1) KEYBOARD function key (with a light)
When the system is powered on, the initial state is that the panel keyboard is closed and the
KEYBOARD light is out. After the KEYBOARD key is pressed or the CTRL , ALT and DEL keys on
the PS/2 keyboard are pressed at the same time, a password input box and a figure selection box
(there will be no figure selection box if login is realized through the PS/2 keyboard) will pop up on
the screen. At this time, user may log in the system after inputting the correct password (for
details, see the instructions on user login). If the system receives the correct password, the panel
keyboard will be opened and the KEYBOARD light will be lit at the same time. When the panel
keyboard is opened, the system will close the keyboard and exit the login after the KEYBOARD
key is pressed or the CTRL , ALT and DEL keys on the PS/2 keyboard are pressed at the same
time.
User’s Tip: If no operations are done on the system for about 10min when the
panel keyboard is opened, the system will exit the login automatically and close the
panel keyboard. All the function keys (all those introduced below) except for the
LOCAL MUTE key can be operated when the panel keyboard is opened only.
2) INTEGRATION function key (with a light)
If the integration control is in the PRHB state, press the INTEGRATION key to switch it to the
PERMIT state. During the process, the INTEGRATION light will be lit. If the IINTEGRATION key
is pressed again, the integration control will be in the PRHB state again and the INTEGRATION
light will go out at the same time. If multiple fire alarm control panels are networked and the
INTEGRATION key on the No.1 fire alarm control panel in the network is pressed, the integration
control states of all the fire alarm control panels will be changed at the same time; if the
INTEGRATION key on any other fire alarm control panel is pressed, only the integration control
state of the fire alarm control panel will be changed. The integration control state will be saved
upon a power failure. In other words, if the system suffers a power failure and is then powered on
again, the integration control state before the power failure will be restored.
User’s Tip: Integration refers to the integration control except for the sounder.
Sounder refers to a kind of linkage control of the system over the alarm bell, the
audible and visual alarm and other alarm devices. These alarm devices are used
extensively in projects and have independent muting operations. In order to simplify
the settings for users, we list the integrations of this sort separately for independent
operations.
3) SOUNDER function key (with a light)
If the sounder control is in the PRHB state, press the SOUNDER key to switch it to the
PERMIT state. During the process, the PERMIT light near the SOUNDER key will be lit. If the
SOUNDER key is pressed again, the sounder control will be in the PRHB state again and the
PERMIT light will go out at the same time. If multiple fire alarm control panels are networked and
the SOUNDER key on the No.1 fire alarm control panel in the network is pressed, the sounder
control states of all the other fire alarm control panels will be changed at the same time to make
them the same as that of the No.1 fire alarm control panel; if the SOUNDER key on any other fire
alarm control panel is pressed, only the sounder control state of the fire alarm control panel will be
changed. The sounder control state will be saved upon a power failure. In other words, if the
system suffers a power failure and is then powered on again, the sounder control state before the
power failure will be restored.
4) MANUAL function key (with a light)
If the MANUAL control of the system is in the PRHB state, press the MANUAL key to switch all
the accessed manual control panels to the PERMIT state. During the process, the PERMIT light
below the MANUAL key will be lit. If the MANUAL key is pressed again, the MANUAL control will
be in the PRHB state again and the PERMIT light will go out at the same time. If multiple fire
alarm control panels are networked and the MANUAL key on the No.1 fire alarm control panel in
the network is pressed, the manual control states of all the other fire alarm control panels will be
changed at the same time to make them the same as that of the No.1 fire alarm control panel; if