6.

 

Resetting the GSCM for 60 seconds by shorting terminals 7 and 8 while in the ready mode forces the GSCM back to the 
original factory default settings, as it came out of the box. The adjustment LEDs blink once in sequence to indicate a 
return to default settings. 

7.

 

An alternate set of test adjustments may be selected by performing step 5 above and holding down the change/ store 
button just before releasing the 60 second reset. The change/ store button is then released after the reset jumper is 
removed, three of the ten adjustment LEDs blink. The test parameters are: 

 

Maximum crank = 7 seconds - load delay = 20 seconds - pre-cool off delay = 10 seconds 

 

Battery cut-in delay = 1 minute - battery cut-out delay = 2 minutes- 12 hour run time = 1 hour 

To exit the test parameters operation the user must perform step 5 above to return to factory defaults. 

LED Description and What They Mean 

 

OPERATION LEDS: 

 

Start:  

Continuous = manual start signal received 

 

One blink every 5 seconds = ready to receive a command 

 

Slow blink = auto start mode operation 

 

Fast blink = 60 second delay after reset, before ready mode 

 

Generator Hz Shutdown:  

Fast blink = over speed; slow blink = under speed  

 

Continuous = start function disabled, AC Hz detected 

 

Three slow blinks = run fault, loss of AC feedback signal after load relay has energized 

 

 

Emergency Shutdown:  

Fast blink = high temperature; slow blink = low oil pressure 

 

 

Max. Crank Shutdown:  

Fast blink = max. 4 crank attempts exceeded; slow blink = 12 hour max. runtime exceeded 

 

ADJUSTMENT & TIMING LEDS: 

On continuous = selected for adjustment 

 

 

0-60 Second Crank Delay:  

Blinking = entered crank delay period while glow plug relay K1 energized 

 

 

0-60 Second Maximum Crank:   Blinking = rest period after unsuccessful cranking attempt 

 

 

 

0-60 Second Load Delay:  

Blinking = generator running, delay period before load transfer 

 

 

0-120 Second Load Pre-Off:  

Blinking = load disconnected, cool down period before shutdown 

 

 

 

Battery Charge Cut-In (x12):  

Blinking = battery voltage lower than cut-in point, during 5 minute delay 

 

 

 

Battery Charge Cut-Out (x12):   Blinking = battery voltage greater than cut-out point, during 10 minute delay 

 

 

 

15-75Hz Under Hz Shutdown:   Blinking = generator Hz (under speed) less than trip point, during 10 second delay 

 

 

15-75Hz Over Hz Shutdown:   Blinking = generator Hz (over speed) greater than trip point, during 10 second delay 

 

 

15-75Hz Run/Crank Off:  

Continuous = adjustment selection; no blinking condition 

 

 

0-1 Hour 30 Day Exercise:  

One blink every minute = 30 day exercise option activated; 

 

Fast blink = 60 second warning before 30 day exercise generator starting 

Generator Emergency Shutdown with GSCM 

 

The GSCM Generator Start Controller is NOT AN EMERGENCY SHUTDOWN DEVICE!!  Shorting the reset terminals 7 and 8 
terminates the current GSCM cycle. See GSCM RESET CONDITIONS section. If the manual start signal is removed the generator will 
go through a normal shutdown which may include running for up to two minutes in a load removed cool-down cycle. Also shorting 
reset terminals 7 and 8 will shut down the generator in a normal sequence including the cool-down cycle. If the generator has 
started but is in the load delay period, applying a reset to terminals 7 and 8 will shut down the generator immediately. 

 

A RECOMMENDED EMERGENCY SHUTDOWN SOLUTION is to install a separate “Kill” switch and label it as such. The recommended 
wiring is shown on page 2 of these instructions and also in application 1. Disconnecting the power to the GSCM module will force 
the relays to open. This will shut down generators that require a maintained run signal from K3 (ignition) relay. However this also 
prevents the K4 (shutdown) relay from closing to shut down those generators requiring a momentary stop signal. Using a double 
pole kill switch and wiring the second pole in parallel with the K4 (shutdown) relay terminals will force the generator to stop in an 
emergency situation such as a fuel spill.

 

 

 

 

Содержание A0217

Страница 1: ...Generator Start Control Module Part GSCM Rev C Code Version 5 13 ATKINSON ELECTRONICS INC 14 West Vine Street Murray Utah 84107 ...

Страница 2: ... not already running before trying to start a second or third time Features Applications Automatic starting load transfer and shutdown for gas and diesel generators Off grid generators Automatic adjustable voltage set points for generator battery charging applications 0 60VDC Works with 12 24 or 48V battery systems Provides fault shutdown for low oil pressure high temperature and under speed or ov...

Страница 3: ...e is set at 0 de activated The GSCM provides a 30 day exercise function which can be synchronized with a photo voltaic input to only start each 30 day period at the beginning of the solar charge day A user supplied DC relay can be energized during the 30 day generator exercise to override a battery charger and allow the battery bank to equalize by charging the batteries above the normal charger cu...

Страница 4: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 4 Revised 09 18 GSCM Wiring Diagram ...

Страница 5: ...e maximum crank lockout condition This lockout condition remains until the GSCM is reset by momentarily shorting the reset terminals 7 and 8 together after which the start LED blinks for 60 seconds and then enters ready mode Powering down the GSCM for 5 seconds and powering it back up will also clear the maximum crank lockout condition with the GSCM returning to ready mode 6 When the generator sta...

Страница 6: ...ins 7 and 8 momentarily The open collector transistor terminal 18 will energize a user supplied DC relay not exceeding 180 milliamp coil current whenever a fault shutdown occurs and will de energize the relay when the fault is reset The shutdown conditions are as follows 1 Failure to start with 4 cranking attempts See GSCM STARTING SEQUENCE section 4 5 The max crank max runtime fault LED blinks ra...

Страница 7: ... will shut down the generator and indicate a maximum runtime fault by slowly blinking the max crank max runtime LED See GSCM SHUTDOWN CONDITIONS section 6 This runtime fault is only active in the automatic starting mode 6 The GSCM will clear the max runtime fault if the reset terminals 7 8 are momentarily shorted a manual start signal is applied to terminals 5 6 or a period of 12 hours passes from...

Страница 8: ...e to 0VDC store setting advance to high Hz position and set to zero volts both must be set 9 To re enable the 5 and 10 minute time delays the GSCM must enter adjustment mode as in paragraph 1 of this section and then the cut in and cut out adjustment re entered and stored without the jumper between terminals 15 and 16 Restoring the GSCM factory default values as described in GSCM Reset Conditions ...

Страница 9: ...ad transfer 0 120 Second Load Pre Off Blinking load disconnected cool down period before shutdown Battery Charge Cut In x12 Blinking battery voltage lower than cut in point during 5 minute delay Battery Charge Cut Out x12 Blinking battery voltage greater than cut out point during 10 minute delay 15 75Hz Under Hz Shutdown Blinking generator Hz under speed less than trip point during 10 second delay...

Страница 10: ...rank Delay 5 second minimum 60 seconds Maximum crank time Will not energize starter 60 seconds Load transfer delay Ignition and load relays energize together 60 seconds Load pre off delay Ignition and load relays de energize together 120 seconds Battery charge cut in Ignores automatic battery charge function Switched auto start Battery charge cut out Ignores automatic battery charge function Switc...

Страница 11: ...e generator has reached 30Hz or half speed If this setting doesn t allow the start input to remain engaged long enough for the generator to stay on line adjust the run disconnect setting to 55Hz See GSCM INITALIZATON AND ADJUSTMENT for changing adjustments The K4 shutdown relay provides a momentary stop signal until the generator AC Hz has dropped to zero The K3 ignition relay provides a continuou...

Страница 12: ...rations are shown for both automotive and magneto type with or without fuel valves High speed 3600 RPM generators may need the crank disconnect hertz adjustment set to 20Hz or less to avoid over driving the starter Low Speed Gas Propane Generator with Safeties The low speed gas propane generators also wire the same as in application 2 However the installer should determine ignition type and oil an...

Страница 13: ...ession solenoid furnished with the generator must be wired to K4 shutdown relay to energize on shutdown Automatic Generator Powered AC Pump In this application the GSCM is connected to a pressure or level switch into the battery sense terminals To make the appropriate cut in and cut out adjustments See AUTOMATIC STARTING FOR BATTERY CHARGING section 9 The cut in and cut out adjustments must be set...

Страница 14: ...a special low voltage generator frequency input version for 12V alternator applications GSCM 12V ALT 255 Hz See AUTOMATIC STARTING FOR BATTERY CHARGING section 9 4 9 Generator Powered Air Conditioner The room thermostat should be line voltage slow action type to minimize short cycling signals the generator to start The GSCM K5 load transfer relay starts the air conditioner after the generator is r...

Страница 15: ...ter the GSCM starts the generator with a 3 wire start stop or any other generator starting application to match the type of generator to be controlled If the user desires the voltage from the generator s battery may be connected to the GSCM on terminal 4 and the GSCM will start the generator automatically to charge its own battery when the voltage falls below the battery cut in threshold voltage T...

Страница 16: ...m the date of shipment by Atkinson Electronics Inc or its authorized distributors to the original Customer Atkinson Electronics Inc will repair or replace at our option any defective products provided that our inspection discloses that such defects developed under normal and proper use This warranty does not extend to goods subjected to misuse neglect accident or improper installation or to mainte...

Отзывы: