LED
DESCRIPTION
OFF
BLINKING
ON
LED 1 ON/OFF
Unit is not
energised
Unit in standby
Unit is working
LED 2 Column 2
Column 2
Repressurizing /
Column 1 Drying
Column 2 Drying /
Column 1
Regenerating
LED 3
Service advice
Service will be
needed soon
LED 4 Urgent service
Service is needed
LED 5 Column 1
Column 1
Repressurizing /
Column 2 Drying
Column 1 Drying /
Column 2
Regenerating
LED 6 Alarm
High dew point
alarm
SPECIFICATIONS
- POWER SUPPLY: 230VAC,50-60HZ ., +/-10%
-
OUTPUTS: n° 5 RELAYS , 230VAC, 5A
- IP PROTECTION : IP65 (only front panel)
- CERTIFICATION: CE
- STOCKING TEMPERATURE: -
40, +50°C
- OPERATING TEMPERATURE:
0 ,+40°C
5.2 STANDARD OPERATION
HGO and HGL have 3 different operating modes.
1.
TIMED SEQUENCE CONTROL (STANDARD):
the dryer is time controlled.
Every working phase is controlled by one of the parameter of the controller.
The end user can change the value based on the table on chapter 5.3.
2.
DEW POINT CONTROL (ENERGY SAVING):
the dryer works in Energy
saving mode connected with a dew point sensor. Controller is programmed to
work with 2 different kind of sensors.
Dryer will automatically adjust time of work, but the required dew point value
can be adjusted on the controller.
Содержание HGL 120
Страница 17: ...B Schemat przep ywu powietrza...
Страница 18: ...C Wymiary osuszacza...
Страница 20: ...D Schemat elektryczny...
Страница 21: ...E Widok rozstrzelony...
Страница 23: ...DESICCANT DRYER Instruction and Maintenance Manual...
Страница 24: ...HGO 40 160 HGL 40 160...
Страница 27: ...B Flow diagram C Dryer dimensions D Wiring diagram E Exploded view F Suggested spares...
Страница 41: ...LIST OF ATTACHMENTS...
Страница 44: ...A C IN L E T O U T L E T IN L E T E B F G D MODEL 40 80 120 160 INLET OUTLET INLET...
Страница 46: ...D WIRING DIAGRAM C CONTROLLER EMV 1 EMV 2 EMV 3 EMV 4 EMV ELECTROMAGNETIC VALVE...
Страница 47: ...E EXPLODED VIEW C PG GG G NRV SV VV VV EMV M...