9
Auxiliary Output
Option #60, #61, #62, #63: Auxiliary Output
Auxiliary Output
Input Option Menu
Option #60, #61, #62, #63: Auxiliary Output
Option Description:
The Setpoint Variable or Process Variable is
transmitted to a remote device (chart recorders, indica-
tors, data recorders, computers, process
controllers, etc.) with 1 of 4 different interfaces:
Option 60: 4-20 mA
Option 61: 1-5 V
Option 62: 0-20 mA
Option 63: 0-5 V
The output signal is scalable in the Auxiliary Output Menu. Multiple remote indicators
may be driven by the controller. However, current and voltage outputs cannot be used
simultaneously.
For current (mA) options, the remote indicators are connected in series. The sum of
the input resistance for all remote indicators must be less than 400 ohms. For voltage
options, the remote indicators are connected in parallel.
The sum of the currents for all remote indicators must be less than 10 mA.