Astraada DRV-24 frequency inverters Function Parameters
67
Functio
n code
Name
Detailed instruction of parameters
Defaul
t value
Modify
2: Valid in the running, clear after receiving the
stop commands
P08.45
UP
terminals
frequency
changing
ratio
0.01~50.00s
0.50 s
○
P08.46
DOWN
terminals
frequency
changing
ratio
0.01~50.00s
0.50 s
○
P08.47
Action
selection at
power loss
0x000~0x111
LED ones: Action selection when power off.
0:Save when power off
1:Clear when power off
LED tens: Action selection when MODBUS set
frequency off
0:Save when power off
1:Clear when power off
LED hundreds:The action selection when other
frequency set frequency off
0:Save when power off
1:Clear when power off
0x000
○
P08.48
High bit of
original
power
consumptio
n
This parameter is used to set the original value
of the power consumption.
The original value of the power consumption
=P08.48*1000+ P08.49
Setting range of P08.48: 0~59999 kWh (k)
Setting range of P08.49:0.0~999.9 kWh
0 kWh
○
P08.49
Low bit of
original
power
consumptio
n
0.0
kWh
○
P08.50
Magnetic
flux braking
coefficient
This function code is used to enable magnetic
flux.
0: Invalid.
100~150: the bigger the coefficient, the bigger
the braking strength.
This inverter can slow down the motor by
increasing the magnetic flux. The energy
generated by the motor during braking can be
transformed into heat energy by increasing the
magnetic flux.
The inverter monitors the state of the motor
continuously even during the magnetic flux
period. So the magnetic flux can be used in the
0
○