Example of connection cables for gas detector
PW-017 and PW-044 with 4-20 mA output
1
Introduction
It is recommended that all system components are made according to the design created by
person with the necessary skills and competence.
2
Connection cable
In case where project does not specify this, you can use the following types of shielded cables for
connecting gas detectors:
An example of a cable symbol
Approximate external
diameter [mm]
Maximum cable length
[m]
Outdoor installations
Indoor installations
LiYCYv 300/500 V 3x1,0
LiYCY 300/500 V 3x1,0
9,1
155
LiYCYv-Nr 300/500 V 3x1,0 LiYCY-Nr 300/500 V 3x1,0
9,1
155
LiYCYv 300/500 V 3x1,5
LiYCY 300/500 V 3x1,5
9,8
230
LiYCYv-Nr 300/500 V 3x1,5 LiYCY-Nr 300/500 V 3x1,5
9,8
230
It is recommended to use cables with a more accurate, round cross-section, made with the use of pressure
(better sealing in the Ex glands).