www.atestgaz.pl
Maximum quantity Alpa EcoWent XT and Alpa EcoDet XT
detectors by cable type
1
Open loop configuration
Cross-section of
a single cable
conductor
[mm
2
]
Alpa EcoWent XT Gas Detector
System without backup battery supply
(U
IN
= 24 V)
System with backup battery supply
(U
IN(min)
= 20 V)
L1 [m]
L2 [m]
Quantity of detectors
L1 [m]
L2 [m]
Quantity of detectors
0,75
58
628
20
53
533
17
91
631
19
87
537
16
127
637
18
123
543
15
165
645
17
163
553
14
206
656
16
206
566
13
1
63
723
23
75
615
19
96
726
22
109
619
18
131
731
21
146
626
17
168
738
20
186
636
16
207
747
19
229
649
15
1,5
62
872
28
81
741
23
94
874
27
115
745
22
128
878
26
150
750
21
163
883
25
188
758
20
200
890
24
229
769
19
2,5
69
1389
45
53
1193
39
100
1390
44
84
1194
38
133
1393
43
116
1196
37
166
1396
42
150
1200
36
200
1400
41
184
1204
35
Table 1: Maximum quantity of Alpa EcoWent XT detectors – open loop configuration
Atest-Gaz
A. M. Pachole sp. j.
ul. Spokojna 3, 44-109 Gliwice, Poland
VAT No.: PL 9691433231
tel.: +48 32 238 87 94
fax: +48 32 234 92 71
e-mail: [email protected]
p. 1/7
Appendix: PU-Z-098-ENG R04
•
Figure 1: Open loop configuration for Alpa EcoWent XT detectors
Control
unit
Detectors installed 30 m apart
Length L2 [m]
Length L1 [m]
Alpa
EcoWent XT
Alpa
EcoWent XT
Alpa
EcoWent XT