10.4 Control a small load without using any external SSR or relay

a. Wiring diagram 

6

7

8

9

10

11

12

13

14

1

2

3

4

5

J2

+ -

K type TC

L

N

Fuse

Heater/cooler

120VAC

 

Figure 13. Typical wiring set up for driving a 120V AC heater or cooler directly.  
Only low power device can be wired in this way. The current limit for resistive 
load is 3 Amp. The current limit for inductive load is lower, depending on the 
inductance. 
 
b. Parameter setting.  These are the parameters that need to be changed from the 
initial value: outy= 1, 4 or 5 for J2 relay output depending the control mode. ot=20 
to increase the relay life time. Rd=1 if the load is a cooling device. 
 

10.5 Drive a 120V solenoid valve directly in cooling mode 

a. Wiring diagram 

6

7

8

9

10

11

12

13

14

1

2

3

4

5

J2

L

N

S

120V

Solenoid valve

120VAC

Fuse

RTD

R

R

W

Alarm

120V buzzer

 

Figure 14. A simple auto draw-off system setup for maple syrup. Only low power 
solenoid valve (cooler) can be wired in this way. The current limit for resistive 
load is 3 Amp. RTD sensor is used for better accuracy (e.g. 

PL6350

). One 120V 

buzzer is wired to the J1 relay, to work as a high temperature alarm.  
 
b. Parameter setting. Set SV = 219° F. To use solenoid valve as a cooling device, 
please set outy = 4 (on/off mode), and rd = 1 (cooling mode). Set ot = 20 to increase 
the relay life time. Adjust Hy (hysteresis band) accordingly.  
 

11. Error Message and trouble shooting

 

11.1 Display EEEE 

This  is  an  input  error  message.  The  possible  reasons  are,  the  sensor  is  not 
connected correctly; the input setting is wrong type; or the sensor is defective. If 
this happens when using thermocouple sensor, you can short terminal 9 and 10. 
If the display shows ambient temperature, the thermocouple is defective. If this 
happens when using the RTD sensor, check the input setting first because most 
controllers are shipped with input set for thermocouple. Then check the wiring. The 

two red wires should be on terminal 9 and 10. The clear wire should be on terminal 
8. 

 

 
11.2 No heating 

When controller output is set for relay output, the “AL2” LED is synchronized with 

output  relay.  Wh

en  controller  output  is  set  for  SSR  output,  the  “OUT”  LED  is 

synchronized with SSR control output. If there is no heat when it is supposed to, 
check the AL2 or OUT first. If it is not lit, the controller parameter setting is wrong. 
If it is on, check external switching device (if the relay is pulled-in, or the red LED 
of the SSR). If the external switching device is on, then the problem is either the 
external switching device output, its wiring, or the heater. If the external switching 
device is not on, then the problem is either the controller output, or the external 
switch device. 

 
11.3 Poor Accuracy

 

Please make sure calibration is done by immersing the probe in liquid. Comparing 
with  reference  in  air  is  not  recommended  because  response  time  of  sensor 
depends on its mass. Some of our sensor has response time >10 minutes in the 
air. When the error is larger than 5 ° F, the most common problem is improper 
connection between the thermocouple and the controller. The thermocouple needs 
to  be  connected  directly  to  the  controller  unless  thermocouple  connector  and 
extension  wire  is  used.  A  copper  connector,  copper  wire,  or  thermocouple 
extension wire with wrong polarity connected on the thermocouple will cause the 
reading drift more than 5 ° F. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Auber Instruments Inc. 

5755 North Point Parkway, Suite 99, 

Alpharetta, GA 30022 

www.auberins.com 

Email: [email protected] 

 

Copyright ©  2021 Auber Instruments Inc. All rights reserved. 

No part of this datasheet shall be copied, reproduced, or transmitted in any way 

without the prior, written consent of Auber Instruments. Auber Instruments retains 

the exclusive rights to all information included in this document. 

Отзывы: