GB
This parameter determines to what extent a deviation of the
room temperature from the specified setvalue has an influence
on the control of the heat generator temperature.
If there is no difference between desired
(SET)
and actual
(ACT)
room temperature, the flow temperature of the heating circuit is
controlled in accordance with the adjusted heating curve.
Should the room temperature deviate from the adjusted setvalue,
the heating characteristic is adjusted on the room temperature
axis in such a way, that the control deviation is compensated. The
size of this displacement thereby depends on the setting of the
room effect.
The following relation applies:
with
Room setcorr = corrected new room setvalue
Room setnom = adjusted room setvalue
Room setcorr = Room setnom -
(
Deviation x Room factor
)
RRCC
PPAARRAAMMEETTEERR 0044
Parameter 4 - Room sensor function
Setting range: OFF, 1. . . 500 %, RC
Factory setting: RC
HHCC
Example:
adjusted room setvalue = 21 °C
actual room temperature = 20 °C
The deviation resulting from this is therefore — 1 K.
The following applies with room factor 100 %:
Room setcorr = 21 °C -
(
-1K x 100
)
= 22 °C
100
The heat generator temperature is controlled in accordance with
a heating characteristic, which complies with a specified room
temperature of 22 °C.
Setting OFF:
completely dependent on the weather
conditions without correcting the room set value
Setting RC:
completely dependent on the room temperature
without any influence of the outside temperature
Important note: High settings reduce the stability of the control
circuit and may lead to fluctuations in room tem-
perature. The setting should be adapted to the
conditions of the room.
next parameter
Page GB-31
100
8A520900_GB.qxp 12.11.2004 13:17 Seite 31
Содержание BrainQ RSC/2
Страница 2: ...NL GB F I Nederlands English...
Страница 36: ...NL Aantekeningen Pagina NL 36 8A520900_NL qxd 12 11 2004 14 46 Seite 36...
Страница 38: ......
Страница 72: ...GB Notes Page GB 36 8A520900_GB qxp 12 11 2004 13 17 Seite 36...
Страница 74: ...Art 0451003403 0445 20...
Страница 75: ...www atagheating com...