual shall be copied, reproduced, or transmitted in any way without the prior, written 

consent of Auber Instruments. Auber Instruments retains the exclusive rights to all information 

included in this document.

 

Содержание SYL-2813A

Страница 1: ... to enter the setting mode In Parameter Setting Mode press it to select a parameter or to save the value 4 SHIFT key In the Parameter Setting Mode press this key to select the digit to be changed In the Normal Operating Mode press this key to toggle the displayed variables between Process Values PV1 and PV2 Maximum Value of Channel 1 MA1 and MAt1 and Maximum Value of Channel 2 MA2 and MAt2 See the...

Страница 2: ...T1 and T3 connect white wire to T5 for a two wire RTD connect the red wire to T3 and connect the white wire to T5 and short T3 and T1 See Figure 4 b 5 Wiring of Pressure Sensors In Channel 1 connect the power source wire of the sensor to T9 the signal wire of the sensor to T13 and the ground wire of the sensor to T1 In Channel 2 connect the power source wire of the sensor to T9 the signal wire of ...

Страница 3: ... SET key once the upper window will display pass and the lower window will display 0000 Change the number to 0089 in the lower window and press SET again to enter the Parameter Setting Mode Two parameters from the parameter list will be displayed The upper window will flash the first parameter the lower window will steadily display the next parameter on the list see table 3 Use UP or DOWN key to s...

Страница 4: ...36 D 3 c Check the Peak Value To check the Peak Value during operation mode use the SHIFT key Press once the PK1 indicator will be on MA1 and MAt1 will be displayed in the upper and lower window respectively Press key again the PK2 indicator will be on MA2 and MAt2 will be displayed in the upper and lower window respectively press again to exit this mode and return to the Normal Operating Mode D 3...

Страница 5: ... Oil Temperature To measure temperatures with one thermocouple sensor and one RTD sensor you can wire the sensors to SYL 2813 gauge as the diagram in Figure 9 In this diagram the thermocouple is connected to the Channel 1 and the RTD sensor is connected to the Channel 2 You will need to change the input types and other parameters for Channel 1 and 2 accordingly E 3 Read Temperature Difference Betw...

Отзывы: