10 .3 Start-up data sheet
Site
Installer
Outdoor unit
serial No.
Hydraulic unit
serial No.
model
model
Refrigerant type
Refrigerant charge
kg
Checks
Operating voltage & current on outdoor unit
Compliance with positioning distances
L/N or L1/N
V
Condensate evacuation correct
L2/N
V
Electric connections / connections tightnees
L3/N
V
No GAS leaks (unit ID No. : )
L/T or L1/T
V
Installation of refrigeration connection correct (lenght : m)
L2/T
V
Reading in HEATING operating mode
L3/T
V
Compressor discharge temperature
°C
N/T
V
Liquid line temperature
°C
}
}
}
Icomp
A
Condensation
temperature
HP = bar
°C
sub-cooling
°C
Tank water output temperature
°C
ΔT condensation
°C
Tank water input temperature
°C
ΔT secondary
°C
Evaporation temperature
LP = bar
°C
}
}
}
Suction temperature
°C
Overheating
°C
Battery air input temperature
°C
ΔT evaporation
°C
Battery air output temperature
°C
ΔT battery
°C
Hydraulic system of hydraulic unit
Secondary system
Low temp. heating floor
}
Circulator brand
Type
LT Radiators
fan coils
Domestic hot water ; tank type
Estimated water volume of secondary system
L
Options & accessories :
Power supply for connected electric auxiliary
Room thermostat T37, T55
Operation in cooling mode possible
Wireless room thermostat T58
Location of room sensor correct
Remote control T75
Cooling kit
Wireless remote control T78
2 zone kit
Details
Control settings
Configuration type
Essential settings
Installation and operating manual "1572 - EN"
- 71 -
Heat pump air/water split 2 services alféa excellia duo