www.atestgaz.pl
Cross-section of
a single cable
conductor
[mm
2
]
A set of one Alpa EcoWent XT Gas Detector and one Alpa EcoDet XT Gas Detector
System without backup battery supply
(U
IN
= 24 V)
System with backup battery supply
(U
IN(min)
= 20 V)
L1 [m]
L2 [m]
Quantity of sets
L1 [m]
L2 [m]
Quantity of sets
0,75
70
319
9
80
267
7
107
325
8
122
278
6
152
339
7
173
298
5
203
359
6
243
337
4
1
58
369
11
56
305
9
93
373
10
93
311
8
133
382
9
135
322
7
177
395
8
185
341
6
229
416
7
249
374
5
1,5
78
451
13
62
373
11
114
456
12
98
378
10
153
464
11
138
387
9
197
477
10
183
432
8
245
494
9
237
424
7
2,5
66
636
20
52
532
17
99
639
19
84
534
16
133
643
18
118
538
15
169
649
17
154
544
14
Table 3: Maximum quantity of sets of Alpa EcoWent XT and Alpa EcoDet XT – open loop configuration
Atest-Gaz
A. M. Pachole sp. j.
ul. Spokojna 3, 44-109 Gliwice, Poland
VAT No.: PL 9691433231
tel.: +48 32 238 87 94
fax: +48 32 234 92 71
e-mail: [email protected]
p. 3/7
Appendix: PU-Z-098-ENG R04
•
Figure 3: Open loop configuration for sets of Alpa EcoWent XT and Alpa EcoDet XT detectors
Length L2 [m]
Control
unit
Detectors sets installed 30 m apart
Length L1 [m]
Alpa
EcoWent XT
Alpa
EcoDet XT
Alpa
EcoWent XT
Alpa
EcoDet XT
Alpa
EcoWent XT
Alpa
EcoDet XT
Содержание Alpa MOD LED8
Страница 1: ...POD 006 ENG R03 User Manual Control Unit Module Alpa MOD LED8 Product code PW 033 A...
Страница 29: ...www atestgaz pl Notes...
Страница 30: ...www atestgaz pl Notes...
Страница 31: ......