Astraada DRV-24 frequency inverters Function Parameters
54
Functio
n code
Name
Detailed instruction of parameters
Defaul
t value
Modify
23: Ramp reference frequency (with sign)
24~30: Reserved
P06.17
Lower limit
of AO1
output
The above function codes define the relative
relationship between the output value and
analog output. When the output value exceeds
the range of set maximum or minimum output,
it will count according to the low-limit or
upper-limit output.
When the analog output is current output,
1mA equals to 0.5V.
In different cases, the corresponding analog
output of 100% of the output value is different.
Please refer to each application for detailed
information.
10V (20mA)
0.0%
100.0%
AO
Setting range of P06.17:-100.0%~ P06.19
Setting range of P06.18:0.00V~10.00V
Setting range of P06.19:P06.17~100.0%
Setting range of P06.20:0.00V~10.00V
Setting range of P06.21:0.000s~10.000s
Setting range of P06.22:-100.0%~ P06.24
Setting range of P06.23:0.00V~10.00V
Setting range of P06.24:P06.22~100.0%
Setting range of P06.25:0.00V~10.00V
Setting range of P06.26:0.000s~10.000s
0.0%
○
P06.18
Correspondi
ng AO1
output to
the lower
limit
0.00V
○
P06.19
Upper limit
of AO1
output
100.0%
○
P06.20
The
correspondi
ng AO1
output to
the upper
limit
10.00V
○
P06.21
AO1 output
filter time
0.000s
○
P06.22
Lower limit
of AO2
output
0.0%
○
P06.23
Correspondi
ng AO2
output to
the lower
limit
0.00V
○
P06.24
Upper limit
of AO2
output
100.0%
○
P06.25
Correspondi
ng AO2
output to
the upper
limit
10.00V
○
P06.26
AO2 output
filter time
0.000s
○
P07 Group Human-Machine Interface
P07.00
User’s
password
0~65535
The password protection will be valid when
setting any non-zero number.
00000: Clear the previous user’s password, and
make the password protection invalid.
After the user’s password becomes valid, if the
0
○