background image

  AUBER INSTRUMENTS

    

 

 

     

 

 

 

             

WWW.AUBERINS.COM  

 

2021.10                                                                                                                                                                                                          P1/6

 

SYL-2362A2 PID TEMPERATURE CONTROLLER  

INSTRUCTION MANUAL  

Version 2.6 (Oct, 2021) 

 

 

Caution 

 

This  controller  is  intended  to  control  equipment  under  normal  operating 
conditions. If failure or malfunction of it could lead to an abnormal operating 
condition that could cause personal injury or damage to the equipment or other 
property,  other  devices  (limit  or  safety  controls)  or  systems  (alarm  or 
supervisory) intended to warn of or protect against failure or malfunction of the 
controller  must  be  incorporated  into  and  maintained  as  part  of  the  control 
system. 

 

Installing the rubber gasket supplied will protect the controller front panel from 
dust and water splash (IP54 rating). Additional protection is needed for higher 
IP rating. 

 

This  controller  carries  a  90-day  warranty.  This  warranty  is  limited  to  the 
controller only. 

 
1. Features 

 

The PID control with artificial intelligent enhancement for precision temperature 
control.  

 

Auto-tuning function can find the best PID parameter automatically.  

 

On/off  control  mode  for  refrigerator,  motor  and  solenoid  valve  control 
application. 

 

Bumpless transfer between Auto and Manual control. 

 

Limit control for safety protection and special applications.  

 

The output can be set for SSR output control or relay contactor control by the 
user.  

 

Two contact relays can be configured as one PID and one alarm output, dual 
alarm outputs, or dual On/off control.  

 

Support 10 different types of commonly used temperature sensor inputs. 

 
2. Specification 

Input type 

Thermocouple (TC): K, E, S, R, J, T, B, WRe3/25 
RTD (Resistance temperature detector): Pt100, Cu50 

Input range 

See table 2 

Display 

Dual lines, four digits, ° F or ° C 

Display 
resolution 

1° C, 1° F; or 0.1° C, 0.1° F with Pt100 

Accuracy 

± 0.2% or ± 1 unit of full input range 

Control mode 

PID, On-off. Limit, Manual 

Output mode 

Relay contact: 3A at 240VAC, SSR: 8VDC, 12 mA. 

Alarm 

Process high/low alarm 

Power 
consumption 

<2 Watt 

Power supply 

85~260VAC/50~60Hz or 85-360VDC 

Sample rate 

4 samples/sec 

Operating 
condition 

0 ~ 50 ° C, 

85%RH 

Mounting cutout 

45 x 45 mm 

Dimension 

48x48x75mm (1/16 DIN) 

 

3. Front Panel and Operation 

 

 
 
 
 
 
 
 
 
 
 
 

Figure 1. Front panel

 

 

 AL-1 Relay J1 output indicator 

      AL-2 Relay J2 output indicator 
      AT/M- On for manual mode. Blinking during auto-tuning process  
      OUT- SSR output indicator  

 Value increment/Select next parameter 

 Value decrement/Select previous parameter 

 Auto tuning/Digit shift 

 Set/Confirm/Manual Auto switching/Reset (for Limit control mode)  

 Measured temperature, or, Process Value (PV)  

 Set temperature, or, Set Value (SV) 

 

4. Terminal Wiring (back view)

 

6

7

8

9

10

11

12

13

14

1

2

3

4

5

+

-

SSR

J1

+ -

J2

RTD

TC

           

Po wer

                   

AC/DC

           85-260V

R

R

W

NO

NC

NC

NO

to

 te

rm

in

al

 11

 

Figure 2. Wiring diagram

 

4.1 Sensor connection 
4.1.1 Thermocouple 

The thermocouple should be connected to terminals  9 and 10. Make sure that 
polarity  is  correct.  There  are  two  commonly  used  color  codes  for  the  K  type 
thermocouple. US color code uses yellow (positive) and red (negative). Imported 
DIN color code uses red (positive) and green/blue (negative). The temperature 
reading will decrease as temperature increases if the connection is reversed. 
 

Instruction Manual

 

 