- 55 -
System setup
General setup
6001
Frequency
48.0Hz – 62.0Hz
6002
Power
10kW – 20000kW
6003
Current
0A – 9000A
6004
Voltage
100V – 25000V
6005
Speed
100 rpm – 4000 rpm
6011
Frequency
48.0Hz – 62.0Hz
6012
Power
10kW – 20000kW
6013
Current
0A – 9000A
6014
Voltage
100V – 25000V
6015
Speed
100 rpm – 4000 rpm
60*1
Frequency
48.0Hz – 62.0Hz
60*2
Power
10kW – 20000kW
60*3
Current
0A – 9000A
60*4
Voltage
100V – 25000V
60*5
Speed
100 rpm – 4000 rpm
6051
U Primary
100V – 25000V
6052
U Secondary 100V – 690V
6071
Type
Island
6081
Type
English Qc
6131
Delay
0.0 s – 990.0 s
6161
Delay
0.0 s – 300.0 s
6162
Output A
Not Used – Option dependent
6163
Output B
Not Used – Option dependent
6164
Enable
Off – On
6165
Failclass
Alarm (1) – Trip MB (6)
** = 00, 01, 02, 03
6000 Nom. settings
6171
Number of Teeth 0 teeth – 500 teeth
6172
Run. detect type
Binary input
MPU input
Frequency
Engine communication
6173
Run. detection
0 rpm – 4000 rpm
6174
Remove starter
1 rpm – 2000 rpm
6181
Start prepare
0.0 s – 600.0 s
6182
Ext. start prepare 0.0 s – 600.0 s
6183
Start ON time
1.0 s – 30.0 s
6184
Start OFF time
1.0 s – 99.0 s
6170 Running detect.
6180 Starter
619 1
Setpoint
1 – 10
6211
Cooldown
0.0 s – 990.0 s
6212
Ext. stop time
1.0 s – 99.0 s
6221
Timer
1.0 s – 99.0 s
6231
GB Close Delay
0.0 s – 30.0 s
6232
GB Load Time
0.0 s – 30.0 s
6261
Input
Multi input 102
Multi input 105
Multi input 108
M-logic
EIC
6262
Start Derate @
0 – 20000
6263
Derate Slope
0.1%/U – 100.0%/U
6264
Enable
Off – On
6265
Derate Limit
0.0% – 100.0%
6190 Start attempts
6210 Stop
6220 Hz/V OK
6230 GB control
6260 Power derate
6010 Nom. settings 2
60*0 Nom. settings *
6050 BB settings p
6070 Gen-set mode
6080 Language
6130 Alarm horn
6160 Run status
6401
Start Hour
0h – 23h
6402
Stop Hour
0h – 23h
6403
Difference
1.0 s – 999.0 s
6404
Set point
0.1Hz – 1.0Hz
6405
Enable
Off – On
6400 Master clock
6281
Output A
Not Used – Option dependent
6282
Output B
Not Used – Option dependent
6283
Enable
Off – On
6284
Failclass
Alarm (1) – Trip MB (6)
6321
Setpoint
20.0˚C – 250.0˚C
6322
Output A
Not Used – Option dependent
6323
Input Type
MI 102
MI 105
MI 108
EIC
6324
Hysteresis
1.0˚C – 70.0˚C
6325
Enable
Off – On
6331
Setpoint
10.0˚C – 250.0˚C
6332
Delay
1.0 s – 300.0 s
6333
Output A
Not Used – Option dependent
6334
Output B
Not Used – Option dependent
6335
Enable
Off – On
6336
Failclass
Alarm (1) – Trip MB (6)
6381
Setpoint
1V – 5V
6391
Type
Adjustable – Selco T4800
6280 Int. comm. fail
6320 Engine heater
6330 Engine heater 1
6380 Load share output
6390 Load share type