Astraada DRV-24 frequency inverters Function Parameters
77
Functio
n code
Name
Detailed instruction of parameters
Defaul
t value
Modify
with the rated current of the inverter
LED tens:
0:The inverter continues to work after
underload pre-alarm
1:The inverter continues to work after
underload pre-alarm and the inverter stops to
run after overload fault
2: The inverter continues to work after
overload pre-alarm and the inverter stops to
run after underload fault
3. The inverter stops when overloading or
underloading.
LED hundreds :
0:Detection all the time
1:Detection in constant running
Setting range of P11.09: P11.11~200%
Setting range of P11.10: 0.1~3600.0s
P11.11
Detection
level of the
underload
pre-alarm
If the inverter current or the output current is
lower than P11.11, and its lasting time is
beyond P11.12, the inverter will output
underload pre-alarm.
Setting range of P11.11: 0~P11.09
Setting range of P11.12: 0.1~3600.0s
50%
○
P11.12
Detection
time of the
underload
pre-alarm
1.0s
○
P11.13
Output
terminal
action
selection
during fault
Select the action of fault output terminals on
undervoltage and fault reset.
0x00~0x11
LED ones:
0:Action under fault undervoltage
1:No action under fault undervoltage
LED tens:
0:Action during the automatic reset
1:No action during the automatic reset
0x00
○
P11.14
Speed
deviation
detection
0.0~50.0%
Set the speed deviation detection time.
10.0%
○
P11.15
Speed
deviation
detection
time
This parameter is used to set the speed
deviation detection time.
0.5s
○