background image

         AUBER INSTRUMENTS

  

 

 

 

 

 

 

 

         

WWW.AUBERINS.COM  

 

 

         2017.01                                                                     

   

                                                       P3/5 

 

Psb1 

PSb1 

Input Offset 1 

-1000 ~ 1000 

Int2 

Int2 

Input type of Channel 2 

See Table 3 

Cu50 

Dot2 

dot2 

Decimal Point Position 2 

0000 ~ 0.000 

Pul2 

PuL2 

Scale Low 2 

-1999 ~ 9999 

3000 

Puh2 

PuH2 

Scale High 2 

-1999 ~ 9999 

4000 

Psb2 

PSb2 

Input Offset 2 

-1000 ~ 1000 

C-F 

C-F Temperature 

Unit 

1 & 2 

C, F 

 

Filt 

Filt 

Filter Coefficient 

0 ~ 3 

End 

End Exit 

 

 

 

 

Note 1

. All 19 input types are available to Channel 1. The 375R, 10 mA, 20 

mA, and 4 - 20 mA input types are not available to Channel 2. 
 

Note 2

. Dot parameter does not work for temperature input sensor 

(thermocouple, RTD). Thermocouple will be displayed as integer (XXXX). RTD 
will be displayed with 1 decimal place (XXX.X). 
 

Note 3

. Only valid for input types that are neither TC nor RTD. 

 

Note 4

. Display Value = gauge r 

PSb

. Only valid for TC and RTD 

signals. To enter negative value, please use shift key to shift to first left digit, 
then use UP and DOWN key to scroll to the negative sign. 
 

Note 5

. Digital Filtering Coefficient: 0, no filter; 1, weak; 2, medium; 3, strong.     

 
 
Table 4. Input type options. 

Symbol 

Input Type 

Gauge Range 

Resolution 

Accuracy 

Impedance 

TC, Type T 

-200 ~ 400 °C 

1 °C (°F) 

0.3 % 

100 K 

TC, Type R 

-50 ~ 1600°C 

1°C (°F) 

0.3 % 

100 K 

TC, Type J 

-200 ~ 1200°C 

1°C (°F) 

0.3 % 

100 K 

Wre 

TC, WRe3/25 

0 ~ 2300°C 

1°C (°F) 

0.2 % 

100 K 

TC, Type B 

260 ~ 1800°C 

1°C (°F) 

0.2 % 

100 K 

TC, Type S 

-50 ~ 1600°C 

1°C (°F) 

0.3 % 

100 K 

TC, Type K 

-200 ~ 1300°C 

1°C (°F) 

0.2 % 

100 K 

TC, Type E 

-200 ~ 850°C 

1°C (°F) 

0.2 % 

100 K 

P100 

RTD, Pt100 

-199.9 ~ 
600.0°C 

0.1°C (°F) 

0.2 % 

(0.2 mA) 

Cu50 

RTD, Cu50 

-50.0 ~ 150.0°C 

0.1°C (°F) 

0.5 % 

(0.2 mA) 

375R 

375 

, Pressure * 

the display 

values 

can be set to any 

range within 

(-1999 ~ 9999) 

16 Bit A/D 

0.2 % 

(0.2 mA) 

75mv 

75 mV 

0.1 % 

100 K 

30mv 

30 mV 

0.1 % 

100 K 

0-5v 

0 - 5 V 

0.1 % 

100 K 

1-5v 

1 - 5 V 

0.1 % 

100 K 

10v 

0 - 10 V 

0.1 % 

100 K 

0-10 

0 - 10 mA * 

0.3 % 

150 K 

0-20 

0 - 20 mA * 

0.2 % 

150 K 

4-20 

4 - 20 mA * 

0.2 % 

150 K 

(TC: thermocouple. RTD: resistance temperature detector.) 

Note

: * These sensor types are not available to channel 2.  

 

D.1.b) The Procedure of Setting Basic Parameters

 (see Figure 5). 

To set or view Basic Parameters, press SET key once, the upper window will 
display “pass” and the lower window will display “0000”. Change the number to 

“0089” in the lower window and press SET again to enter the Parameter 
Setting Mode. Two parameters from the parameter list will be displayed. The 
upper window will flash the first parameter, the lower window will steadily 
display the next parameter on the list (see table 3). Use UP or DOWN key to 
scroll to the desired parameter (flashing in the upper window) and press SET to 
view the value. For numerical values, use SHIFT key to go to any digit that 
needs to be changed and use UP or DOWN key to change the value. For letter 
values, use UP or DOWN key to select from available values. Then press SET 
to save and exit to the parameter list. To exit this mode, use UP or DOWN key 
to scroll to “End” (flashing in the upper display window) and press SET. See 
Figure 4 for a schematic diagram of how to change Basic Parameters.   
 

PV2

PV1

dot1

Int1

PuL1

dot1

Int1

End

0-5v

Int1

0000

PAS S

SET

SET

enter code 

0089 

UP key

SET

Basic Parameter 

Setting Mode

SET

Normal 

Operating Mode

 

Figure 5. Schematic diagram of how to set Basic Parameters. 

 
 

D.2 Alarm Parameters 

(Press SET Key and enter 0001 to enter setting mode)

   

D.2.a) Alarm Parameters and Alarm Relays 

Relay J1 and J2 are normally open (NO) relays associated with alarm settings 
of Channel 1 and Channel 2 respectively. Each relay has two alarm 
parameters 

AH

 and 

AL

. The parameter 

AH

 (

AH1

 for Channel 1, or 

AH2

 for 

Channel 2) is the relay pull-in temperature, and the parameter AL (

AL1

 for 

Channel 1, or 

AL2

 for Channel 2) is the relay drop-off temperature. The range 

for each alarm parameter is shown in Table 5. If 

AH

 > 

AL

, relay acts as a high 

temperature alarm relay; if 

AH

 < 

AL

, relay acts as a low temperature alarm 

relay; if 

AH

 = 

AL

, the relay/alarm is disabled. Please see Note 6, Figure 7, and 

Figure 8 for details.      
   
Table 5. Alarm Parameters. 

Symbol Name Description 

Range 

Initial Note 

AH1 

AH1 

J1 on 

-1999 ~ +9999 

800 

AL1 

AL1 

J1 off 

-1999 ~ +9999 

900 

AH2 

AH2 

J2 on 

-1999 ~ +9999 

800 

AL2 

AL2 

J2 off 

-1999 ~ +9999 

900 

 
 

Note 6

. Relay Action Setting.  

For either J1 or J2 relay: 
1). When 

AH

 = 

AL

, relay is disabled. 

2). When 

AH

 > 

AL

, relay is set as high limit alarm (see Figure 6). 

3). When 

AH

 < 

AL

, relay is set as low limit alarm (see Figure 7). 

Содержание SYL-2813A

Страница 1: ... to enter the setting mode In Parameter Setting Mode press it to select a parameter or to save the value 4 SHIFT key In the Parameter Setting Mode press this key to select the digit to be changed In the Normal Operating Mode press this key to toggle the displayed variables between Process Values PV1 and PV2 Maximum Value of Channel 1 MA1 and MAt1 and Maximum Value of Channel 2 MA2 and MAt2 See the...

Страница 2: ...T1 and T3 connect white wire to T5 for a two wire RTD connect the red wire to T3 and connect the white wire to T5 and short T3 and T1 See Figure 4 b 5 Wiring of Pressure Sensors In Channel 1 connect the power source wire of the sensor to T9 the signal wire of the sensor to T13 and the ground wire of the sensor to T1 In Channel 2 connect the power source wire of the sensor to T9 the signal wire of ...

Страница 3: ... SET key once the upper window will display pass and the lower window will display 0000 Change the number to 0089 in the lower window and press SET again to enter the Parameter Setting Mode Two parameters from the parameter list will be displayed The upper window will flash the first parameter the lower window will steadily display the next parameter on the list see table 3 Use UP or DOWN key to s...

Страница 4: ...36 D 3 c Check the Peak Value To check the Peak Value during operation mode use the SHIFT key Press once the PK1 indicator will be on MA1 and MAt1 will be displayed in the upper and lower window respectively Press key again the PK2 indicator will be on MA2 and MAt2 will be displayed in the upper and lower window respectively press again to exit this mode and return to the Normal Operating Mode D 3...

Страница 5: ... Oil Temperature To measure temperatures with one thermocouple sensor and one RTD sensor you can wire the sensors to SYL 2813 gauge as the diagram in Figure 9 In this diagram the thermocouple is connected to the Channel 1 and the RTD sensor is connected to the Channel 2 You will need to change the input types and other parameters for Channel 1 and 2 accordingly E 3 Read Temperature Difference Betw...

Отзывы: