Line
Function
Setting range or display
Setting
increment
Basic setting
Additional generator (Boiler connection)
3692
S
With DHW charging
Locked, Substitute,
Complement, Instantly
Substitute
- DHW Instantly :
When DHW request, the HP and the boiler are put into operation. The HP will stop when the primary
return temperature is over 55 °C.
- DHW Substitute :
If the outdoor temperature is above 2 °C, the operation of the HP when DHW request last 5 minutes
at least. The HP operating time can be extended depending on the outdoor temperature. The boiler will activate then.
3700
S
Release below outside temperature
-50... 50 °C
1 °C
2 °C
3701
S
Release above outside temperature
-50... 50 °C
1 °C
--
3705
S
Overrun time
0... 120 min
1 min
0
3720
S
Switching integral (for boiler relief)
0... 500 °Cmin
1 °Cmin
100 °Cmin
3723
S
Locking time
1... 120 min
1 min
--
Domestic hot water (DHW)
5024
S
Differential
0... 20 °C
1 °C
7 °C
5030
S
Limitation on load duration
10... 600 min
10 min
90 min
5055
S
Recooling temp
10... 95 °C
1 °C
65 °C
5057
S
Recooling collector
Off, Summer, Always
Summer
5061
S
Electric immersion heater release
24h / day, Release of DHW,
Programme 4 / DHW
Release of
DHW
5093
S
Not used function
Installation configuration
5700
I
Pre-setting
1,2,3,... 10
1
10
For any configuration installation, the preset is 10.
5710
S
Heating circuit 1
Off, On
Off
For a simple installation (1 radiator circuit only) =
Stop
With 2 circuit kit option (2 circuits or 1 underfloor heating circuit) =
On
5711
S
Cooling circuit 1
Off, System with 4 tubes,
System with 2 tubes
Not used
This parameter must be on
Off
5715
S
Heating circuit 2
Off, On
On
5716
S
Cooling circuit 2
Off, System with 4 tubes,
System with 2 tubes
Not used
This parameter must be on
Off
5731
S
DHW controlling element Q3
No charging request, Charging pump,
Diverting valve
Diverting
valve
5740
S
Output el imm heater K6 (not used)
0,1... 99 kW
1,5 kW
5806
I
Type el imm heater flow
1 : 3-stage, 2 : 2-stage excluding,
3 : 2-stage complementary, 4 : Modulating UX
3 : 2-stage
complementary
5811
S
Output el imm heater K25 (not used)
3 kW
5813
S
Output el imm heater K26 (not used)
3 kW
Installation and commissioning instructions "1485 - EN"
Heat pump alféa hybrid duo gas
- 62 -
Содержание WOYG112LHT
Страница 51: ... Installation and commissioning instructions 1485 EN 51 Heat pump alféa hybrid duo gas ...
Страница 69: ... Installation and commissioning instructions 1485 EN 69 Heat pump alféa hybrid duo gas ...
Страница 90: ...Installation and commissioning instructions 1485 EN Heat pump alféa hybrid duo gas 90 ...
Страница 91: ...Installation and commissioning instructions 1485 EN 91 Heat pump alféa hybrid duo gas ...