background image

         AUBER INSTRUMENTS

  

 

 

 

 

 

 

 

         

WWW.AUBERINS.COM  

 

 

         2021.10                                                                    

   

                                                       P5/6 

 

Relay on

Start

outy=5, SV=100, Hy=3. The 
heating stops after it reached 100 
degree.

PV

SV

SV-Hy

100

97

mode, press and hold SET key until the 

AT/M

 indicator turned off. This controller 

offers 

bumpless

 switch from the PID to manual mode. If the controller outputs 

75% of power at PID mode, the controller will stay at 75% when it is switched to 
the manual mode, until it is adjusted manually. 
 

9. Limit control mode. 

 

The Limit control mode will shut the heater off when SV is reached. The heater will 
not be turned on again until the controller is reset manually (press the SET key for 
5 seconds). When powered on, it  will not start the  heating until reset button is 

pressed. The controller can’t be reset when the temperature is within 

Hysteresis 

Band (Hy).  
To use the Limit control mode, set outy to 5 or 6. Then, set the Hy to the range that 
you want reset to be blocked. To start the heating or cooling, press SET key for 5 
second or until the output indicator is on. 
 
 
 

 
 
 
 
 

Figure 9. Limit control mode 

 

 
10. Application Example  

10.1

 A water tank needs to be controlled at 150.0 ° F.  Alarm 1 will go off if T > 

155.0 ° F, Alarm 2 will go off, if T> 170.0 ° F. The power source is 240V AC. The 
heating element is switched by a SSR. A Pt100 RTD sensor with 0.1°  resolution 
input is used as the temperature sensor.  
a. Wiring diagram 

1

+ -

4

SSR

6

7

8

9

10

11

12

13

14

1

2

3

4

5

J1

J2

Fuse

L2

L1

RTD

R

R

W

Heater

240VAC

2

3

Alarm1

240V buzzer

Alarm2

240V buzzer

 

Figure 10. Typical wiring set up for beer brewing and bird incubator. For smoker 
control, the RTD sensor should be replaced by K type thermocouple 
 
b. Parameter setting. These are the parameters that need to be changed from 
the initial value: Inty=P10.0, SV=150.0 ° F, AH1=155.0 ° F, AL1=154.0 ° F, 
AH2=170.0 ° F, AL2=169.0 ° F. 
 
Auto-tune is used to set the PID parameters.  Power up the controller. Press and 
hold the > key until 

AT

 starts to blink. The controller starts the Auto-tuning. When 

the 

AT

 stops blinking, the new PID parameters are generated for the system. 

The controller is in normal operation mode. The tank will be maintained at 150.0 ° F.  

Please note that you don’t not have to wire or set the alarm to control the 

temperature. 

 

10.2 

A furnace needs to be controlled at 1200 ° F. The power source is 120V AC. 

The heating element is 1800W/120V. It is switched on/off by a contactor. The coil 
voltage  of  the  contactor  is  120V  AC.  A  K  type  thermocouple  is  used  as  the 
temperature sensor. 
 
a. Wiring diagram 

6

7

8

9

10

11

12

13

14

1

2

3

4

5

J2

+ -

K type TC

L

N

Fuse

Contactor

Heater

120VAC

 

Figure 11. Typical wiring set up for powder coating oven and kiln. This diagram 
also applies to 240V AC power system, if both the heater and the coil voltage of 
the contactor are 240V AC. 
 
b. Parameter setting.  These are the parameters that need to be changed from the 
initial value: outy=1 for PID mode with J2 relay output; ot=20 to increase the relay 
life time; SV=1200 ° F for the target temperature. 
 

10.3 Drive a 24VAC solenoid valve directly in heating mode 

A 24VAC solenoid valve is switched by J2 relay in on/off mode. The valve will be 
on until temperature reaches 200 ° F. Then, it will shut off. When the temperature 
drops to below 195 ° F, it will be on again. Power source is 120V AC. A K type 
thermocouple is used as the temperature sensor.  
a. Wiring diagram 

6

7

8

9

10

11

12

13

14

1

2

3

4

5

J2

+ -

K type TC

L

N

S

Solenoid valve

24VAC

120VAC

Fuse

 

Figure 12. Typical wiring set up for a 24V gas, hot water valve, or a contractor with 
24V coil voltage 
 
b. Parameter setting.  These are the parameters that need to be changed from the 
initial  value:  outy  =  4  for  on/off  mode  with  J2  relay  output;  Hy  =  5  degree, 
SV=200° F for the target temperature. Note, if this is to control a contactor with 24V 
coil, PID mode should be used. The setting should be same as example 2 except 
the SV value. 