                                                       P2/4 

 

6.b) 

Connect a DC logic signal (TTL or CMOS or voltage in the range from 3 to 

30 VDC) between the terminal (3, 4 or 5) to the COM (1). Please note, the 
function is rising-edge triggered. The logic signal should normally be at a high 
level. The function starts when the signal goes from low to high. If you have an 
inverted logic signal, you need to connect a NPN transistor between the 
terminal and COM; add 10Kohm resistor to the gate for signal input.

 See 

Figure 6 for details.  
7. Terminal 2 is reserved for customized applications.  
 

Note for terminal 3, 4, and 5.

 These terminals are activated by the rising 

phase of control signal. If the control signal is from a NO switch that is 
connected to the terminal, the action starts when the switch is released (from 
close to open). When the control signal is received from an external device, the 
action starts as the voltage goes from low to high.  
 

5. How to Set the Timer and Relay Delay Time T1/T2 

Press “SET” key momentarily,

 and T1 will show up at the top display. Use Up 

and Down key to set the value. Press SET again to set the T2 (only for delayed 
interval or cycle mode). Press SET key to confirm the setting and exit the timer 
setting mode.  
 
When adjusting the time, each time the Up or Down key is pressed, the value 
will increase by one unit. But if key is held, the value will continuously increase, 
as the holding time increases, the speed of number increasing will accelerate. 
You can use this feature for large number increment. When the number is 
getting close to desired value, release the key. Press it momentarily for fine 
setting adjustment.    
 

6. Programming 

0110

0110

Process Value
Set Value

SET

OUT

OFDL

OUT
OFDL

tdir
dn

SET

FUNC

SDL

RUN

RST

Func
SdL

RUN
rSt

SET

SET

Hold 3s

SET

T1

S

T2

S

tdir

dn

T1
S

T2
S

SET

PoM
ON

SET

pom

on

SET

Exit

 

Figure 3. Flow chart of how to program JSL-74A. 

 

Press the SET key for 3 seconds to enter programming mode. To reach 
individual parameter settings, use up/down key to select different programming 
values. Press the SET key to confirm and move on to next parameter. See 
Figure 3 for the procedure. For the definition of each programming value, see 
following section.  
 

Definition of Programming Parameters 
Func, timer operating function mode. 

Available options are:  

SdL

 (single delay): relay turns on at the beginning of relay delay time T1 

(OFDL); relay turns on at the end of relay delay time T1 (ONDL). It will not 
change until the timer is reset or repowered again. In Single Delay ON mode, a 
special parameter for stop function, STOP will show up in the parameter menu. 
For details please refer to note1 below. 

dint

 (delayed interval): relay turns on at the end of T1 time delay then off at the 

end of T2 time delay (OFDL); relay turns off at the end of T1 time delay then on 
at the end of T2 time delay (ONDL). There is no repeat. 

CYCL

 (cycle): repeat relay on and off in cycle. Relay turns on at the end of T1 

time delay then off at the end of T2 time delay (OFDL); relay turns off at the 
end of T1 time delay then on at the end of T2 time delay (ONDL). It will repeat 
this cycle until power is off. 
 

T1 or T2, timer range.

 Available options are:  

S

: 0.01 s ~ 99.99 s.   

M:S

: 1 s ~ 99 m 59 s. 

M

: 1 m ~ 9999 m. 

H:M

: 1 m ~ 99 h 59 m. 

H: 

1 h ~ 9999 h. 

D:H: 

1 h ~ 99 d 23h. 

 

tdir, timing direction.

 Available options are:  

up

: counting up. 

dn

: counting down. 

 

PoM, power-on memory setting. 

Available options are:

  

After a loss of power, this timer can be set to either reset when power is 
restored, or continue running from the point of power outage.  

ON

: After a loss of power, this unit will continue running from the point of power 

outage when power is restored.  

OFF

: After a loss of power, this unit will be reset when power is restored.   

 

OUT, relay output mode.

 Available options are:  

OFDL

 (off delay): relay will be on at the start of timer and off when time reach 

the set point. 

ONDL

 (on delay): relay will stay off at the start of timer and on when time reach 

the set. 
 

RUN, timer starting run mode.

 Available options are:    

PU

 (power up): When timer is powered up, timer will start counting.  

rSt

 (reset): When reset button is pressed and released, timer will start counting.  

 

 

 

 

 

Note 1

: Running the single delayed on mode. 

When running the Single Delay On mode, depending on the applications, users 
may want the relay to stay at off (initial state), or stay on (final state) when the 
operation is interrupted by stop function. Examples. A) Some user uses the 
timer to turn on a buzzer at the end of a process for notification purpose. He 
wants to be able to disable the buzzer (change to initial state) by simply 

Содержание JSL-74A

Страница 1: ...see note 1 on page 2 for details 8 Up key PAU key This key increases the value in the programming mode when timer is running pressing holding this key will pause the timer Once you release the Up key PAU key the timer will resume 9 RST key reset key When the timer is running the reset button will reset the timer If RUN parameter is set to RST pressing the button will start the timer after it has p...

Страница 2: ...see following section Definition of Programming Parameters Func timer operating function mode Available options are SdL single delay relay turns on at the beginning of relay delay time T1 OFDL relay turns on at the end of relay delay time T1 ONDL It will not change until the timer is reset or repowered again In Single Delay ON mode a special parameter for stop function STOP will show up in the par...

Страница 3: ...this example is also optional It is to show how to wire the output You can substitute it with any output such as a coffee grinder The output terminals 6 7 and 8 are from a C form internal relay It is a dry switch that does not provide the power by itself In this case the alarm is powered by the 120VAC The external switch connected to the alarm is for disabling the sound if needed 6 7 8 9 10 1 2 3 ...

Страница 4: ...top T1 Ta Tb Ta Tb T1 T2 T2 T1 T2 F cycle delay off Auber Instruments Inc 5755 North Point Parkway Suite 99 Alpharetta GA 30022 www auberins com Email info auberins com Copyright 2021 Auber Instruments Inc All rights reserved No part of this datasheet shall be copied reproduced or transmitted in any way without the prior written consent of Auber Instruments Auber Instruments retains the exclusive ...

Отзывы: