After installation of the control replace cover to insure electrical safety and to protect internal parts from the 
environment. 

8.4.3  Differential pressure switch model D7 (low range) 

A single setpoint adjustment nut (7⁄8˝) is located centrally at the bottom on the inside of the enclosure. 
The direction of turning is indicated on a label affixed to the inside of the control enclosure. XG5 controls have a 
setpoint indication scale adjacent to the adjustment nut. To adjust the control, align the top of the adjustment nut hex 
with the indicator line on the scale. Do not force adjustment or attempt to exceed the maximum setting shown on the 
scale or nameplate. 

For accurate setpoint calibration or for controls without a scale mount the control on a calibration stand so that the 
HIGH and LOW pressures expected under operating conditions may be obtained. Suitable reference standards are 
necessary for each pressure. 

 

Note

 – Due to the sensitivity of these controls it is imperative that the LOW pressure side volume be large 

to prevent a setpoint shift between calibration and field installation. If this is not possible, an approximate 
setpoint under operating conditions can be obtained by setting the operating point with the low side open to 
atmosphere. A final setpoint adjustment can be made after installation. 

Apply LOW pressure. Then apply HIGH pressure to the required setpoint and turn the adjustment nut until the switch 
operates. When the setpoint has been achieved, raise and lower HIGH pressure to ensure that the differential 
pressure between the HIGH and LOW pressures is correct. 

After installation of the control, replace the cover to ensure electrical safety and to protect the internal parts from the 
environment. 

8.4.4  Temperature switch model T7 

A single setpoint adjustment nut (7⁄8˝) is located centrally at the bottom on the inside of the enclosure. 
The bulb of the control should be immersed in a bath at the desired setpoint temperature. Optimum performance will 
be obtained if the bulb is fully immersed. Allow five minutes for initial stabilization. 

As received, the temperature switch will normally be set to approximately 90% of the indicated range. After 
stabilization, turn the adjustment nut until switch changes mode. Direction of turning is indicated on a label affixed to 
the inside of the control enclosure. When setpoint has been achieved raise and lower temperature to insure that the 
setpoint is correct. 

After installation of the control replace cover to insure electrical safety and to protect  internal parts from the 
environment. 

8.4.5  B750, D750 and T750 Variable Deadband Switches 

Deadband is varied by rotating the wheel on the precision switch. When viewed from the front of the enclosure, 
rotation to the left increases deadband – rotation to the right decreases deadband. Letters on the wheel may be used 
as a reference. Deadbands obtainable will vary from 0.5% to 9% of pressure or temperature range depending on 
range segment and type of diaphragm. 

Adjustment of Setpoint – As received, the switch will normally be set to approximately 90% of range. Rotate the wheel 
on the MICRO SWITCH all the way to the right; this will provide smallest deadband. Pressurize, or increase bath 
temperature, to the required setpoint and turn the adjustment nut until the switch changes mode. Lower the pressure 
to reset the switch. Rotate the wheel on the MICRO SWITCH until the desired deadband is obtained. The upper 
setpoint will be changing upward with this adjustment. Lower the pressure to reset the switch. Then increase the 
pressure to the desired setpoint and turn the adjusting nut until the switch changes mode. Lower the pressure and 
check resetpoint and deadband. 

8.5  Subsequent relocation of the switch (by the customer) 

Recommendation:

  Do not remove the switch  from one metering point and fit it in a different place, as 

there is a risk of the measuring media being mixed, with unforeseeable chemical reactions. 

 

9  Servicing 

All ASHCROFT switches require little or no maintenance. 

 

Be sure that the case is closed at all times. 

Содержание B7 series

Страница 1: ...del B7 differential pressure switch model D7 and temperature switch model T7 for explosion risk areas pursuant to Directive 94 9 EC ATEX IEC In the following configuration B7 CN pressure switch D7 CN...

Страница 2: ...ical data 7 5 Labeling on the device 7 5 1 Labeling on the device for explosion risk areas ATEX 7 6 Construction and function 7 6 1 Overview 7 6 2 Description of function 7 6 3 Description of componen...

Страница 3: ...19 11 Removal disposal 13 11 1 Safety 13 11 2 Removal 13 11 3 Disposal 14 12 Appendix 14 12 1 Data sheet for switches B7 D7 and T7 14 12 2 EG Declaration of Conformity 15 12 3 IECEX Declaration of con...

Страница 4: ...ality 1 4 Copyright This Operating Manual may only be copied and passed on as a complete document without the special permission of the publisher 1 5 Warranty For the product described here we offer a...

Страница 5: ...al regulations for accident prevention and the operator s internal regulations regarding working operations and safety must be respected The operator is responsible for all specified servicing inspect...

Страница 6: ...32 UNF 2B socket head cap screw The base houses a range of various switch elements and an operating rod The base has three bosses at 90 apart on its side walls The two opposing bosses each contain a N...

Страница 7: ...on and function 6 1 Overview B7 pressure switch D7 differential pressure switch T7 temperature switch Figure 1 6 2 Description of function The Ashcroft pressure switch is a precision built agency appr...

Страница 8: ...This is inherent in the design due to the precise relationship that exists between temperature and pressure according to the vapor pressure laws A wide selection of sensing bulb and armored capillary...

Страница 9: ...tection against special conditions such as vibrations pulsations and pressure spikes A bracket must be installed to support the switch if the metering pipe is not able to provide adequate support Ambi...

Страница 10: ...ust be frost protected Safety notice When tightening control to pressure line always use the wrench flats or hex on the lower housing and do not twist the device itself 8 3 2 Electrical connection Tak...

Страница 11: ...pressure As received the pressure switch will normally be set to approximately 90 of the indicated range Pressurize the system to required setpoint and turn the adjustment nut until switch changes mod...

Страница 12: ...a bath at the desired setpoint temperature Optimum performance will be obtained if the bulb is fully immersed Allow five minutes for initial stabilization As received the temperature switch will norma...

Страница 13: ...nance Never use aggressive solvents Do not use high pressure water to clean the switch 10 Faults 10 1 Safety Defective or faulty switches put the operational safety and process safety of the plant at...

Страница 14: ...pose of or recycle the devices and components used in accordance with the applicable regulations 12 Appendix 12 1 Data sheet for switches B7 D7 and T7 More detailed datasheets are available direct fro...

Страница 15: ...Page 15 of 19 12 2 EG Declaration of Conformity...

Страница 16: ...Page 16 of 19 12 3 IECEX Declaration of conformity...

Страница 17: ...Page 17 of 19...

Страница 18: ...Page 18 of 19...

Страница 19: ...Page 19 of 19...

Отзывы: