Automatic Starting for Battery Charging or from Pressure Switch, Etc. 

 

The GSCM monitors a battery voltage of 0 to 60VDC on battery voltage sense terminal 4. This mode is disabled if the voltage on 
terminal 4 is less than 6V, (no connection) or both the cut-in or cut-out voltage adjustment has been set to 5V. 

 

1.

 

The start LED blinks once every 5 seconds to indicate that the GSCM is in ready mode. When the battery voltage 
connected to the battery sense input, terminal 4, drops below the battery voltage cut-in adjustment value, the battery 
cut-in LED begins blinking once a second. The battery voltage must remain below the cut-in adjustment value for 5 
continuous minutes to activate an auto start. If the battery voltage rises above the cut-in adjustment value during the 5 
minute period it clears the timer and starts over. Temporary battery voltage fluctuations such as instantaneous inverter 
loads will not cause the GSCM to start the generator. 

2.

 

Once the battery cut-in timer has reached 5 minutes, it sets the automatic start, indicated by the start LED blinks once 
every 2.5 seconds. The GSCM then enters its start routine with the K4 (shutdown) relay energizes to ensure the generator 
is not running before beginning the cranking sequence. After 7 seconds the K4 relay de-energizes and the GSCM begins its 
cranking routine. See GSCM STARTING SEQUENCE section 1-8. 

3.

 

The GSCM shuts down the generator whenever the battery voltage exceed the cut-out adjustment value for 10 minutes. 
See GSCM STARTING SEQUENCE section: 9-14. The battery cut-out LED blinks during this 10 minute period. The GSCM will 
exit the 10 minute period and shutdown the generator if the battery voltage exceeds the cut-out value by +1VDC (for 12V 
systems, +2 for 24V system, higher voltages are proportional). The generator remains off until started again by the battery 
voltage dropping below the battery cut-in adjustment value. 

4.

 

If the user wishes to disable the 5 minute start delay and 10 minute shutdown delay timers for a battery charging 
application. See GSCM INITALIZATION AND ADJUSTMENT section 6-7

5.

 

If the generator has been running for 12 continuous hours in automatic battery charge mode without the battery voltage 
reaching the cut-out adjustment value, the GSCM will shut down the generator and indicate a maximum runtime fault by 
slowly blinking the max crank/ max runtime LED. See GSCM SHUTDOWN CONDITIONS section: 6. This runtime fault is only 
active in the automatic starting mode. 

6.

 

The GSCM will clear the max runtime fault if the reset terminals 7 & 8 are momentarily shorted, a manual start signal is 
applied to terminals 5 & 6, or a period of 12 hours passes from the time the max runtime fault occurred. 

7.

 

The user can force the GSCM to remain locked out beyond the 12 hours shutdown period by interrupting the battery 
voltage applied to terminal 4 with a normally closed contact DC relay connected to terminal 18 and B. This relay 
will energize during any fault condition requiring a manual reset to clear the fault. (See the wiring diagram on page 2). 

8.

 

Connecting the 12 hour shutdown terminals 15 and 16 together with a jumper wire will allow the generator to continue to 
run indefinitely in automatic battery charge mode if the battery voltage does not reach the battery cut-out adjustment 
value. If the user wishes to only override the current cycle, such as needing more than the 12 hours to initially charge a 
large battery bank, the momentarily connecting the 12 hour shutdown terminals 15 & 16 together while the generator is 
running will allow it to exceed the 12 hour limit on its current cycle, but will reinstate the 12 hour limit for all future 
charge cycles. 

9.

 

There is no maximum runtime shutdown after 12 hours if the manual start input (terminal 5 & 6) is used to start the 
generator. 

10.

 

If the user wishes to have the 12 hour max runtime feature present when starting the generator from a separate pressure 
switch, level switch, thermostat or inverter start contact, etc. to prevent the generator from running indefinitely, all one 
needs to do is; run the battery voltage through previously mentioned device contacts and connect it to the battery sense 
input (terminal 4) and adjusting both the battery cut-in and cut-out values to 5VDC (while in set-up adjustment mode). 
The GSCM will start the generator in automatic start mode and it will run until either the input voltage signal is 
disconnected by the contact opening, the 12 hour max run time limit is reached (as described in paragraphs 5-8) or a fault 
occurs. Any DC voltage greater than 6VDC and less than 60VDC may be used for this mode with the battery cut-in and cut-
out values set to maximum. Terminal 4 switched input applications automatically disables the 5 minute and 10 minute 
start and shutdown delay timers.  

 

 

Содержание A0217

Страница 1: ...Generator Start Control Module Part GSCM Rev C Code Version 5 13 ATKINSON ELECTRONICS INC 14 West Vine Street Murray Utah 84107 ...

Страница 2: ... not already running before trying to start a second or third time Features Applications Automatic starting load transfer and shutdown for gas and diesel generators Off grid generators Automatic adjustable voltage set points for generator battery charging applications 0 60VDC Works with 12 24 or 48V battery systems Provides fault shutdown for low oil pressure high temperature and under speed or ov...

Страница 3: ...e is set at 0 de activated The GSCM provides a 30 day exercise function which can be synchronized with a photo voltaic input to only start each 30 day period at the beginning of the solar charge day A user supplied DC relay can be energized during the 30 day generator exercise to override a battery charger and allow the battery bank to equalize by charging the batteries above the normal charger cu...

Страница 4: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 4 Revised 09 18 GSCM Wiring Diagram ...

Страница 5: ...e maximum crank lockout condition This lockout condition remains until the GSCM is reset by momentarily shorting the reset terminals 7 and 8 together after which the start LED blinks for 60 seconds and then enters ready mode Powering down the GSCM for 5 seconds and powering it back up will also clear the maximum crank lockout condition with the GSCM returning to ready mode 6 When the generator sta...

Страница 6: ...ins 7 and 8 momentarily The open collector transistor terminal 18 will energize a user supplied DC relay not exceeding 180 milliamp coil current whenever a fault shutdown occurs and will de energize the relay when the fault is reset The shutdown conditions are as follows 1 Failure to start with 4 cranking attempts See GSCM STARTING SEQUENCE section 4 5 The max crank max runtime fault LED blinks ra...

Страница 7: ... will shut down the generator and indicate a maximum runtime fault by slowly blinking the max crank max runtime LED See GSCM SHUTDOWN CONDITIONS section 6 This runtime fault is only active in the automatic starting mode 6 The GSCM will clear the max runtime fault if the reset terminals 7 8 are momentarily shorted a manual start signal is applied to terminals 5 6 or a period of 12 hours passes from...

Страница 8: ...e to 0VDC store setting advance to high Hz position and set to zero volts both must be set 9 To re enable the 5 and 10 minute time delays the GSCM must enter adjustment mode as in paragraph 1 of this section and then the cut in and cut out adjustment re entered and stored without the jumper between terminals 15 and 16 Restoring the GSCM factory default values as described in GSCM Reset Conditions ...

Страница 9: ...ad transfer 0 120 Second Load Pre Off Blinking load disconnected cool down period before shutdown Battery Charge Cut In x12 Blinking battery voltage lower than cut in point during 5 minute delay Battery Charge Cut Out x12 Blinking battery voltage greater than cut out point during 10 minute delay 15 75Hz Under Hz Shutdown Blinking generator Hz under speed less than trip point during 10 second delay...

Страница 10: ...rank Delay 5 second minimum 60 seconds Maximum crank time Will not energize starter 60 seconds Load transfer delay Ignition and load relays energize together 60 seconds Load pre off delay Ignition and load relays de energize together 120 seconds Battery charge cut in Ignores automatic battery charge function Switched auto start Battery charge cut out Ignores automatic battery charge function Switc...

Страница 11: ...e generator has reached 30Hz or half speed If this setting doesn t allow the start input to remain engaged long enough for the generator to stay on line adjust the run disconnect setting to 55Hz See GSCM INITALIZATON AND ADJUSTMENT for changing adjustments The K4 shutdown relay provides a momentary stop signal until the generator AC Hz has dropped to zero The K3 ignition relay provides a continuou...

Страница 12: ...rations are shown for both automotive and magneto type with or without fuel valves High speed 3600 RPM generators may need the crank disconnect hertz adjustment set to 20Hz or less to avoid over driving the starter Low Speed Gas Propane Generator with Safeties The low speed gas propane generators also wire the same as in application 2 However the installer should determine ignition type and oil an...

Страница 13: ...ession solenoid furnished with the generator must be wired to K4 shutdown relay to energize on shutdown Automatic Generator Powered AC Pump In this application the GSCM is connected to a pressure or level switch into the battery sense terminals To make the appropriate cut in and cut out adjustments See AUTOMATIC STARTING FOR BATTERY CHARGING section 9 The cut in and cut out adjustments must be set...

Страница 14: ...a special low voltage generator frequency input version for 12V alternator applications GSCM 12V ALT 255 Hz See AUTOMATIC STARTING FOR BATTERY CHARGING section 9 4 9 Generator Powered Air Conditioner The room thermostat should be line voltage slow action type to minimize short cycling signals the generator to start The GSCM K5 load transfer relay starts the air conditioner after the generator is r...

Страница 15: ...ter the GSCM starts the generator with a 3 wire start stop or any other generator starting application to match the type of generator to be controlled If the user desires the voltage from the generator s battery may be connected to the GSCM on terminal 4 and the GSCM will start the generator automatically to charge its own battery when the voltage falls below the battery cut in threshold voltage T...

Страница 16: ...m the date of shipment by Atkinson Electronics Inc or its authorized distributors to the original Customer Atkinson Electronics Inc will repair or replace at our option any defective products provided that our inspection discloses that such defects developed under normal and proper use This warranty does not extend to goods subjected to misuse neglect accident or improper installation or to mainte...

Отзывы: