1) KEYBOARD function key (with a light)

 

          When the system is powered on, the initial state is that the panel keyboard is closed and the

 

KEYBOARD light is out. After the KEYBOARD key is pressed or the CTRL , ALT and DEL keys on

 

the PS/2 keyboard are pressed at the same time, a password input box and a figure selection box

 

(there will be no figure selection box if login is realized through the PS/2 keyboard) will pop up on

 

the screen. At this time, user may log in the system after inputting the correct password (for

 

details, see the instructions on user login). If the system receives the correct password, the panel

 

keyboard will be opened and the KEYBOARD light will be lit at the same time. When the panel

 

keyboard is opened, the system will close the keyboard and exit the login after the KEYBOARD

 

key is pressed or the CTRL , ALT and DEL keys on the PS/2 keyboard are pressed at the same

 

time.

 

       

User’s Tip: If no operations are done on the system for about 10min when the

 

panel keyboard is opened, the system will exit the login automatically and close the

 

panel keyboard. All the function keys (all those introduced below) except for the

 

LOCAL MUTE key can be operated when the panel keyboard is opened only.

 

2) INTEGRATION function key (with a light)

 

          If the integration control is in the PRHB state, press the INTEGRATION key to switch it to the

 

PERMIT state. During the process, the INTEGRATION light will be lit. If the IINTEGRATION key

 

is pressed again, the integration control will be in the PRHB state again and the INTEGRATION

 

light will go out at the same time. If multiple fire alarm control panels are networked and the

 

INTEGRATION key on the No.1 fire alarm control panel in the network is pressed, the integration

 

control states of all the fire alarm control panels will be changed at the same time; if the

 

INTEGRATION key on any other fire alarm control panel is pressed, only the integration control

 

state of the fire alarm control panel will be changed. The integration control state will be saved

 

upon a power failure. In other words, if the system suffers a power failure and is then powered on

 

again, the integration control state before the power failure will be restored.

 

         

User’s Tip: Integration refers to the integration control except for the sounder.

 

Sounder refers to a kind of linkage control of the system over the alarm bell, the

 

audible and visual alarm and other alarm devices. These alarm devices are used

 

extensively in projects and have independent muting operations. In order to simplify

 

the settings for users, we list the integrations of this sort separately for independent

 

operations.

 

3) SOUNDER function key (with a light)

 

        If the sounder control is in the PRHB state, press the SOUNDER key to switch it to the

 

PERMIT state. During the process, the PERMIT light near the SOUNDER key will be lit. If the

 

SOUNDER key is pressed again, the sounder control will be in the PRHB state again and the

 

PERMIT light will go out at the same time. If multiple fire alarm control panels are networked and

 

the SOUNDER key on the No.1 fire alarm control panel in the network is pressed, the sounder

 

control states of all the other fire alarm control panels will be changed at the same time to make

 

them the same as that of the No.1 fire alarm control panel; if the SOUNDER key on any other fire

 

alarm control panel is pressed, only the sounder control state of the fire alarm control panel will be

 

changed. The sounder control state will be saved upon a power failure. In other words, if the

 

system suffers a power failure and is then powered on again, the sounder control state before the

 

power failure will be restored.

 

4) MANUAL function key (with a light)

 

If the MANUAL control of the system is in the PRHB state, press the MANUAL key to switch all

 

the accessed manual control panels to the PERMIT state. During the process, the PERMIT light

 

below the MANUAL key will be lit. If the MANUAL key is pressed again, the MANUAL control will

 

be in the PRHB state again and the PERMIT light will go out at the same time. If multiple fire

 

alarm control panels are networked and the MANUAL key on the No.1 fire alarm control panel in

 

the network is pressed, the manual control states of all the other fire alarm control panels will be

 

changed at the same time to make them the same as that of the No.1 fire alarm control panel; if

 

- 13 -

 

Содержание ATL-9000 Series

Страница 1: ...m Control Panel Linkage Type ATL 9000 SERIES ATL 9000 2 ATL 9000 4 ATL 9000 6 Angel Technologies Hongkong Ltd Add 3 F South Gate Chuangsheng Building XiIi Twon Yangguang Industrial Zone Nanshan Distri...

Страница 2: ...rations of the system into Chinese The system can realize comprehensive on site programming and solve complicated linkage relation settings The system simulates the operating interfaces of Windows and...

Страница 3: ...arm linkage mode and has a total of 324 intelligent detectors or modules for a single circuit The addresses of the intelligent detectors or modules may be hashed with No 1 to No 324 It is equipped wit...

Страница 4: ...rities making system administration convenient It can realize local or remote software upgrades thus enabling it to operate stably and reliably Executive standards Fire Alarm Control Units GB4717 2005...

Страница 5: ...panel Fire display panel 1 L 1 L PH O NE A LA R M Powersupply PRE SS HER E 1 3 System schematic diagram CFT QGL 9000 CFT QGL 9000 Intelligent 80 L smoke detector 80 L Intelligent heat detector Intell...

Страница 6: ...terface board has two circuits Each of the two circuits can drive 324 intelligent detectors or modules Fire detector The system can be accessed to multiple intelligent smoke heat or composite detector...

Страница 7: ...chnical parameters of the products of the system 1 5 1 Power supplies Main power supply AC 220V 20 50Hz or DC24V Emergency power supply Maintenance free DC24V battery its capacity depends on the syste...

Страница 8: ...mensions of system engineering 2 1 Outline drawing and dimensional drawing of the product Appearance and dimensions of CFT QTL 9000 Main control unit Manual control unit Linkage unit Blank cover Print...

Страница 9: ...Appearance and dimensions of CFT QGL 9000 Host cover Manual control unit Linkage unit Keyboard mouse Printer Blank cover Fig 2 2 Cabinet Dimensions 7...

Страница 10: ...Lashing eye Scale3 1 Lashing eye Scale3 1 Inlet wire Fig 2 3 CFT QBL 9000 diagrammatic sketch 8...

Страница 11: ...key and so on After checking the above do necessary inspections for the appearance of the fire alarm control panel If any non conformities are discovered in the check or inspections call our salesper...

Страница 12: ...he insulation resistances between the buses of different circuits and that between the buses and ground as well as the loads of the circuits The insulation resistances should be larger than 20M and th...

Страница 13: ...ANCEALARM OPERATIONDELAY POWER FAULT HO RN STROBEFAULT C MN AOM U IC TION SURVEILLANCEFAULT SYST TESTEM AUTO MANUAL K OREYB A D ISO TIOLA N GN AE ER LL KGIN A E R ETES SO N ERUDLIN A EKG SELE TC SSE T...

Страница 14: ...en a fire alarm triggers a linkage and it will go out when all the linkage delays have ended and all the linkages have been established It will be lit when a power supply alarm of the fire alarm contr...

Страница 15: ...power failure and is then powered on again the integration control state before the power failure will be restored User s Tip Integration refers to the integration control except for the sounder Sound...

Страница 16: ...larms for the alarm information of the bus equipment The fault information of the interface boards the power supplies the printer the display panels and the communication of the fire alarm control pan...

Страница 17: ...re alarm request feedback area fault area CONFIRM Confirm the activity area fire alarm request feedback area fault area Downward rolling Input the area area password Move the cursor upward SELECT Sele...

Страница 18: ...upy 30 continuous bus module addresses The quantity of the manual control panels that may be accessed to a fire alarm control panel depends on the quantity of the interface boards There are 11 initial...

Страница 19: ...US TNE TR B U STNE TRB U SENT TRB US TNE TR B U STNE TRB U STNE Fig 7 1 Multi line Linkage Control Unit The quantity of the multi line control points that may be accessed depends on the quantity of th...

Страница 20: ...nd d Check whether there are linkage setting data in the linkage setup or not or whether the Register option in the linkage data is selected or not After the system reports a fire alarm linkage may be...

Страница 21: ...rol panel nor slave fire alarm control panel s in the networked system Only after another fire alarm control panel has its number registered can the alarm information of the current fire alarm control...

Страница 22: ...ely The other two yellow lights are respectively the short or open circuit lights for the No 1 circuit and the No 2 circuit There are two circumstances of open circuit Complete open circuit or partial...

Страница 23: ...0 Positive pressure fan 11 Blow valve 12 Air blower 13 Fire damper 14 Fire door 15 Deluge valve 17 Spray pump 18 Stabilizing pump 19 Fire pump 20 Foam pump 21 Water curtain pump 22 Municipal electrici...

Страница 24: ...1 L2 J k1 J k 2 S p 1 S p 2 J k1 J k 2 S p 1 S p 2 J k1 J k 2 S p 1 S p 2 9000 series host Bro a d ca stin g m o d u le Bro a d ca stin g m o d u le Bro a d ca stin g m o d u le 485 Bus Louds peak er...

Страница 25: ...y 485 Bus Fault input 485 bus hub 1 2 3 4 5 6 Remot e B ackup Self control power inspection Publicf ailure Circ uit 1 Circ uit 2 DC2 4 Output Input Output 1 2 3 4 5 6 Broadc as ting c ontroller Broadc...

Страница 26: ...A N interface Constant vol tage i nput 1 Constant vol tage output 1 Constant vol tage i nput 2 Constant voltage output 2 Amplifier failure input 1 2 RS485 A B Line C output GND 24 E CAN CAN HL C asca...

Отзывы: