Installation
900912-00C, 04/2019
Innovative Hearth Products
Gemini™ -C Series Direct-Vent Gas Fireplaces
43
Table 28 - Air Shutter Adjustment Guidelines
Amount of Primary Air
Flame Color
Air Shutter Adjustment
If air shutter is
closed too far
Flame will
be orange
Air shutter gap should be increased
If air shutter is
open too far
Flame will
be blue
Air shutter gap should be decreased
Air Shutter
Adjustment
Rod Down
(Fully-Open
Position)
Burner
Tube
Adjustment
Rod Up
(Fully-Closed
Position)
Adjustment
Set-Screw
Figure 34 - Air Shutter Adjustment Rod
Figure 35 - Burner Flame Appearance
Table 29 - Main Burner Shutter Opening—Factory Setting
Models
Natural Gas
Propane Gas
All
1/4” (6.35 mm)
1/2” (12.7 mm)
NOTE: When rear venting or running fireplace for an extended period of time the shutter
should be moved to a more open position by pulling rod down. (especially on LP gas)
21.
Install the Hood after fireplace is cool
NOTE: All models must have a hood installed prior to operation.
NOTE: Hood is slotted and has some adjustment incase hood is not
entirely flat. It is suggested that the center screw should be installed
first and the ends last.
1. Attach hood using three screws as shown here.
WARNING
Reinstall any barrier removed before operating the fireplace. The barrier is designed to
reduce the risk of burns from hot glass. Do not operate the fireplace without the barrier
installed.
NOTE: All models must have a barrier installed prior to operation.
22.
Installation / Re-installation of the required facade / barrier
35” / 40” / 45” Logs
1. Move the adjustment rod down to increase air flow and up to decrease it. The rod is located in the lower control
compartment. Position the air shutter to the factory setting (
Table 29
).
2. Light the fireplace. Follow the lighting procedure on the lighting label in the control compartment or
Pages 66-67
.
3. Allow the burner to operate for at least fifteen (15) minutes while observing the flame continuously to ensure that
the proper flame appearance is achieved (
Figure 35
). If the following conditions are present, adjust accordingly.
• If flame appears sooty, adjust the air shutter, incrementally, to a more open position until the proper flame
appearance is achieved.
• If flame remains blue, adjust the air shutter, incrementally, to a more closed position until the proper flame
appearance is achieved.
4. When satisfied that the burner flame appearance is normal. Turn fireplace to the off position, and reinstall the
facade, then proceed to finish the installation.