Flue gas system
Collective flue gas outlet overpressure
An installation with a collective flue gas outlet over
-
pressure in combination with individually controlled boilers
(e.g. 0
-
10VDC control), where no bus cable is connected, is
NOT
allowed.
Diameter and venting lengths of the flue gas outlet/air supply:
Open system with over
-
pressure.
NOTE!
1. IPX0D at flue category B23 and B33
2. Only with bus cable connected!
3. Adjust parameter 102 to 2
Open system, overpressure
Output (80/60)
d = minimum diameter Ø in mm
[kW]
h = 2
-
5
h = 6
-
10
h = 11
-
15
h = 16
-
20
114
-
240
150
150
150
150
240
-
360
150
150
180
180
360
-
480
180
180
180
200
480
-
600
200
200
220
220
600
-
720
230
230
250
250
720
-
840
260
260
260
260
840
-
960
280
280
280
300
960
-
1200
280
280
280
300